Foutcodes Gree Airco
Hier staan 174 foutcodes uit 53 handleidingen van Gree Airco, met de betekenis zoals die in de handleidingen staat en de modellen waarin de code voorkomt. Via een model open je de handleiding zelf.
| Code | Betekenis | Modellen |
|---|---|---|
| F1 | Binnenlucht temperatuursensor open/kortsluitingook: Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor ambient temperature sensor damaged | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, ETAC-15HP265V30A, ETAC2-09HC265VA-CP, CAS12HP230V1AC +38 andere |
| F2 | Binnenspoel sensor open of kortsluitingook: Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board Sensor Malfunction 2) Indoor coil temperature sensor damaged | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, ETAC-15HP265V30A, ETAC2-09HC265VA-CP, CAS12HP230V1AC +38 andere |
| E1 | Systeemhoge drukook: System High Pressure E1 1) Over charged with refrigerant 2) Blocked or dirty outdoor coil | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, ETAC-15HP265V30A, ETAC2-09HC265VA-CP, CAS12HP230V1AC +33 andere |
| F4 | Buitenspoel sensor open/kortsluitingook: Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor coil temperature sensor damaged | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, ETAC-15HP265V30A, ETAC2-09HC265VA-CP, CAS12HP230V1AC +30 andere |
| E6 | Communicatiestoringook: Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, Free Match GWHD(24)NK3GO +28 andere |
| C5 | Systeemconfiguratiestoringook: System Configuration C5 1) No jumper cap inserted on the control board Malfunction 2) Incorrect or damaged jumper cap on control board | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, Inverter GWH 09 KF-K3DNA6G +26 andere |
| E5 | Overstroombeveiligingook: Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable and 1 sec Off 2) Supply voltage is too low and system load is too high | VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, Inverter GWH 09 KF-K3DNA6G, Free Match GWHD(24)NK3GO +26 andere |
| H3 | Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose and 1 sec Off 2) Refer to the malfunction analysis in Service Manualook: Compressor overbelastingsbescherming | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, Free Match GWHD(24)NK3GO +25 andere |
| F0 | Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s) and 1 sec Off 2) Indoor coil temperature sensor no calibratedook: Abnormale status van de airconditioner; de temperatuurindicator op de binnenunit knippert om de foutcode weer te geven. | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, XE7C-24 +24 andere |
| E8 | High Temperature E8 6 flashes 1) Incorrect refrigerant charge level Resistant Protection and 1 sec Off 2) Refrigerant metering device malfunctionook: Beveiliging tegen hoge temperatuurweerstand | VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, Inverter GWH 09 KF-K3DNA6G, VIR12HP230V1BO +23 andere |
| F3 | Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Outdoor ambient temperature sensor damagedook: Storing sensor omgevingstemperatuur buitenunit | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, XE7C-24 +23 andere |
| E4 | Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and 1 sec Off temperature, overload) in service manualook: Compressor Hoge Uitlaattemperatuur Beveiliging | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, XE7C-24 +22 andere |
| F5 | Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board Sensor Malfunction and 1 sec Off 2) Discharge temperature sensor damagedook: Storing uitlaattemperatuursensor | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, XE7C-24 +21 andere |
| E2 | Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow and 1 sec Off 2) Indoor fan speed is too lowook: Antivriesbeveiliging binnenunit | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, CAS12HP230V1AC, VIR12HP115V1BH, XE7C-24 +20 andere |
