Bekijk gratis de handleiding van Eastron SDM120CTP (6 pagina’s), behorend tot de categorie Meetapparatuur. Deze gids werd als nuttig beoordeeld door 3 mensen en kreeg gemiddeld 3.6 sterren uit 2 reviews. Heb je een vraag over Eastron SDM120CTP of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/6

Eastron SDM120-CTM User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Add: No.52 Dongjin Road, Nanhu, Jiaxing, Zhejiang, 314000, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
SDM120CTP
Single-Phase Multifunction DIN Rail Meter
Measures kWh, kVArh, kW, kVAr, kVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
Din rail mounting 35mm
5A CT connection
Better than Class 1 accuracy
User Manual V1.0

Eastron SDM120-CTM User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Add: No.52 Dongjin Road, Nanhu, Jiaxing, Zhejiang, 314000, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
Application
The energy-meters are used to measure single-phase applications like residential, utility and Industrial. The unit
measures and displays various important electrical parameters. It equipped with a white back-lighted LCD screen
for prefect reading. As well as a RS485 communication port for remote reading and monitoring. Bi-directional
energy measurement makes it a good choice for solar PV energy metering. The compact design and din rail
installation provides an easy and economical solution for your metering demand.
PART 1 Specification
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) 5A
Power consumption <2W/10VA
Frequency 50/ 60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS waveform
Overcurrent withstand 20Imax for 0.5s
Pulse output 1 1000 imp/kWh (export)
Pulse output 2 1000imp/kWh (import)
Display LCD with white backlit
Max. Reading 999999 kWh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Active energy Class 1 IEC62053-21
Class B EN50470-1/3
Reactive energy Class 2 IEC62053-23
Environment
Operating temperature -25 to +55℃ ℃
Storage and transportation temperature -40 to +70℃ ℃
Reference temperature 23 2℃± ℃

Eastron SDM120-CTM User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Add: No.52 Dongjin Road, Nanhu, Jiaxing, Zhejiang, 314000, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
Relative humidity 0 to 95%, non-condensing
Altitude up to 2000m
Warm up time 5s
Installation category CAT III
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is fixed to export kWh. The constant is 1000 imp/kWh.
Pulse output 2 is fixed to import kWh. The constant is 1000imp/kWh.
Mechanics
Din rail dimensions 18x118x64 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Ingress protection IP51 (indoor)
Material Self-extinguishing UL94V-0
PART 2 Operation
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
1
Full Screen
It will last for 3 seconds.
2
Software version in kind prevail
It will last for 3 seconds.
After the self-checking program, the meter display will show the total active energy (kWh)
Scroll Display by Button
There is a button on the front of the meter. After initialization and self-checking program, the meter display the
measured values. The default page is total kWh. If the user wants to check other information, he needs to press
the scroll button on the front panel.
Product specificaties
Merk: | Eastron |
Categorie: | Meetapparatuur |
Model: | SDM120CTP |
Heb je hulp nodig?
Als je hulp nodig hebt met Eastron SDM120CTP stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Meetapparatuur Eastron
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
23 Mei 2025
Handleiding Meetapparatuur
- Siglent
- Fysic
- Flir
- Brandson
- Makita
- Kemo
- KS Tools
- Einhell
- Ideal
- TFA Dostmann
- SHX
- Extech
- Monacor
- Topex
- CEM
Nieuwste handleidingen voor Meetapparatuur
17 Juni 2025
16 Juni 2025
16 Juni 2025
16 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025