Bekijk gratis de handleiding van Salus NPC1B (1 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.4 sterren uit 4 reviews. Heb je een vraag over Salus NPC1B of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/1

C.H. PUMP CONTROLLER
Model: NPC1B
04/2026
Introduction
Product compliance
Product description
Wiring diagram
Alarm
Controller operation
Histeresis
Safety information
The NPC1B controller is designed to control a water pump in a central
heating or domestic hot water circuit, or to act as a safety thermostat.
The controller allows the user to set both the pump’s start and stop
temperatures. The pump will start when the user-set temperature ‘C’ is
exceeded, and will stop when the set stop temperature ‘U’ is exceeded.
1.
Power supply indicator
2.
C.H. pump operation indicator
3.
Display
4.
Increasing setpoint temperature
or value
5.
Menu button
6.
Decreasing setpoint
temperature or value
7.
Temperature sensor
8.
Pump power supply
9.
Controller power supply
10.
ON/OFF power
supply switch
The temperature controller is tted with an alarm that is triggered
when the temperature detected by the sensor exceeds 90 °C.
You can change the pump start-up temperature setting by pressing
the button (options menu). The letter ‘C’ will appear on the display.
You can now adjust the temperature setting using the or buttons.
After a few seconds, the controller will return to normal operating
mode and display the measured temperature.
This is the dierence between the temperature at which the controller
starts the pump and the temperature at which it stops it. The
controller has a xed hysteresis of 2 °C.
For example:
1.When parameter ‘C’ is set to 30 °C, the pump starts when the
measured temperature exceeds 30 °C and stops when the measured
temperature falls below 28 °C.
2. When parameter ‘U’ is set to 50 °C, the pump will stop when the
measured temperature exceeds 50 °C and will start when the
measured temperature falls below 48 °C.
Use in accordance with the regulations in force in your country and
within the EU. The device must be used for its intended purpose.
It must not be used in conditions where water vapour condensation
occurs, nor must it be exposed to water.
This product is for indoor use only.
The controller must be installed by a qualied person, in accordance
with the regulations in force in the relevant country and within the
EU. Before carrying out any work involving the power supply
(connecting cables, installing the device, etc.), ensure that the
controller is not connected to the mains! Incorrect connection of
cables may damage the controller.
www.saluscontrols.com
SALUS Control is a member of the Computime Group.
In line with its policy of continuous product development, SALUS Controls reserves the
right to change the specications, design and materials of the products listed in this
brochure without prior notice.
MANUFACTURER:
SALUS Controls plc,
Units 8-10,
Northeld Business Park,
Forge Way, Parkgate
Rotherham, S60 1SD, UK
DE / NL: [email protected]
IMPORTER:
Salus Controls
European Distribution sp.z o.o.
ul. Szamocka 8, piętro 6.,
01 748 Warszawa,
Poland
Technical specications
Input rated voltage230 V / 50Hz ±10%
Rated frequency2 W
Working temperature-10 / +50°C
Max load of the pump output
Temperature measurement range
6 A
0 - 99°C
Setpoint temperature range5 - 80°C
Sensor temperature range−10 – 120 °C
Sensor cable length1,2 m
123
789
10
4
5
6
[°C]
ARMLA
(sound alarm)
PUMP OPERATION
Note
U – the pump switches o above this temperature
C – the pump is switched on above this temperature
Additional features
The controller also features functions designed to prevent the pump
from becoming blocked. The ‘anti-stop’ function protects against
limescale build-up outside the heating season.
The pump runs for 15 seconds every 14 days. Another safety feature is
the ‘anti-freeze’ function, which keeps the pump running continuous-
ly when the temperature measured by the sensor drops below 5°C.
Manual mode
Ta funkcja pozwala sprawdzić, czy pompa działa prawidłowo.
Pompa uruchomi się po jednoczesnym naciśnięciu przycisków i .
Aby zatrzymać pompę, należy ponownie nacisnąć te same przyciski.
You can change the pump cut-o temperature by pressing
button twice (options menu). The ‘U’ setting follows the ‘C’ setting.
The letter “U” will ash on the display. At this point, you can change
the set “U” temperature using the or buttons. After a few
seconds, the controller will return to normal operation and display the
measured temperature.
1. Central power supply
2. Domestic hot water
or safety thermostat
NPBC1
NPBC1
This product complies with the following European directives: GPSR
2023/988/EU, EMC 2014/30/EU, LVD 2014/35/EU, RoHS 2017/2102/EU,
and SVHC 215. The full text of the EU Declaration of Conformity is available
at the following web address: www.saluslegal.com
PN-EN 60730-1:2016-10+A1:2019-07+A2:2022-10
PN-EN IEC 60730-2-9:2019-06+A1:2019-06+A2:2021-01
PN-EN 61000-3-2:2019-04+A1:2021-08
PN-EN 61000-3-3:2013-10+A1:2019-10+A2:2022-04
PN-EN 50419:2023-05
PN-EN IEC 63000:2019-01
QUICK GUIDE
MULTILANGUAGE
MANUAL
MULTILANGUAGE
MANUAL
Product specificaties
| Merk: | Salus |
| Categorie: | Niet gecategoriseerd |
| Model: | NPC1B |
Heb je hulp nodig?
Als je hulp nodig hebt met Salus NPC1B stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Salus
5 September 2026
3 September 2026
2 September 2026
1 September 2026
1 September 2026
1 September 2026
1 September 2026
1 September 2026
3 Oktober 2025
4 September 2025
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026
4 September 2026