Foutcodes VänEE Airco


Hier staan 33 foutcodes uit 2 handleidingen van VänEE Airco, met de betekenis zoals die in de handleidingen staat en de modellen waarin de code voorkomt. Via een model open je de handleiding zelf.

Code Betekenis Modellen
E01 E01 Supply damper range STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the V180E75RT, V150H75NS
E02 E02 Supply damper timeout damper system). Plug unit. V180E75RT, V150H75NS
E03 E03 Supply damper If STEP 1 did not x the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any V180E75RT, V150H75NS
E05 E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the V180E75RT, V150H75NS
E06 E06 Exhaust damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical V180E75RT, V150H75NS
E07 E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any V180E75RT, V150H75NS
E09 E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the V180E75RT, V150H75NS
E10 E10 Recirculation damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical V180E75RT, V150H75NS
E11 E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any V180E75RT, V150H75NS
E22 E22 Supply airow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean lters, distribution registers and outside supply hood. Inspect V180E75RT, V150H75NS
E23 E23 Supply motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear V180E75RT, V150H75NS
E24 E24 Supply motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection. V180E75RT, V150H75NS
E25 E25 Supply motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly. V180E75RT, V150H75NS
E26 E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4) V180E75RT, V150H75NS
E27 E27 Supply motor (drive foc duration) the ventilation wheel from any dirt or obstacles. If STEP 2 did not x the problem, perform STEP 3: Disconnect J2 (white) and V180E75RT, V150H75NS
E28 E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower. V180E75RT, V150H75NS
E29 E29 Supply motor (startup) assembly. V180E75RT, V150H75NS
E32 E32 Exhaust airow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean lters, distribution registers and outside exhaust hood. Make V180E75RT, V150H75NS
E33 E33 Exhaust motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear the V180E75RT, V150H75NS
E34 E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection. V180E75RT, V150H75NS
E35 E35 Exhaust motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly. V180E75RT, V150H75NS
E36 E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4) V180E75RT, V150H75NS
E37 E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles. V180E75RT, V150H75NS
E38 E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower. V180E75RT, V150H75NS
E39 E39 Exhaust motor (startup) assembly. E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with V180E75RT, V150H75NS
E40 E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7A V180E75RT, V150H75NS
E41 E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7B V180E75RT, V150H75NS
E42 E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures V180E75RT, V150H75NS
E43 E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4) V180E75RT, V150H75NS
E50 E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove wall control from V180E75RT, V150H75NS
E51 E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Replace the wall control. V180E75RT, V150H75NS
E60 E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, lters). 21 V180E75RT, V150H75NS