Fantini Cosmi L02DI2B Handleiding


Bekijk gratis de handleiding van Fantini Cosmi L02DI2B (2 pagina’s), behorend tot de categorie Thermostaat. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.4 sterren uit 4 reviews. Heb je een vraag over Fantini Cosmi L02DI2B of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/2
Minimum ON time.
After output 2 has been turned ON, it remains active for minutes regardless of the2T0
temperature value measured.
Minimum OFF time ().the following parameter will be 2PF
After output 2 has been turned OFF, it remains inactive for minutes regardless of the2T1
temperature value measured.
Minimum ON time.
After output 1 has been turned ON, it remains active for minutes regardless of the1T0
temperature value measured.
Minimum OFF time ().the following parameter will be 1PF
After output 1 has been turned OFF, it remains inactive for minutes regardless of the1T1
temperature value measured.
CONFIGURATION PARAMETERS
PARRANGEDESCRIPTION
UM
RES
r01; r1Resolution of measure: r01=0.1°; r1=1°. This parameter is not available when UM=F and
in the model L02D.
SPL
-50°...SPHMinimum limit for setting1SP
SPH
SPL...150°Maximum limit for setting.1SP
1SP
SPL... SPHSetpoint (value to be maintained in the room).
1CM
HY; PIDControl mode.
With =HY you select control with hysteresis: parameters , and are used.1CM1HY1T01T1
With =PID you select a Proportional-Integral-Derivative control mode: parameters , , 1CM1PB1IT
1DT1AR1CT, , will be used
1CH
REF; HEARefrigerating (REF) or Heating (HEA) control mode.
1CM=HY
1HY
0...19.9°OFF/ON thermostat differential. With =0 the output is always off. 1HY
1T0
0...30 min
1T1
0...30 min
1CM=PID
1PB
0...19.9°Proportional band width.
Temperature control takes place by changing the
ON time of the output: the closer the temperature
to the setpoint, the less time of activation. A small
proportional band increases the promptness of
response of the system to temperature variations,
but tends to make it less stable. A purely
proportional control stabilises the temperature
within the proportional band but does not cancel
the deviation from setpoint.
With =0 the output is always off.1PB
1IT
0...999sIntegral action time.
The steady-state error is cancelled by inserting an
integral action. The integral action time, determines
the speed with which the steady-state temperature
is achieved, but a high speed ( low) may be the 1IT
cause of overshoot and instability in the response.
With =0 the integral control is disabled.1IT
1DT
0...999sDerivative action time.
Response overshoot may be reduced by inserting
a derivative Action. A high derivative action ( 1DT
high) makes the system very sensitive to small
temperature variations and causes instability. With
1AR
0...100%Reset of integral action time referred to 1PB
Decreasing the parameter reduces the integral control action zone, and consequently the 1AR
overshoot (see figure on paragraph 1IT).
1CT
1...255sCycle time.
Its the period in which the output ON time
changes. The quicker the system to be controlled
reacts to temperature variations, the smaller the cycle time must be, in order to obtain higher
temperature stability and less sensitivity to load variations.
1PF
ON/OFFOutput state in case of probe failure.
OAU
NON;
THR;
AL0;
AL1
AUX output operation.
NON : output disabled (always off). (the next parameter will be ATM)
THR: output programmed for second thermostat control ().the next parameter will be 2SM
AL0: contacts open when an alarm condition occurs (the next parameter will be ATM).
AL1: contacts make when an alarm condition occurs (the next parameter will be ATM).
OAU=THR
2SM
ABS;
REL
Setpoint 2 mode.
Channelsepoin 2 tt maybeabsolu te (2SM=ABS, )ordieren a fftialrela tiveoet1 ( t spoint 2SM=REL)
2SM=ABS
2SP
SPL...SPHAuxiliary output switchover temperature ()the next parameter will be 2CH
2SM=REL
2DF
-19.9...19.9°Temperature differential relative to . The auxiliary output setpoint is equal to +1SP1SP2DF
ON/OFF refrigerating control
(=HY, =REF)1CM1CH
ON/OFF heating control
(=HY, =HEA)1CM1CH
1SP
1SP+1HY
T[°]
ON
