Kyoritsu KEW 2055 Handleiding


Pagina's 2 Engels Multimeter

Bekijk de handleiding van Kyoritsu KEW 2055 gratis online of download de PDF. Deze handleiding is 23 keer bekeken. Vraag over dit model? Stel een vraag

INSTRUCTION MANUAL
DIGITAL CLAMP METER
KEW 2055
1.Features
●
Designedtomeetinternationalsafetystandards.
 
IEC61010-1.IEC61010-031:2002&IEC61010-2-032
 
MeasurementCategory(CAT)IV600V
 
PollutionDegree2
●
Double molded main body provides comfortable
singlehandedgrip
 
●
DataHoldFunction
●
LCD Backlight function to facilitate working at
dimlylitsituations.
●
RELfunctiontoindicatemeasurementvariation.
 
(Current,voltage,Resistancemeasurement)
●
MIN/MAX functionenables easyreading ofmin &
maxvalueduringmeasurement.
●
WithContinuity&DiodeCheckFunction
●
NCV
(
Non Contact Voltage
)
Function for wiring
check.
●
600Vinputprotection.
●
Sleepfunctiontoextendbatterylife.
●
WithBarGraph,6039counts
2. Safety Warnings
This instrument has been designed, manufactured and
testedaccordingtoIEC61010:Safetyrequirementsfor
Electronic Measuring apparatus, anddelivered in
the best condition after passed the inspection. This
instructionmanual contains warningsand safety
rules which must be observedby the user to ensure
safeoperation of the instrument and retain it in safe
condition.
Therefore, readthrough theseoperating instructions
beforeusingtheinstrument.
 
WARNING
●
Read throughand understandthe instructions
contained inthis manual before usingthe
instrument.
●
Keepthemanual at handto enable quick
referencewhenevernecessary.
●
Theinstrumentistobeusedonlyinitsintended
applications.
●
U n d e r s t a n da n df o l l owa l lt h es a f e t y
instructionscontainedinthemanual.
Failure tofollow the instructions may cause injury,
instrument damage and/or damage toequipment
undertest. Kyoritsu isby no meansliable for
any damage resultingfrom the instrument in
contradictiontothiscautionarynote.
Thesymbol indicatedontheinstrumentmeansthat
theusermustrefertotherelatedpartsinthemanual
forsafe operation ofthe instrument. It isessential to
readthe instructions whereverthesymbol appears
inthemanual.

DANGER is reserved for conditions and actions
that are likely to cause serious or fatal injury.

WARNING is reserved for conditions and actions
that can cause serious or fatal injury.

CAUTION is reserved for conditions and actions
that can cause injury or instrument damage.
●
Marks listed in the table below are usedon this
instrument.
Usermustrefertothemanual.
Instrumentwithdoubleorreinforcedinsulation
Indicates that this instrument can clampon
bareconductorswhenmeasuring avoltage
corresponding to the applicablemeasurement
category,whichismarkednexttothissymbol.
AC
 DC
AC&DC
Thisinstrumentsatisfiesthemarkingrequirement
defined inthe WEEE Directive (2002/96/EC).
This symbol indicates separate collection for
electricalandelectronicequipment.
 
DANGER
●
Never make measurement on a circuit in which
voltageoverAC600Vexists.
●
Donot attempt to makemeasurementin the
presenceof flammable gasses. Otherwise, the use
of the instrument may cause sparking, whichcan
leadtoanexplosion.
●
Transformerjawtips aredesignednot toshort
the circuit under test. If equipment under test
hasexposed conductive parts,however, extra
precaution shouldbe takento minimize the
possibilityofshorting.
●
Neverattempttousetheinstrumentifitssurface
oryourhandiswet.
●
Donot exceed the maximumallowable input of
anymeasuringrange.
●
N e ve rop e nt h eB a t t e ry c ov e rd u ri n ga
measurement.
●
The instrument is to beused only in its intended
applications orconditions.Otherwise, safety
functionsequippedwiththeinstrumentdoesn
twork,
and instrumentdamageorseriouspersonalinjury
maybecaused.
●
Verify proper operation ona known source before
use ortaking actionas a result indicationof the
instrument.
●
Keepyourfingersandhandsbehindtheprotective
fingerguardduringmeasurement.
 
