Bekijk gratis de handleiding van EBERLE FIT 3L (2 pagina’s), behorend tot de categorie Thermostaat. Deze gids werd als nuttig beoordeeld door 12 mensen en kreeg gemiddeld 4.4 sterren uit 5 reviews. Heb je een vraag over EBERLE FIT 3L of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/2
User and
installation guide
Room Temperature Controller
with LimiterFIT 3L
468931003 591-5
1 Principle of operation
The programmable temperature controller FIT 3L allows
automatically shows the time of day and the room tempera-
ture. In AUTO mode, the heater will be automatically activat-
ed according to programmed time and temperature. Program
1 is the default pre-set program (see 8.).
Room temperature will be controlled, the floor temperature
will be switched on when the temperature drops below the
current set-point.
the floor temp drops below the set min-value. This is even
when the room temp. is too high.
In case of function "Max Floor Temp" (H3) heating will be
stopped if the floor temp exceeds the set max-value. This is
even when the room temp. is too low.
2 Installation
3 Use
used to control the room temperature in conjunction with:
• Electrical floor heating systems where the floor tempera-
ture has to be limited to a certain value
Hot-water floor heating systems in conjunction with ther-
mal actuators
In order to measure the floor temperature the remote sensor
has to be used
4 Features
One line text display for simplified operation
Back light
Real time clock (setting of year, month, day, time)
Automatic Summer- Winter time change over
Max 9 events per day (each day independently)
Pre-set and adjustable programs
Optimum-Start
Arm chair programming (with display unit removed)
OFF-Function, Key to be pressed for 10 secV
Holiday-Mode (date from - until can be set)
Timer (Party) specific temperature for configurable duration
• Energy consumption display (heating on time * cost) for last
2 days, -week, -month, -year
Energy cost per hour configurable
Frost protection
Range limits for adjusting max and min temperature
Access protection
Operating language can be selected
Control mode PWM or ON/OFF
Minimum output on/off time and hysteresis configurable
for ON/OFF control
Min- and max limits for floor temperature adjustable
Valve protection
Adaptation to valves normally open or normally closed
• Adjustable heating interrupt according standard EN 50559
(not for valves normally open)
Caution!
This device must be installed by a qualified electrician,
according to the wiring diagram on the device and in com-
pliance with all applicable safety regulations.
Appropriate installation measures must be taken to achieve
the requirements of protection class II.
This device, is used to control the temperature only in dry
rooms, under normal environmental conditions. This elec-
tronic device conforms to EN 60730, It is an “independently
mounted control” and works according to operating princi-
ple 1C.
Remote Sensor F 193 720
8. Pre-set programs
There are 3 pre-set time/temperature programs in the
Therefore, if pre-set program 1 is the best program to suit the
application, there will be no need to change the
time/temperature settings on the device.
To select another program see 9. G1.
Program 1
Monday to Friday
Events123456
Time06:0008:3012:0014:0017:0022:00
Temperature °C21,018,021,018,021,015,0
Saturday and Sunday
Events123456
Time07:0010:0012:0014:0017:00
23:00/22:00*
Temperature °C21,018,021,021,021,015,0
*23:00/22:00 = 23:00 for Saturday
Program 2
Monday to Friday
Events123456
Time06:0008:3012:0014:0017:0022:00
Temperature °C21,018,021,018,021,015,0
Saturday and Sunday
Events12
Time07:00
23:00/22:00*
Temperature °C21,015,0
*23:00/22:00 = 23:00 for Saturday
Program 3
Monday to Friday
Events1234
Time06:0008:3017:0022:00
Temperature °C21,018,021,015,0
Saturday and Sunday
Events1234
Time07:0010:0012:00
23:00/22:00*
Temperature °C21,018,021,015,0
*23:00/22:00 = 23:00 for Saturday
Notes for Programming
Activated settings terminate automatically 3 Min after the
last key press, without saving. They return to the mode
which was active before entering the settings, e.g. AUTO,
MAN, etc.