OFF
1SP1SP-1HY
T[°]
ON
OFF
Time
Temperature
Time
Temperature
Time
Temperature
Process
temperature
Overshoot
Steady-state error
1PB
1SP
Process
temperature
Overshoot
1PB
1PBx1AR%
integral control
action area
1SP
Process
temperature
Overshoot
1PB
1SP
2SP
2SP+2HY
T[°]
ON
OFF
ON/OFF control in refrigeration
(=ABS, =REF)2SM2CH
2SP2SP-2HY
T[°]
ON
OFF
ON/OFF control in heating
(=ABS, =HEA)2SM2CH
1SP+2DF
1SP
2DF>0
1SP+2DF+2HY
T[°]
ON
OFF
ON/OFF control in refrigeration. Setpoint 2
relative to setpoint 1 (=THR, =REF)OAU2CH
1SP
1SP+2DF
2DF<0
1SP+2DF-2HY
T[°]
ON
OFF
ON/OFF control in heating. Setpoint 2
relative to setpoint 1 (=THR, =HEA)OAU2CH
INPUT SPECIFICATIONS
MODELINPUT
RANGE [MEASUREMENT ACCURACY]
RES = r01 (UM = c)RES = r1 (UM = c)RES = r1 (UM = F)
L02D--
INP=T1TC J----50÷750°C [ < ±3°C ]
-60÷999°F [ < ±5°F ]
L02C--PT100
-50/-19.9÷99.9/150°C
[ < ±0.3°C ]
-100÷850°C
[<±1°C(-50÷850°), ±2°C]
-150÷999°F
[<±2°F(-60÷999°), ±4°F]
L02A--
INP=ST1
PT1000
(LS 120)
-50/-19.9 ÷ 99.9/150°C
[<±0.C(-30130÷°)1°C],±
-50 ÷ 150°C
[<±0.3°C(-30÷130°), ±1°C]
-60 ÷ 300°F
[< ±0.6°F(-20÷260°),±2°F]
INP=SN4
NTC 10k
(LS 130)
-40/-19.9 ÷ 99.9/125°C
[<±0.C(-40100÷°)1°C],±
-40 ÷ 125°C
[<±0.3°C(-40÷100°), ±1°C]
-40 ÷ 260°F
[<±0.6°F(-40÷210°), ±2°F]
WIRING DIAGRAMS
OAU=THR
2CH
REF; HEARefrigerating control (REF) or heating control mode (HEA) for the auxiliary output.
2HY
0...19.9°Differential of thermostat 2. With =0 the auxiliary output always remains off.2HY
2T0
0...30min
2T1
0...30min
2PF
ON/OFFAuxiliary output state in case of probe failure.
ATM
NON;
ABS;
REL
As t.larm threholdmanagemen
NON: all temperaurealarmsareinhibiedt t (the followingpaameerwillbe rt SB).
ABS: thealue vs programmed inALAA andAH s repreent therealalarmhreholds ts.
REL : thevalues programmedin ALRand AHRarealarmdi ffterenialres ferred to 1SP and1SP+1HY.
ATM=ABS
ALA
-50°...AHALow temperature alarm threshold.
AHA
ALA...150°High temperature alarm threshold.
ATM=REL
ALR
-12.0...0°Low temperature alarm differential.
With =0 the low temperature alarm is excluded.ALR
AHR
0...12.0°High temperature alarm differential.
With =0 the high temperature alarm is excluded.AHR
ATD
0...120minDelay before alarm temperature warning.
SB
NO/YESStand-by button enabling.
INP
0mA/4mA,
T1/T2
ST1/SN4
Sensor input selection (see table of input specifications).
In the models L02C-- only.
RLO
-19.9...RHIMinimum range value (function not available).
RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V, 0/4mA).
RHI
RLO...99.9Maximum range value (function not available).
RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V, 20mA)
OS1
-12.5...12.5°Probe T1 offset.
TLD
1...30minDelay for minimum temperature (TLO) and maximum temperature (THI) logging.
SIM
0...100Display slowdown.
ADR
1...255Address for communication with a PC (function not available).
PRT
ASC;
RTU
ASCII and RTU Modbus protocol selection (.function not available)
1SP
1SP-ALR
T[°]
ON
OFF
1SP+1HY+AHR
1SP1SP-1HY-ALR
1SP+AHR
T[°]
ON
OFF
Temperature alarm with relative thresholds,
refrigerating control (ATM1CH=REL, =REF)
Temperature alarm with relative thresholds,
heating control (ATM1CH=REL, =HEA).
DISPLAY
During normal operation, the display shows either the temperature measured or one of the following indications:
OPERATION
Insert the controller through a hole measuring 71x29 mm;
Make sure that electrical connections comply with the paragraph wiring diagrams. To reduce the effects of electromagnetic
disturbance, keep the sensor and signal cables well separate from the power wires.
Fix the controller to the panel by means of the suitable clips, by pressingly gently; if check that the rubber gasket adheres fitted,
to the panel perfectly, in order to prevent debris and moisture infiltration to the back of the instrument.
ATTENTION: during the setup of the controller, please make sure that the parameter INP matches the sensor used, as indicated
in the table “input specifications”.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
INSTALLATION
= Channel 1 output1
= Channel 2 output
= View in °C or °F
2
Fig.1 - Front panel