WARNING
●
Never attempt to make measurement if any
abnormal conditions, such as broken case and
exposedmetalpartsarefoundontheinstrument.
 
●
Do notrotate the FunctionSwitch while the test
leadsarebeingconnected.
●
Do not install substitute parts or make any
modification totheinstrument. Forrepair or
re-calibration, returnthe instrumentto yourlocal
distributorfromwhereitwaspurchased.
●
Donot try to replace the batteries if the surface
oftheinstrumentiswet.
●
Disconnect all thecordsandcables from the
object under test and poweroffthe instrument
before openingtheBattery Coverfor Battery
replacement.
●
Verify proper operation ona known source before
useortakingactionasaresultoftheindicationof
theinstrument.
●
Use appropriate personal protective equipment
such asinsulating gloves, Insulating boots, and
safetyglasses.
●
Stop using the test lead if the outer jacketis
damaged and the inner metal orcolor jacket is
exposed.
 
CAUTION
●
SettheFunctionSwitchtoanappropriateposition
beforestartingmeasurement.
 
●
Firmlyinsertthetestleads.
 
●
Disconnectthetestleadsfromtheinstrumentfor
currentmeasurement.
 
●
Do not exposethe instrument to the directsun,
hightemperatureandhumidityordewfall.
 
●
Altitude 2000m or less. Appropriate operating
temperatureiswithin0
℃
and40
℃
.
●
This instrument isn
t dust & water proofed. Keep
awayfromdustandwater.
●
Be sure to power off theinstrument after use.
Whentheinstrumentwill notbein usefora long
period,placeit in storage after removing the
batteries.
●
Use a cloth dipped in water or neutraldetergent
for cleaning the instrument. Do not use abrasives
orsolvents.
Measurement Category
To ensuresafe operationof measuring instruments,
IEC 61010establishes safety standardsfor various
electrical environments,categorized as Oto CATIV,
and calledmeasurement categories.Higher-numbered
categories correspondto electrical environments with
greatermomentary energy,so a measuringinstrument
designedforCAT III environmentscanendure greater
momentaryenergythanonedesignedforCATII.
O
:Circuits whichare notdirectly connected
tothemainspowersupply.
CAT II
:Electrical circuits of equipmentconnected
toanACelectricaloutletbyapowercord.
CAT III
:Primary electrical circuits of the
equipment connected directly to the
distribution panel,and feeders fromthe
distributionpaneltooutlets.
CAT IV
:Thecircuit from theservice dropto the
service entrance,and to the power meter
andprimaryover-currentprotectiondevice
(distributionpanel).
3. Specification
3-1. Measuring range & accuracy
(accuracyguaranteedat23
℃ ±
5
℃
.humidity45
〜
85%)
ACCurrent600A,1000AFunction
Function Measuring
Range Accuracy
600A 0-600.0A
±
1.5%rdg
±
5dgt
(50/60Hz)
±
3.5%rdg
±
8dgt
(40-400Hz)
1000A 0-1000A
DCCurrent600A,1000AFunction
Function Measuring
Range Accuracy
600A
0-600.0A
±
1.5%rdg
±
5dgt
1000A
0-1000A
ACVoltageFunction

(
Auto-ranging,Inputimpedance:approx.10M
Ω)
Range Measuring
Range Accuracy
6/60/600V 1-600.0V
±
1.3%rdg
±
4dgt(50/60Hz)
±
3.0%rdg
±
5dgt(40
〜
400Hz)
DCVoltageFunction

