Page 1 of 4 D A T A S H E E T K85001-0646
Not to be used f or installation purposes. Issue 1
KIDDE® Catalog Intelligent Initiating Devices
Technology that saves lives
Intelligent Smoke
Detector
KI-PD
Overview
The KI-PD optical smoke detector brings advanced sensing
technology to a practical design that increases efficiency, saves
installation time, cuts costs, and extends life safety and property
protection capabilities. Continuous self-diagnostics ensure reli-
ability over the long-haul, while environmental compensation helps
reduce maintenance costs.
Like all KI Series detectors, the KI-PD is an intelligent device that
gathers analog information from its optical sensor, converting this
data into digital signals. To make an alarm decision, the detectors
on-board microprocessor measures and analyzes sensor read-
ings and compares this information to historical data. Digital filters
remove signal patterns that are not typical of fires, thus virtually
eliminating unwanted alarms.
Standard Features
Note: Some features described here may not be supported by
all control systems. Check your control panel’s Installation and
Operation Guide for details.
• Next generation optical smoke sensing technology
• Wide 0.53 to 3.94 %/ft. (1.7 to 12.35 %/m) smoke obscuration
• Uses Existing Wiring
• Automatic Device Mapping
• Up To 250 Total Addresses Per Loop
• Two Levels of Environmental Compensation
• Two Levels of Dirty Detector Warning
• Twenty Pre-Alarm Settings
• Five Sensitivity Settings
• Non-Volatile Memory
• Electronic Addressing
• Identification of Dirty or Defective Detectors
• Automatic Day/Night Sensitivity Adjustment
• Bicolor (Green/Red) Status Led
• Standard, Relay, Fault Isolator, and Audible Mounting Bases
• Sensor Markings Provide Easy Testing Identification
S853
Compatible with VS & VM control systemsCompatible with VS & VM control systems
Page 2 of 4 D A T A S H E E T K85001-0646
Not to be used f or installation purposes. Issue 1
Application
The KI-PD detects extremely small particles of combustion and
triggers an alarm at the first sign of smoke. Thanks to its high-
performance forward-scattering reflective response technology,
the photoelectric smoke sensor responds quickly and reliably to
a wide range of fire types, espe cially slow burning fires fuelled by
combustibles typically found in modern multi-use buildings.
Compatibility
The KI-PD detector is compatible with Kidde VS and VM series
panels.
Installation
Self-locking tab
LED Indicator
KI Series detector bases mount
to North American 1-gang boxes,
3-1/2 inch or 4 inch octagon
boxes, and to 4 inch square elec-
trical boxes 1-1/2 inches (38 mm)
deep. They mount to European
BESA and 1-gang boxes with 60.3
mm fixing centers. See mounting
base installation and wiring for
more information.
Sensing and reporting technology
The microprocessor in each detector provides additional benefits -
Self-diagnostics and History Log, Automatic Device Mapping, and
Fast, Stable Communication.
Self-diagnostics and History Log - Each KI Series detector
constantly runs self-checks to provide important maintenance in-
formation. The results of the self-check are automatically updated
and permanently stored in the detectors non-volatile memory
Automatic Device Mapping - The loop controller learns where
each device’s serial number address is installed relative to other
devices on the circuit. The mapping feature provides supervision
of each device’s installed location to prevent a detector from being
reinstalled (after cleaning etc.) in a different location from where it
was originally.
Fast Stable Communication - On-board intelligence means less
information needs to be sent between the detector and the loop
controller. Other than regular supervisory polling response, the
detector only needs to communicate with the loop controller when
it has something new to report.
Testing & Maintenance
Each detector automatically identifies when it is dirty or defective
and causes a “dirty detector” message. The detector’s sensitiv-
ity measurement can also be transmitted to the loop controller. A
sensitivity report may be printed to satisfy NFPA sensitivity mea-
surements, which must be conducted at the end of the first year
and every two years thereafter.
The user-friendly maintenance program shows the current state
of each detector and other pertinent messages. Single detectors
may be turned off temporarily from the control panel. Availability of
maintenance features is dependent on the fire alarm system used.
Accessories
Detector mounting bases have wiring terminals that are acces-
sible from the “room-side” after mounting the base to the electrical
box. The bases mount to North American 1-gang boxes and to
3½ inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They
also mount to European BESA and 1-gang boxes with 60.3 mm
fixing centers. The KI-SB4, KI-RB4, and KI-IB4 mount to North
American 4 inch sq. electrical boxes in addition to the above
boxes. They include the GSA-TS4 Trim Skirt, which is used to
cover the “mounting ears” on the base. The KI-ABST mounts to a
4 inch square box only.
KI-IB
Isolator Base
GSA-LED
Remote LED
KI-RB
Relay Base
KI-SB
Standard Base
KI-ABST/T/LF
Audible Base
Remote LED GSA-LED - The remote LED connects to the KI-SB
or KI-SB4 Standard Base only. It features a North American size
1-gang plastic faceplate with a white finish and red alarm LED.
GSA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also
be ordered separately to use with the other bases to help hide
surface imperfections not covered by the smaller bases.