| P5 | Compressor Phase Current P5 1) IPM module malfunction Protection 2) Outdoor control board malfunctionook: Over stroom beveiliging | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, VIR12HP115V1BH, XE7C-24, Free Match GWHD(24)NK3GO +17 andere |
| P8 | Module temperatuurbeschermingook: Module Temperature Protection P8 1) Lack of thermal grease on IPM module 2) Heat sink (radiator) not tightly mounted | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, VIR12HP115V1BH, XE7C-24, Free Match GWHD(24)NK3GO +17 andere |
| H6 | Indoor DC Fan Motor H6 1) Loose connections between fan motor and control board Malfunction 2) Fan motor or blower wheel bearings malfunctionook: Abnormale status van de airconditioner; de temperatuurindicator op de binnenunit knippert om de foutcode weer te geven. | GTH 36 K3FI-GUHD 36 NM3FO, CAS12HP230V1AC, Inverter GWH 09 KF-K3DNA6G, Free Match GWHD(24)NK3GO, GIST12BXAE +16 andere |
| P7 | Module Temperature Sensor P7 Outdoor control board malfunction Malfunctionook: Storing temperatuursensor module. Oorzaak: storing besturingsprint buitenunit. | GTH 36 K3FI-GUHD 36 NM3FO, VIR36HP230V1BO, VIR12HP115V1BH, Free Match GWHD(24)NK3GO, VIR12HP230V1BO +16 andere |
| U8 | Zero cross detection circuit U8 Hardware malfunction malfunction(for indoor unit)ook: Abnormale status van de airconditioner; de temperatuurindicator op de binnenunit knippert om de foutcode weer te geven. | Inverter GWH 09 KF-K3DNA6G, XE7C-24, Free Match GWHD(24)NK3GO, XK41, GIC818A +13 andere |
| L9 | High Input Power Protection L9 9 flashes 1) Compressor malfunction and 1 sec Off 2) Power circuit malfunctionook: Hoge Ingangssprung Beveiliging | CAS12HP230V1AC, XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), XK41 +11 andere |
| E3 | Low Pressure Protection E3 9 flashes 1) Low on refrigerant and 1 sec Off 2) Pressure sensor is damagedook: Lage druk beveiliging compressor | GTH 36 K3FI-GUHD 36 NM3FO, CAS12HP230V1AC, XE7C-24, Free Match GWHD(24)NK3GO, UMAT36HP230V1AF +10 andere |
| H5 | IPM Module Protection H5 4 flashes 1) IPM module over heating and 1 sec Off 2) Improper or Low voltage at the IPM moduleook: IPM module beveiliging | GTH 36 K3FI-GUHD 36 NM3FO, CAS12HP230V1AC, XE7C-24, Free Match GWHD(24)NK3GO, XK41 +9 andere |
| L1 | High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac and 1 sec Off 2) Capacitor on control board malfunctionook: Indoor Fan Protection | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +9 andere |
| EE | EEPROM-geheugenstoringook: Buitendeel geheugen chip storing | VIR12HP230V1AH, VIR30HP230V1AH, Vireo VIR12HP115V1AH, All Match DUC09HP230V1R32AH, WK-010WC1 +8 andere |
| H7 | Compressor De-Synchronized H7 1) Compressor voltage is not balance Malfunction 2) Control board malfunctionook: Hc PFC Beveiliging | GTH 36 K3FI-GUHD 36 NM3FO, CAS12HP230V1AC, XE7C-24, Free Match GWHD(24)NK3GO, XK41 +8 andere |
| L3 | Water Full Protectionook: Beveiliging water vol | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), XK41, GMV-ND72PH/B-T(U) +8 andere |
| LC | Opstart beveiligingook: Elektrische verwarmings PCB fout | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), Free Match GWHD(42)NK3AO +8 andere |
| PH | Bescherming tegen hoge DC-busspanningook: BUS hoog spanning beveiliging | VIR12HP230V1AH, GWHD18NK3KO, VIR30HP230V1AH, 660 GFH09EA-K3DNA1A-I, Vireo VIR12HP115V1AH +8 andere |
| PL | Bescherming tegen lage DC-busspanningook: BUS laag spanning beveiliging | VIR12HP230V1AH, GWHD18NK3KO, VIR30HP230V1AH, 660 GFH09EA-K3DNA1A-I, Vireo VIR12HP115V1AH +8 andere |
| E7 | Mode conflict (Indoor units E7 Operation status calling for simultaneouslyook: Modusconflict | CAS12HP230V1AC, Free Match GWHD(24)NK3GO, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +6 andere |