(
Auto-ranging,Inputimpedance:approx.10M
Ω)
Range Measuring
Range Accuracy
600mV/6/
60/600V 0-600.0V
±
1.0%rdg
±
3dgt
Resistance
(
Continuity/DiodeCheck
)
Function
Range Measuring
Range Accuracy
600
Ω
/6k/
60k/600k
Ω
6M
Ω
0-6M
Ω ±
1.0%rdg
±
5dgt
60M
Ω
6.00M-
60.00M
Ω±
5%rdg
±
8dgt
ContBuzzer 0-600.0
Ω
Thresholdvalue:60
Ω±
30
Ω
Diode Testvoltage:0-2V
Frequency/ DUTYFunction
(
Auto-ranging for
Frequency
)
Range Measuring
Range Accuracy
ACA 40Hz
−
400Hz
±
0.5%rdg
±
5dgt
ACV 1Hz
〜
10kHz
0.1-99.9%
(Pulsewidth/Pulseperiod)
±
2.5%rdg
±
5dgt
Note:Measurableinputsare:40Vrms@ACVor
60Arms@AC600A,350A@AC1000ARange
3-2. General Specification
●
Modeofoperation
 
:
Δ
∑mode
●
Display 
 
:max.6039counts

(Frequency:9999)&Bargraph
●
Over-range indication:"OL" displayed when exceeding
the measuring range. (except for AC/DCV and 1000A
Function)
●
Rangeswitching :
 
Auto-ranging/Voltage,ResistanceRange
 
Singlerange/Continuity,Diodecheckand
DUTY
●
Samplerate
:threetimespersecond
●
Functionalconstruction:
 
OFF/ACA/DCA/ACV/DCV/
Ω
●
Keys :
 
SELECT(AC/DCswitching&/
Ω
/ /),REL
Δ
,
 
Hz/DUTY,MIN/MAX,HOLD/BackLight
●
Powersource :DC3V/R03(UM-4)x2pcs
●
Lowbatterywarning
:
" "markisdisplayedat
 
2.4V
±
0.15Vorless.
●
Temperature & humidity: 23
℃ ±
5
℃
,relative humidity
accuracyguaranteed85%orless(nocondensation)
●
Operatingtemperature:0
〜
40
℃
,relativehumidity
 
&humidityrange85%orless(nocondensation)
●
Storagetemperature :-20
〜
60
℃
,relativehumidity
 
&humidityrange85%orless(nocondensation)
●
Currentconsumption:approx.12mA
●
SleepFunction:Automaticallypoweredoffinabout
 
15minafterthelastFunctionswitchoperation.
 
Pressany key or rotate the Function Switch from
OFFtoanypositiontoexitfromtheSleepstate.
●
Locationforuse
Outdooruse,Altitudeupto2000m
●
ApplicableStandards
 
IEC61010-1,61010-2-032,61010-2-033
 
MeasurementCATIV600VPollutiondegree2
 
IEC61010-031
 
EMC
:
EN61326-1
 ・
EN55022
 ・
EN61000-4-2(performancecriterionB)
 ・
EN61000-4-3(performancecriterionB)
●
RoHS
:
EN50581
●
OverloadProtection
 
CurrentRange :1200AAC/DC/10sec
 
VoltageRange :720VAC/DC/10sec
 
ResistanceRange :600VAC/DC/10sec
●
WithstandVoltage
 
6720VAC
(
TRMS50/60Hz
)
/5sec
 
(betweenJawsandelectricalcircuit/betweeninternal
 
circuitandenclosure)
●
InsulationResistance:10M
Ω
ormore/1000V
 (
betweenelectricalcircuitandenclosure
)
●
Conductorsize
 
approx.40mm
●
Dimension
 
approx.254(L)
×
82(W)
×
36(D)mm
●
Weight:approx.:310g
●
Accessories
 
 
TestLeads Model7066A/1set
 
BatteryR03
(
UM-4
)
/2pcs
 
InstructionmanualEnglish,Japanese/1pce
 
CarriyngCaseModel9094/1pcs
3-3. Function Keys
The"
●
"markshowsavailablefunctionateachRange.
DCCurrentMeasurement
HOLD SELECTZEROHz/
DUTY MAX/
MIN
ACA
●●●●●
ACV
●
-
●●●
DCA
●●●
-
●
DCV
●
-
●
-
●
Ω●●●
-
●
-
●
---
-
●
---
4. Preparation for measurement
4-1. Checking Battery Voltage
Set theFunctionSwitch toanyposition otherthan
"
OFF
".When thedisplayis clearwithout  "
BATT
" mark,
showing, batteryvoltage is enough. When the display
is blankor
 
 "
BATT
" mark isindicated,replacethe
batteriesaccordingtoSection7,BatteryReplacement.
 
