Foutcodes Gree CAS18HP230V1AC

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing Pagina
C5 System Configuration C5 1) No jumper cap inserted on the control board Malfunction 2) Incorrect or damaged jumper cap on control board 30
E1 System High Pressure E1 1) Over charged with refrigerant 2) Blocked or dirty outdoor coil 30
E2 Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow and 1 sec Off 2) Indoor fan speed is too low 30
E3 Low Pressure Protection E3 9 flashes 1) Low on refrigerant and 1 sec Off 2) Pressure sensor is damaged 30
E4 Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and 1 sec Off temperature, overload) in service manual 30
E5 Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable and 1 sec Off 2) Supply voltage is too low and system load is too high 30
E6 Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units 30
E7 Mode conflict (Indoor units E7 Operation status calling for simultaneously 30
E8 High Temperature E8 6 flashes 1) Incorrect refrigerant charge level Resistant Protection and 1 sec Off 2) Refrigerant metering device malfunction 31
E9 Cold Air Protection E9 1) Indoor coil has not reach minimum heating temperature 2) Indoor ambient is abnormally cold 31
F0 Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s) and 1 sec Off 2) Indoor coil temperature sensor no calibrated 31
F1 Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor ambient temperature sensor damaged 31
F2 Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor coil temperature sensor damaged 31
F3 Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor ambient temperature sensor damaged 31
F4 Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor coil temperature sensor damaged 31
F5 Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Discharge temperature sensor damaged 31
F6 Compressor Overload Protection - F6 3 flashes 1) Incorrect refrigerant charge Frequency Decrease/Limit Mode and 1 sec Off 2) Metering device malfunction 31
F7 Oil Return Protection - Frequency F7 Normal function status code only Decrease/Limit Mode 31
F8 System Current Overload Protection - F8 1 flashes 1) Input voltage too low Frequency Decrease/Limit Mode and 1 sec Off 2) System pressure too low 31
F9 High Compressor Discharge F9 2 flashes and 4 flashes 1) Cooling load is too great Temperature - Frequency 1 sec Off and 1 sec Off 2) Outdoor ambient temperature too high 32
H1 Defrost Mode in Heating H1 Operation status Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose 32
H3 Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose and 1 sec Off 2) Refer to the malfunction analysis in Service Manual 32
H5 IPM Module Protection H5 4 flashes 1) IPM module over heating and 1 sec Off 2) Improper or Low voltage at the IPM module 32
H6 Indoor DC Fan Motor H6 1) Loose connections between fan motor and control board Malfunction 2) Fan motor or blower wheel bearings malfunction 32
H7 Compressor De-Synchronized H7 1) Compressor voltage is not balance Malfunction 2) Control board malfunction 32
L1 High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac and 1 sec Off 2) Capacitor on control board malfunction 33
L9 High Input Power Protection L9 9 flashes 1) Compressor malfunction and 1 sec Off 2) Power circuit malfunction 32
P5 Compressor Phase Current P5 1) IPM module malfunction Protection 2) Outdoor control board malfunction 33
P7 Module Temperature Sensor P7 Outdoor control board malfunction Malfunction 33
P8 Module Temperature Protection P8 1) Lack of thermal grease on IPM module 2) Heat sink (radiator) not tightly mounted 33
U1 Compressor Phase-Current U1 Outdoor control board malfunction Detection Malfunction 33
U3 DC Bus Voltage Dip U3 Outdoor control board malfunction Input Current Detection Malfunction U5 Outdoor control board malfunction 33
U5 Input Current Detection Malfunction U5 Outdoor control board malfunction The four-way valve is abnormal U7 Hardware malfunction 33
U7 The four-way valve is abnormal U7 Hardware malfunction Zero cross detection circuit U8 Hardware malfunction 33
U8 Zero cross detection circuit U8 Hardware malfunction malfunction(for indoor unit) 33

Alle foutcodes Gree Airco