| H1 | Defrost Mode in Heating H1 Operation status Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is looseook: Ontdooiingsmodus in verwarming | CAS12HP230V1AC, XE7C-24, Free Match GWHD(24)NK3GO, XK41, DUCT18HP230V1AD +6 andere |
| L0 | Binnenunit foutook: Indoor Unit Error | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +6 andere |
| LA | Incompatibiliteit binnenunitook: Indoor Units Incompatibility Jumper Cap Error | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), Free Match GWHD(42)NK3AO +6 andere |
| PU | Storing condensatorladingook: Laad lus beveiliging | VIR12HP230V1AH, GWHD18NK3KO, VIR30HP230V1AH, 660 GFH09EA-K3DNA1A-I, Vireo VIR12HP115V1AH +6 andere |
| E9 | Cold Air Protection E9 1) Indoor coil has not reach minimum heating temperature 2) Indoor ambient is abnormally coldook: Condens bak vol | GTH 36 K3FI-GUHD 36 NM3FO, CAS12HP230V1AC, UMAT36HP230V1AF, XK41, DUCT18HP230V1AD +5 andere |
| Fo | Koelmiddel recovery mode (speciale mode)ook: Pompen of koudemiddel Verzameling Status | VIR12HP230V1AH, GWHD18NK3KO, VIR30HP230V1AH, 660 GFH09EA-K3DNA1A-I, Vireo VIR12HP115V1AH +5 andere |
| L2 | E-heater Protectionook: L2 E-heater Protection db Debugging Code | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +5 andere |
| L4 | Wired Controller Power Supply Errorook: Fout voeding bedrade bediening | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +5 andere |
| L5 | L5 Anti-Frosting Protection y1 Sensor 2 Errorook: Inlaatleiding temperatuursensorfout voor vrijesbescherming | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +5 andere |
| L7 | No Master Indoor Unit Errorook: L7 y3 Error Sensor 2 Error | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +5 andere |
| L8 | Power Insufficiency Protectionook: Beveiliging onvoldoende vermogen | XE7C-24, GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +5 andere |
| U1 | Compressor Phase-Current U1 Outdoor control board malfunction Detection Malfunctionook: U2 Loss/Phase U1 Current Circuit Detecting Reversal/Out of Phase Error | XE7C-24, Free Match GWHD(24)NK3GO, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +5 andere |
| C0 | Communicatiefoutook: Communication Error | XE7C-24, GMV-ND48A/B-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U), GMV-ND36ZD/A-T(U) +4 andere |
| dA | Binnenunit netwerkadresfoutook: Indoor Unit PC-Board Error | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +4 andere |
| dC | DIP Switch instellingsfoutook: Wired Controller PC-Board Error | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +4 andere |
| dE | Indoor Unit CO2 Sensor Errorook: Fout CO2-sensor binnenunit | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +4 andere |
| dH | Outlet Air Temperature Sensor Errorook: Fout printplaat bedrade bediening | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +4 andere |
| dL | Fout temperatuursensor uitblaasluchtook: Incompatibiliteit binnenunit | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +4 andere |
| U3 | DC Bus Voltage Dip U3 Outdoor control board malfunction Input Current Detection Malfunction U5 Outdoor control board malfunctionook: U3 Protection of Power C1 expansion board | XE7C-24, Free Match GWHD(24)NK3GO, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +4 andere |
| U7 | The four-way valve is abnormal U7 Hardware malfunction Zero cross detection circuit U8 Hardware malfunctionook: $ weg klep beveiliging | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +4 andere |
| d1 | Indoor Unit PCB Errorook: Fout printplaat binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +3 andere |
| d3 | Ambient Temperature Sensor Errorook: Omgevingstemperatuursensorfout | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +3 andere |
| d4 | Fout temperatuursensor inlaatleidingook: Binnenunit CO2 sensorfout | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +3 andere |