Entering a Code: change value with +key then press OK
number used in the manual will be displayed, e.g. G1 for
"Program select one" or H2 for "Control Mode".
There may be gaps in the sequence of menu numbers.
Troubleshooting
1. It is getting warm too late:
a. Are clock and program events set correctly?
b. Is the Optimum Start feature switched on? see H7
Did the controller have enough time (several days) to
adapt to the room’s characteristics?
c. Is an automatic change between Summer- and Winter
time activated, see G5
2. The controller does not accept any changes
Is access protection switched on? see G6
3. The range of temperature setting is limited.
Are temperature limits set? See G7
4. Temperature display doesn‘t change.
Is display of set-temperature activated? See G10
5. The room heats up too slow
The floor temperature may be limited from the controller's
max-limiter. See H3
6. The room becomes too warm
The floor temperature may be limited from the controller's
Min-limiter. See H3
6:00 h8:00 h10:00 h12:00 h14:00 h16:00 h18:00 h20:00 h22:00 h
Mon – Fri
Sat – Sun
6:00 h8:00 h10:00 h12:00 h14:00 h16:00 h18:00 h20:00 h22:00 h
Mon – Fri
Sat – Sun
6:00 h8:00 h10:00 h12:00 h14:00 h16:00 h18:00 h20:00 h22:00 h
Mon – Fri
Sat – Sun
20
Ø7,8
Electric connection
Connecting according to Wiring Diagram
For flexible or solid wires 1-2,5 mm
2
Connecting the remote sensor
should be mounted in such a way that the temperature which
has to be controlled, can be measured correctly. Lay sensor
inside a protective tube (simplifies replacement). The sensor
lead can be extended up to 50m by using a cable and
alongside power cables, for example inside a conduit.
6 Technical Data
Order TypeFIT 3L
Supply voltage230V AC 50 HZ (207…253V)
Temperature setting range5°C...30°C; in 0,5°C steps
Temperature resolution 0,1°C steps
OutputRelay NO contact
Switching current10mA ...10(4)A AC; 230V~
Output signalPWM (Pulse Width modula-
tion) or ON/OFF
PWM cycle timeadjustable
Hysteresis adjustable (ON/OFF only)
Minimum programmable time10 Min
Power consumption ~ 1,2 W
Accuracy of clock< 4 Min/year
Power reserve~ 10 Years
Remote sensorF 193 720, length 4m,
can be extended up to 50m
Ambient temperaturewithout condensation
Operating0°C … 40°C
Storage–20°C … 70°C
Rated impulse voltage 4 kV
Ball pressure test75 ± 2 °C
Voltage and Current for
the purposes of
Interference measurements230V, 0,1A
Degree of protectionIP 30
Protection class of housingII (see Caution)
Pollution degree2
Software classA
Weight (with remote sensor)~280g
Energy classIV = 2%
(acc. EU 811/2013, 812/2013, 813/2013, 814/2013)
7 Wiring Diagram / Dimensions
Caution: disconnect electric circuit from supply
Caution!
The sensor is at mains voltage.
Sensor
LNN
230V~ 50Hz
L
N
Load
Actual Day
Actual
Room
Temperature
Calling for Heat
(Blinks if
detached from
power module
or there is no
mains power)
Helping text
Mode = AUTO
Time = 14:31
The controller should be mounted at a location in the room which:
can be easily accessed
is free of curtains, cabinets, shelves, etc.
allows free air circulation
is not exposed to direct sunlight
is not draughty (when doors or windows are opened)
is not directly influenced by the source of heat
is not located on an outer wall
is approx. 1.5 m above the floor.
Fitting
in a conduit box Ø 60 mm
remove the display unit
remove the frame
Mount it following the reverse
procedure
Caution!
Mounting in plastic wall boxes
only
5. Mounting
To insert or remove a
flexible wire press pin
between the terminals/wires and the mounting screw.
Caution!
Maximum length
of removed cable
insulation 8 mm.