Sounder Bases - KI Series sounder bases are designed for use
where localized or group alarm signaling is required.
• KI-ABST bases provide sounder capability to KI Series heat
and smoke detectors. They are not intended for use with
combination carbon monoxide detectors in Fire-plus-CO
mode.
• KI-ABDT bases provide sounder capability to KI Series
smoke and heat detectors, as well as carbon monoxide
detectors when used with a GSA-T3T4 Temporal Pattern
Generator.
• KI-ABLT bases provide 520 Hz low frequency sounder
capability to KI Series smoke and heat detectors, as well as
carbon monoxide detectors when used with a GSA-T3T4
Temporal Pattern Generator. The KI-ABLT is suitable for ap-
plications requiring low frequency audible tones.
Page 3 of 4 D A T A S H E E T K85001-0646
Not to be used f or installation purposes. Issue 1
Typical Wiring
The detector mounting bases accept #18 AWG (0.75mm2), #16
(1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm²) wire sizes.
Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred
for ease of installation.
Standard Detector Base, KI-SB, KI-SB4
This is the basic mounting base
for Kidde KI Series detectors.
The GSA-LED Remote LED is
supported by this
Base.
Term Description
1 Not Used
2 DATA IN/OUT (+)
3 Not Used
4 DATA IN (-)
4 Remote LED (-)
5 Remote LED (+)
6 Not Used
7 DATA OUT (-)
Max resistance
per wire
must not exceed
10 Ohms
DATA IN (-)
DATA IN (+)
From Signature Controller
or Previous Device
DATA OUT (-)
DATA OUT (+)
To Next Device
Remote LED
Relay Detector Base, KI-RB, KI-RB4
This base includes a relay. Nor-
mally Open or Normally Closed
operation is selected during
installation. The dry contact is
rated for 1 amp (pilot duty) @
30 Vdc. The relay’s position is
supervised to avoid accidentally
jarring it out of position. The KI-RB
can be operated as a control
relay if programmed to do so at
the control panel. The relay base
does not support the GSA-LED
Remote LED. CONTACT RATING
1.0 Amp @ 30 VDC
(Pilot Duty)
Term Description
1 Normally Open
2 DATA IN/OUT (+)
3 Common
4 DATA IN (-)
5 Not Used
6 Normally-Closed
7 DATA OUT (-)
Isolator Detector Base, KI-IB, KI-IB4
This base includes a built-in line fault isolator for use on Class A
circuits. A detector must be installed for it to operate. The isolator
base does not support the GSA-LED Remote LED.
The isolator operates as follows:
- a short on the line causes all iso-
lators to open within 23 msec
- at 10 msec intervals,
beginning on one side
of the Class A
circuit nearest the loop
controller, the isolators
close to provide the
next isolator down the
line with power
- when the isolator next
to the short closes, it reopens within 10
msec.
The process repeats beginning on the
other side of the loop controller.
Term Description
1 Not Used
2 DATA IN/OUT (+)
3 DATA IN (-)
4 Not Used
5 Not Used
6 DATA OUT (-)
7 Not Used
Audible Sounder Bases, Fire Mode
AB4GT, AB4G, AB4G-LF sounder bases
KI-ABLT:
Output Mode
Default = Fire
Cut/remove jumper for
Fire plus CO
KI-ABST:
Tone Setting
Default = Temporal
Cut/remove jumper for
Steady
KI-ABDT:
Not Used
KI-ABDT,
KI-ABST,
KI-ABLT:
Volume Setting
Default = High
Cut/remove
jumper for
low dB
+
-
+
-
+
-
+
-24 Vdc out
To next base or EOL relay
Data out
to next KI Series device
24 Vdc in
From power supply
or previous base
Data in
From KI Device Controller
or previous device
DATA- DATA- DATA+
SIG+ SIG- OUT IN IN/OUT
Jumper cuts
Warnings & Cautions
• This detector does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
• This detector does not sense fires in areas where smoke
cannot reach the detector. Smoke from fires in walls, roofs,
or on the opposite side of closed doors may not reach the
detector.
• Photoelectric detectors have a wide range of fire-sensing
capabilities and are best suited for detecting slow, smolder-
ing fires.
• In Canada, install according to CAN/ULC-S524 Standard for
the Installation of Fire Alarm Systems, CSA C22.1 Canadian
Electrical Code, and the local authority having jurisdiction.


Product specificaties

Merk: Kidde
Categorie: Rookmelder
Model: KI-PD
Kleur van het product: Wit
Materiaal behuizing: Kunststof
Stroombron: AC
Type verpakking: Doos
Ondersteuning voor plaatsing: Horizontaal
Connectiviteitstechnologie: Bedraad
Montagewijze: Opbouwmontage
Aantal per verpakking: 1 stuk(s)
Aantal: 1
Temperatuur bij opslag: -20 - 60 °C
Maximumbereik: 12.35 m
Draadloze verbindingen: Ja
Beste gebruik: Home,Office
Detector type: Koolmonoxide detector
Koppelbaar: Ja
Gemakkelijk te installeren: Ja
Bedrijfstemperatuur (T-T): 0 - 49 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 93 procent