| d6 | Outlet Pipe Temperature Sensor Errorook: Fout temperatuursensor uitlaatleiding | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +3 andere |
| d8 | Watermperatuursensorfoutook: Water Temperature Sensor Error | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +3 andere |
| F7 | Oil Return Protection - Frequency F7 Normal function status code only Decrease/Limit Modeook: Olieterugkeer Beveiliging - Frequentie Afname/Limit Modus | CAS12HP230V1AC, XE7C-24, Free Match GWHD(24)NK3GO, DUCT18HP230V1AD, DUCT09HP230V1AD +3 andere |
| P6 | Communicatie storing tussen controle en driver bordook: Lc Startup Failure P6 Communication Error | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, Free Match GWHD(24)NK3GO, XK41, GWHD18NK3KO +3 andere |
| P9 | Nul punt beveiligingook: P9 AC Contactor Protection b7 Sensor Error | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, Free Match GWHD(24)NK3GO, XK41, GWHD18NK3KO +3 andere |
| AJ | Filterschoonmaakherinneringook: Filter Cleaning Reminder | GMV-ND15TS/A-T(U), WK-010WC1, GMV-ND48A/B-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U) +2 andere |
| F6 | Compressor Overload Protection - F6 3 flashes 1) Incorrect refrigerant charge Frequency Decrease/Limit Mode and 1 sec Off 2) Metering device malfunctionook: Compressor Overbelasting Beveiliging - Frequentie Afname/Limit Modus | CAS12HP230V1AC, XE7C-24, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +2 andere |
| F8 | System Current Overload Protection - F8 1 flashes 1) Input voltage too low Frequency Decrease/Limit Mode and 1 sec Off 2) System pressure too lowook: Systeem Stroom Overbelastingsbeveiliging - Frequentie Afname/Limit Modus | CAS12HP230V1AC, XE7C-24, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +2 andere |
| F9 | High Compressor Discharge F9 2 flashes and 4 flashes 1) Cooling load is too great Temperature - Frequency 1 sec Off and 1 sec Off 2) Outdoor ambient temperature too highook: Hoge Compressor Uitlaattemperatuur - Frequentie Afname/Limit Modus | CAS12HP230V1AC, XE7C-24, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD +2 andere |
| d7 | Vochtigheidssensorfoutook: Water Temperature Error | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U), GMV-ND09PHS/B-T(U) +1 andere |
| d9 | Fout jumperkapook: Jumper Cap fout | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND72PH/B-T(U) +1 andere |
| HC | Power Factor Correction (PFC) Beveiligingook: PFC fout (drive error) | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, GWV35EG, Free Match GWHD(42)NK3AO, WK-010WC1 +1 andere |
| LH | Waarschuwing Lage Luchtkwaliteitook: Low Air Quality Warning | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND18A/A-T(U), GMV-ND12PHS/B-T(U), GMV-ND09PHS/B-T(U) +1 andere |
| P0 | Driver reset beveiligingook: Fy P0 Sensor Error Error | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, Free Match GWHD(24)NK3GO, GWHD18NK3KO, Free Match GWHD(42)NK3AO +1 andere |
| U5 | Input Current Detection Malfunction U5 Outdoor control board malfunction The four-way valve is abnormal U7 Hardware malfunctionook: U5 Compressor Drive C3 and inverter fan motor | XE7C-24, XK41, DUCT18HP230V1AD, DUCT09HP230V1AD, CAS18HP230V1AC +1 andere |
| dy | Water Temperature Sensor Errorook: Wattemperatuursensorfout | GMV-ND15TS/A-T(U), GMV-ND72PH/B-T(U), GMV-ND12PHS/B-T(U), GMV-ND09PHS/B-T(U), GMV-NDX54P/A-T |