Thank you for having chosen a Fantini Cosmi product. Before installing the instrument, please read these instructions carefully
to ensure maximum performance and safety.
DESCRIPTIONINDICATION
INSTRUCTIONS FOR USE
Configuration menu password
SETTING
Confirm
Discard
Confirm
RESET
Discard
oror
Confirm
Discard
Increase
Decrease
blink
Minimum temperature recorded
Maximum temperature recorded
Keypad state lock
Instant probe 1 temperature
Auto-tuning
or
Confirm
Discard
Increase
Decrease
or
Exit
blink
Confirm
Discard
Increase
Decrease
Confirm
Discard
CONDITION
1CM = PID
1CH = configured
1SP = configured
*Configuration access [PSD] is 123
*Tuning access [TUN] is 321
Errors
If the autotuning function failed, the display shows an error code:
E1 timeout1 error: the controller could not bring the temperature within the proportional band. Increase 1SP in case of heating
control, vice versa, decrease in case of refrigerating control and re-start the process.1SP
E2 timeout2 error: the autotuning has not ended within the maximum time allowed (1000 cycle times). Re-start the autotuning
process and set a longer cycle time .1CT
E3 temperature overrange: check that the error was not caused by a probe malfunction, then decrease 1SP in case of heating
control, vice versa increase in case of refrigerating control and then re-start the process.1SP
E4
device not configured correctly: the device has an incorrect configuration of the parameter. 1CM Enter the menu and check that
the parameter is set to .1CM PID
To eliminate the error indication and return to the normal mode, press button .
Control improvement
To reduce overshoot, reduce the integral action reset 1AR
To increase theresponsespeedhe of t sysemreduceheproport, t tionalband 1PB. : Cauiontdoing thismakeshe t sysemlesst st.able
To reduce swings in steady-state temperature, increase the integral action time 1IT; system stability is thus increased, although
its response speed is decreased.
To increase the speed of response to the variations in temperature, increase the derivative action time 1DT. Caution: a high
value makes the system sensitive to small variations and it may be a source of instability.
Confirm
Discard
Next
Previous
Keypad Lock
Reset temperature recorded
Menu access/autotuning
Autotuning
Controller in stand-by
Probe T1 overrange or failure
Room high temperature alarm
Room low temperature alarm
In tuning: timeout1 error
In tuning: timeout2 error
In tuning: overrange error
In tuning: device not configured correctly
Controller in autotuning
= Alarm
= Tap
= Hold
Cod. 5679193D - 07/2025
TECHNICAL DATA
Power supply
Relay outputs
OUT1 3,6 FLA, 21,6 LRA 240Vac
OUT2 1 FLA, 6 LRA, 240V
Inputs
see table of input specifications
Measurement range
see table of input specifications
Measurement accuracy
see table of input specifications
Operating conditions
-10 +50°C; 15%...80% r.H.
Reference Norms
EN61000-6-1
EN61000-6-3
EN60730-1
EN60730-2-9
RoHS Directive 2015/863/EU
REACH Directive 2021/979/EU
Front Protection
IP54 by fitting the front gasket
L02AI2C-L02CI1C-L02CI2C-L02DI1C-L02DI2C:
7...30 Vdc / 12Vac ±10%, 3W
In these
versions, the power supply
for the controller and the loads must be
of type SELV or PELV.
L02AM2A-L02CM1A-L02CM2A-L02DM1A:
100...240Vac±10%, 50/60Hz, 3W
FANTINI COSMI S.p.A.
Via dellOsio, 6
20049 Caleppio di Settala (Mi) - ITALY
Tel. +39 02 956821 - [email protected]
www.fantinicosmi.it
SUPPORTO TECNICO
EXPORT DEPARTMENT
ITA
ISTRUZIONI DUSO
ENG
INSTRUCTIONS FOR USE
L02...A/C/D
-
+
L02CM- / L02CI-
7...30
Vdc
OUT2OUT1
POWER
12
Vac
~
~
6754312
RRW
11910
L02CM- 100...240Vac
L02CI-
-
+
+
-
L02AM- / L02AI2C
7...30
Vdc
OUT2OUT1
POWER
12
Vac
~
~
1110
6754312
L02AM- 100...240Vac
L02AI-
L02DM- 100...240Vac
OUT2OUT1
+
-
POWER
1110
6754312
L02DM- / L02DI-
-
+
7...30
Vdc
12
Vac
~
~
L02DI-

Beoordeel deze handleiding

4.4/5 (4 Beoordelingen)

Product specificaties

Merk: Fantini Cosmi
Categorie: Thermostaat
Model: L02DI2B

Heb je hulp nodig?

Als je hulp nodig hebt met Fantini Cosmi L02DI2B stel dan hieronder een vraag en andere gebruikers zullen je antwoorden