Foutcodes VänEE Airco
Hier staan 33 foutcodes uit 2 handleidingen van VänEE Airco, met de betekenis zoals die in de handleidingen staat en de modellen waarin de code voorkomt. Via een model open je de handleiding zelf.
| Code | Betekenis | Modellen |
|---|---|---|
| E01 | E01 Supply damper range STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the | V180E75RT, V150H75NS |
| E02 | E02 Supply damper timeout damper system). Plug unit. | V180E75RT, V150H75NS |
| E03 | E03 Supply damper If STEP 1 did not x the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any | V180E75RT, V150H75NS |
| E05 | E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the | V180E75RT, V150H75NS |
| E06 | E06 Exhaust damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical | V180E75RT, V150H75NS |
| E07 | E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any | V180E75RT, V150H75NS |
| E09 | E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the | V180E75RT, V150H75NS |
| E10 | E10 Recirculation damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical | V180E75RT, V150H75NS |
| E11 | E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any | V180E75RT, V150H75NS |
| E22 | E22 Supply airow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean lters, distribution registers and outside supply hood. Inspect | V180E75RT, V150H75NS |
| E23 | E23 Supply motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear | V180E75RT, V150H75NS |
| E24 | E24 Supply motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection. | V180E75RT, V150H75NS |
| E25 | E25 Supply motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly. | V180E75RT, V150H75NS |
| E26 | E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4) | V180E75RT, V150H75NS |
| E27 | E27 Supply motor (drive foc duration) the ventilation wheel from any dirt or obstacles. If STEP 2 did not x the problem, perform STEP 3: Disconnect J2 (white) and | V180E75RT, V150H75NS |
| E28 | E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower. | V180E75RT, V150H75NS |
| E29 | E29 Supply motor (startup) assembly. | V180E75RT, V150H75NS |
| E32 | E32 Exhaust airow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean lters, distribution registers and outside exhaust hood. Make | V180E75RT, V150H75NS |
| E33 | E33 Exhaust motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear the | V180E75RT, V150H75NS |
| E34 | E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection. | V180E75RT, V150H75NS |
| E35 | E35 Exhaust motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly. | V180E75RT, V150H75NS |
| E36 | E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4) | V180E75RT, V150H75NS |
| E37 | E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles. | V180E75RT, V150H75NS |
| E38 | E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower. | V180E75RT, V150H75NS |
| E39 | E39 Exhaust motor (startup) assembly. E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with | V180E75RT, V150H75NS |
| E40 | E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7A | V180E75RT, V150H75NS |
| E41 | E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7B | V180E75RT, V150H75NS |
| E42 | E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures | V180E75RT, V150H75NS |
| E43 | E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4) | V180E75RT, V150H75NS |
| E50 | E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove wall control from | V180E75RT, V150H75NS |
| E51 | E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Replace the wall control. | V180E75RT, V150H75NS |
| E60 | E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, lters). 21 | V180E75RT, V150H75NS |