| LE | Compressor stalling (drive error)ook: Compressor blokkering beveiliging | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| LF | Over-speed (drive error)ook: Voeding beveiliging | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| Pd | Sensor aansluiting beveiligingook: Beveiliging sensoraansluiting | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| PE | Beveiliging temperatuurdriftook: Temperatuur drift beveiliging | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| PF | Elektrische box sensor storingook: Lucht temp. sensor drive board defect (drive error) | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| PP | Ingang Spanning beveiligingook: AC ingang spanning niet juist (drive error) | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| b5 | Vloeistofklep Spoel Temperatuur Sensor Storingook: Unit ingang temp. sensor storing (binnen) | CAS12HP230V1AC, GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO |
| b7 | Gaskleptemperatuur sensor is open/kortgeslotenook: Unit uitblaas temp. sensor storing (binnen) | CAS12HP230V1AC, GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO |
| db | Speciale code: debugcode voor veldgebruikook: Field Debugging Code | GMV-ND15TS/A-T(U), GMV-ND42A/A-T(U), GMV-ND48A/B-T(U), GMV-ND18A/A-T(U) |
| E0 | Condens pompook: E0 Outdoor Unit Error J9 Ratio Protection | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, GMV-ND15TS/A-T(U), WK-010WC1 |
| Ld | Fase weg (drive error)ook: Fase compressor ontbreekt | GWHD18NK3KO, 660 GFH09EA-K3DNA1A-I, Free Match GWHD(42)NK3AO, GTH 36 K3FI-GUHD 36 NM3FO |
| PA | AC stroom beveiligingook: AC stroom beveiliging (drive error); weergegeven als E5 | GWHD18NK3KO, Free Match GWHD(42)NK3AO, WK-010WC1, GTH 36 K3FI-GUHD 36 NM3FO |
| FJ | Een sensor is defect.ook: Fout luchtuitlaattemperatuursensor binnenunit | 26TTW09AC115V1A, 26TTW12HP230V1A, WK-010WC1 |
| H4 | Overbelastingook: H4 Overload Protection L3 Outdoor Fan 1 Error ODU AC Current System Low Pressure | GTH 36 K3FI-GUHD 36 NM3FO, XE7C-24, WK-010WC1 |
| Pc | Stroom Driver foutook: Stroom sensor beveiliging (drive error) | GWHD18NK3KO, Free Match GWHD(42)NK3AO, GTH 36 K3FI-GUHD 36 NM3FO |
| 13 | Unit A binnen temp. sensor uitblaas storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 14 | Unit A binnen temp. sensor inlaat storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 15 | Unit A binnen temp. sensor ruimte storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 16 | Unit A mode conflict | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 17 | Unit A invries beveiliging | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 23 | Unit B binnen temp. sensor uitblaas storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 24 | Unit B binnen temp. sensor inlaat storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 25 | Unit B binnen temp. sensor ruimte storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 26 | Unit B mode conflict | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 27 | Unit B invries beveiliging | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 33 | Unit C binnen temp. sensor uitblaas storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 34 | Unit C binnen temp. sensor inlaat storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 35 | Unit C binnen temp. sensor ruimte storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 36 | Unit C mode conflict | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 37 | Unit A invries beveiliging (zoals vermeld in tabel 16) | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 41 | Unit D communicatie storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 42 | Unit D binnen temp. sensor midden storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 43 | Unit D binnen temp. sensor uitblaas storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 44 | Unit D binnen temp. sensor inlaat storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 45 | Unit D binnen temp. sensor ruimte storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 46 | Unit D mode conflict | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 47 | Unit D invries beveiliging | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 51 | Unit E communicatie storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 52 | Unit E binnen temp. sensor midden storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 53 | Unit E binnen temp. sensor uitblaas storing | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| 57 | Unit E invries beveiliging | GWHD18NK3KO, Free Match GWHD(42)NK3AO |