CAUTION
The Sleepfeature automaticallypowers the
instrumentoffinabout 15minafterthe lastswitch
or key operation. Therefore, the display may be
blankevenwiththeFunctionSwitchsettoaposition
other than "
OFF
". Tooperate theinstrument in this
case, turn the switch back to the  "
OFF
"  position,
thentoanyotherposition,orpressanykey.Replace
the batteriesifnothingwasdisplayed afterabove
operations.
4-2. Checking Switch Setting & Operation
Confirm the Function Switch is set to the correct
position,the instrument isset to thecorrect
measurementmode,
and the Datahold function is disabled. Otherwise,
desiredmeasurementcannotbemade.
5. Measurement
5-1. AC Current Measurement
 
DANGER
●
Nevermake measurement on a circuit in which
voltage over AC600V exists to avoid getting
electricalshock.
●
Transformer jaw tips are designed not to short
the circuit under test. Ifequipment under testhas
exposedconductiveparts,however,extraprecaution
shouldbe taken to minimize the possibility of
shorting.
●
Do not make measurement with the Battery Cover
removed.
●
Disconnect the test leadsfrom the instrument for
currentmeasurement.
●
Keep yourfingersand handsbehindthe barrieron
theinstrumentduringameasurement.
(1)Set theFunction Switchto "
600A
" or"
1000A
"
position.
AChasbeenselectedbydefault;presstheSELECT
key, whenDC hasbeenselected, tochangeit to
AC.AC mark isdisplayed at theupper left onthe
display.
(2)Pressthetriggertoopenthetransformerjawsand
clampthemontotheoneconductorundertest,then
take thereading on the display. Pressing the "
Hz/
DUTY
" Key switches the indication in following
sequence.
AC Current
⇨
Hz
⇨
DUTY
Hz/DUTY
 Function requires 60A ormore at AC600A
Rangeand350AormoreatAC1000Arange.
 
CAUTION
●
Max conductorsize for KEW2055 isapprox
dia. 40mm. Duringcurrent measurement, keep
the trans former jaws fully closed.Other wise,
accuratemeasurementscannotbetaken.
5-2. DC Current Measurement
 
DANGER
●
Never make measurementon a circuitin which
voltage overDC600Vexists toavoid getting
electricalshock.
●
DonotmakemeasurementwiththeBatteryCover
removed.
●
Keepyourfingersandhandsbehindthebarrieron
theinstrumentduringameasurement.
(1)Set theFunction Switchto "
600A
" or"
1000A
"
position. AC has been selected by default; press
the SELECT key, when AC has been selected, to
changeittoDC.
DC mark isdisplayed atthe upperleft on the
display.
Barrier
O: Device which is
not directly
connected to the
mains power supply
Protectivefingerguard(Barrier)
:
Itisapartprovidingprotection againstelectrical
shock and ensuring theminimum required airand
creepagedistances.
Cap
:
UncappedconditionforCATIIenvironment
CappedconditionforCATIII/IVenvironments
TheCapshuldbefirmlyattachedtotheprobes.
Whenthe instrument and the testlead are combined
andusedtogether,whicheverlowercategoryeitherof
thembelongstowillbeapplied.
Cap
Protective fingerguard

Beoordeel deze handleiding


Product specificaties

Merk: Kyoritsu
Categorie: Multimeter
Model: KEW 2055

Heb je hulp nodig?

Als je hulp nodig hebt met Kyoritsu KEW 2055 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden