Bekijk gratis de handleiding van VänEE V180E75RT (52 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 108 mensen en kreeg gemiddeld 4.3 sterren uit 7 reviews. Heb je een vraag over VänEE V180E75RT of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/52
USER AND INSTALLER MANUAL
INSTALLER: READ THESE INSTRUCTIONS
SAVE THEM FOR USER
1107074 rev. C
VB0359
VB0360
REGISTER YOUR PRODUCT ONLINE AT:
www.venmar.ca/register-your-product.html or
www.vanee.ca/en/register-your-product.html
For additional information, visit venmar.ca or vanee.ca
A180H75rT*
A180E75RT*
A230H75RT*A230H75RS*
A210E75RT*A210E75RS*
v180H75rT*
V180E75RT*
V230H75RT*V230H75RS*
V210E75RT*V210E75RS*
Venmar Ventilation ULC, 550 Lemire Blvd., Drummondville, Québec, Canada J2C 7W9 venmar.ca / vanee.ca 800-567-3855
*THese producTs eArned THe enerGY
sTAr
®
bY meeTinG sTricT enerGY efficiencY
GuidelinesseTbYnATurAlresourcescAnAdA
AndTHeus epA. THeY meeTenerGY sTAr
requiremenTsonlYwHenusedin cAnAdA.

Beoordeel deze handleiding

4.3/5 (7 Beoordelingen)

Product specificaties

Merk: VänEE
Categorie: Airco
Model: V180E75RT

Foutcodes VänEE V180E75RT

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing
C1 Group C1, residential occupancies, Group D2, business and personal services occupancies,
E01 E01 Supply damper range STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the
E10 E10 Recirculation damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical
E11 E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any
E02 E02 Supply damper timeout damper system). Plug unit.
E22 E22 Supply airow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean lters, distribution registers and outside supply hood. Inspect
E23 E23 Supply motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear
E24 E24 Supply motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection.
E25 E25 Supply motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly.
E26 E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)
E27 E27 Supply motor (drive foc duration) the ventilation wheel from any dirt or obstacles. If STEP 2 did not x the problem, perform STEP 3: Disconnect J2 (white) and
E28 E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower.
E29 E29 Supply motor (startup) assembly.
E03 E03 Supply damper If STEP 1 did not x the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any
E32 E32 Exhaust airow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean lters, distribution registers and outside exhaust hood. Make
E33 E33 Exhaust motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear the
E34 E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection.
E35 E35 Exhaust motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly.
E36 E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)
E37 E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles.
E38 E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower.
E39 E39 Exhaust motor (startup) assembly. E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with
E40 E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7A
E41 E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7B
E42 E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures
E43 E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)
E05 E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the
E50 E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove wall control from
E51 E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Replace the wall control.
E06 E06 Exhaust damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical
E60 E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, lters). 21
E07 E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any
E09 E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the