| C1 | U3 Protection of Power C1 expansion boardook: Fout binnenomgevingstemperatuursensor | XE7C-24, WK-010WC1 |
| C2 | U4 C2 Refrigerant and inverter compressorook: Fout leidingtemperatuursensor binnenunit | XE7C-24, WK-010WC1 |
| C3 | U5 Compressor Drive C3 and inverter fan motorook: Fout leidingtemperatuursensor buitenunit | XE7C-24, WK-010WC1 |
| C4 | U6 Valve Abnormal Alarm C4 Unitook: Fout jumperkap buitenunit | XE7C-24, WK-010WC1 |
| C6 | U8 C6 Malfunction of Outdoor Unitook: Fout persgastemperatuursensor | XE7C-24, WK-010WC1 |
| C7 | U9 C7 Malfunction Communication Errorook: Fout middelste leidingtemperatuursensor buitenunit | XE7C-24, WK-010WC1 |
| C8 | C8 Switch/Jumper Cap Uo ambient temperature orook: Afwijking DIP-schakelaar compressor | XE7C-24, WK-010WC1 |
| dn | Verkeerde verbinding van communicatiedraad of storing van elektronische expansieklepook: Expansieventiel defect of communicatiefout | 660 GFH09EA-K3DNA1A-I, CAS12HP230V1AC |
| EA | Alarm koudemiddellekkageook: Koelmiddellekbeveiliging binnenunit | All Match DUC09HP230V1R32AH, WK-010WC1 |
| En | Module Fase Stroom Beveiliging - Frequentie Afname/Limit Modusook: Frequentie beperkt door IPM-stroombeveiliging | 660 GFH09EA-K3DNA1A-I, CAS12HP230V1AC |
| EU | Module Temperatuur Beveiliging - Frequentie Afname/Limit Modusook: Frequentie beperkt door IPM-temperatuurbeveiliging | 660 GFH09EA-K3DNA1A-I, CAS12HP230V1AC |
| FH | Binnenkoudwisselaar Bevriezing Beveiliging - Frequentie Afname/Limit Modusook: Frequentie beperkt door antibevriezingsbeveiliging | 660 GFH09EA-K3DNA1A-I, CAS12HP230V1AC |
| FP | Vorstbeveiliging (Freeze Guard) | ETAC-09HC265V20A, ETAC-15HC265V20A |
| H2 | J6 H2 current Protection Board Power Supplyook: Beveiliging lage moduletemperatuur | XE7C-24, WK-010WC1 |
| HE | Compressor Demagnetisatie Beveiligingook: Demagnetisatiebeveiliging compressor | 660 GFH09EA-K3DNA1A-I, CAS12HP230V1AC |
| L6 | L6 Mode Conflict y2 Sensor 2 Errorook: Modelconflict - Temperatuursensor fout uitgangsleiding | XE7C-24, GMV-ND36ZD/A-T(U) |
| LP | Binnen en buitendeel passen niet samen | 660 GFH09EA-K3DNA1A-I, GTH 36 K3FI-GUHD 36 NM3FO |
| o0 | Aandrijvingsfout binnenunitook: Overige aandrijvingsstoring | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o1 | Watertemperatuurfoutook: Lage busspanning van binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o2 | IPM module beveiligingsfout binnenunitook: Hoge busspanning van binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o3 | Hoge busbar spanning binnenunitook: IPM-modulebeveiliging van binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o4 | Opstartfout binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o5 | Overstroombeveiliging binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o6 | Stroomdetectie circuitfout binnenunitook: Storing stroomdetectiecircuit van binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o7 | Desynchronisatiebescherming binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o8 | Hoge temperatuur binnenunit moduleook: Communicatiestoring van aandrijving binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| o9 | Communicatiefout binnenunit aandrijvingook: Communicatiestoring van hoofdmaster van binnenunit | GMV-ND48A/B-T(U), GMV-ND15TS/A-T(U) |
| oA | Communicatiefout binnenunitook: Oververhitting van module binnenunit | GMV-ND15TS/A-T(U), GMV-ND48A/B-T(U) |
| ob | Temperatuursensiorfout binnenunit moduleook: Storing temperatuursensor van module binnenunit | GMV-ND15TS/A-T(U), GMV-ND48A/B-T(U) |
| oC | Laadcircuitfout binnenunitook: Storing laadcircuit van binnenunit | GMV-ND15TS/A-T(U), GMV-ND48A/B-T(U) |
| U2 | U2 Code/Jumper Cap C0 communication between Setting Error indoor unit and wiredook: Faseverlies | XE7C-24, WK-010WC1 |
| 5h | time for timer OFF, set the time change at the interval of 0.5h and then press “Menu/OK” button to save the setting. If not save the | XE7C-24 |
| 55 | Unit E binnentemperatuursensor inlaat storing | Free Match GWHD(42)NK3AO |
| 56 | Unit E binnentemperatuursensor ruimte storing | Free Match GWHD(42)NK3AO |
| A0 | Moet nog in bedrijf gesteld (gedebugd) worden | GMV-ND15TS/A-T(U) |
| A1 | Beveiliging IPM-module aandrijving inverter-buitenventilator | WK-010WC1 |
| A3 | Ontdooien / olieretour | GMV-ND15TS/A-T(U) |
| A4 | Ontdooien / olieretour | GMV-ND15TS/A-T(U) |
| A6 | Communicatiefout aandrijving buitenventilator | WK-010WC1 |
| A8 | Hoge temperatuur module buitenventilator | WK-010WC1 |
| A9 | Sensorfout aandrijving buitenventilator | WK-010WC1 |
| Ab | Resetbeveiliging aandrijving buitenventilator | WK-010WC1 |
| AC | Opstartfout inverter-buitenventilator | WK-010WC1 |
| Ad | Faseverliesbeveiliging buitenventilator | WK-010WC1 |
| AE | Fout stroomdetectiecircuit aandrijving inverter-buitenventilator | WK-010WC1 |
| AH | Hoge spanning bus buitenventilator | WK-010WC1 |
| AL | Lage spanning bus buitenventilator | WK-010WC1 |
| b2 | Fout luchtinlaattemperatuursensor subkoeler | WK-010WC1 |
| b3 | Fout luchtuitlaattemperatuursensor subkoeler | WK-010WC1 |
| CA | Fout temperatuursensor inlaatleiding verdamper | WK-010WC1 |
| Cb | Fout temperatuursensor uitlaatleiding verdamper | WK-010WC1 |
| CE | Fout binnentemperatuur- of vochtigheidssensor | WK-010WC1 |
| CJ | Fout jumperkap binnenunit | WK-010WC1 |
| EH | Beveiliging tegen verkeerd gebruik van elektrische bijverwarming | WK-010WC1 |
| FE | Koelmiddelsensorfout/communicatiefout koelmiddelsensor | WK-010WC1 |
| H0 | J4 H0 Error of Fan Drive Board current Protection | XE7C-24 |
| HI | Binnenomgevingstemperatuur is te hoog | WK-010WC1 |
| P1 | J1 P1 current Protection Malfunction | XE7C-24 |
| P2 | J2 P2 Drive Board Power current Protection | XE7C-24 |
| P3 | J3 P3 Drive Board Module current Protection | XE7C-24 |
| U4 | U4 C2 Refrigerant and inverter compressor | XE7C-24 |
| U6 | U6 Valve Abnormal Alarm C4 Unit | XE7C-24 |
| U9 | U9 C7 Malfunction Communication Error | XE7C-24 |
| UL | Overstroombeveiliging inverter-buitenventilator | WK-010WC1 |
Gree Airco met foutcodes
- Gree GTH 36 K3FI-GUHD 36 NM3FO
- Gree VIR36HP230V1BO
- Gree ETAC-15HP265V30A
- Gree ETAC2-09HC265VA-CP
- Gree CAS12HP230V1AC
- Gree VIR12HP115V1BH
- Gree Inverter GWH 09 KF-K3DNA6G
- Gree XE7C-24
- Gree GMV-ND48A/B-T(U)
- Gree ETAC2-15HC265VA-CP
- Gree Free Match GWHD(24)NK3GO
- Gree GMV-ND18A/A-T(U)
- Gree VIR12HP230V1BO
- Gree UMAT36HP230V1AF
- Gree GIST12BXAE
- Gree XK41
- Gree GMV-ND72PH/B-T(U)
- Gree GIC818A
- Gree ETAC-07HP230V20B
- Gree GMV-ND12PHS/B-T(U)
- Gree DUCT18HP230V1AD
- Gree VIR18HP230V1AO
- Gree GMV-ND36ZD/A-T(U)
- Gree SAP09HP230V1AH
- Gree GICF924A
- Gree DUCT09HP230V1AD
- Gree CAS18HP230V1AC
- Gree GMV-ND09PHS/B-T(U)
- Gree GMV-NDX54P/A-T
- Gree GICF18DBE
- Gree VIR24HP230V1BO
- Gree VIR24HP230V1BH
- Gree MULTI42HP230V1AO
- Gree GSAF918A
- Gree ETAC-09HC265V20A
- Gree UMAT30HP230V1AF
- Gree VIR12HP230V1AH
- Gree 26TTW09AC115V1A
- Gree GWHD18NK3KO
- Gree 26TTW12HP230V1A
- Gree VIR30HP230V1AH
- Gree 660 GFH09EA-K3DNA1A-I
- Gree GMV-ND15TS/A-T(U)
- Gree LIVV36HP230V1AH
- Gree Vireo VIR12HP115V1AH
- Gree 3VIR12HP115V1AH
- Gree GWV35EG
- Gree ETAC-15HC265V20A
- Gree GMV-ND42A/A-T(U)
- Gree All Match DUC09HP230V1R32AH
- Gree Free Match GWHD(42)NK3AO
- Gree WK-010WC1
- Gree GISF209BXA