WARNING
Risk of Fire or Electric Shock
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
Installation and/or wiring must be in accordance with national and local electrical code requirements.
Use wires rated at least 90°C - COPPER conductors ONLY.
For outdoor locations, raintight, or wet location, conduit hubs that comply with requirements of UL514B (standard
for fittings for conduit and outlet boxes) are to be used.
Replace plastic insulator covering terminals before powering ON.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
Pour les emplacements extérieurs, étanches à la pluie ou les emplacements mouillés, des entrées de conduit qui
sont conformes aux exigences de UL514B (norme pour les pièces de fixation pour conduit et boîtes de sortie)
doivent être utilisées
LR3730
CLOCK
MOTOR
WIRING DIAGRAM
FROM
208V
240V
OR
277V
SUPPLY
TO
LOAD
GROUND
LINE
GRD
A
4321
TYPICAL WIRING SINGLE POLE NORMALLY OPEN - 277 V
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
N or
LINE 2
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
CLOCK MOTOR: 208-277 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER
REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing
to time (AM or PM) when and operations are desired, tighten tripper screws ON OFF
firmly. For additional tripper pairs on order 156T1978A.CLOCK-DIAL
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align
the exact time-of-day on the (the time now, when switch is being put into CLOCK-DIAL
operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: MANUAL LEVERMove
CLOCK-DIAL below left or
right as indicated by arrows. This will not effect next operation.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See
programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--02053
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER only. May use two wires of the same size and conductors
type. To wire switch follow diagram above. To wire as SINGLE POLE NORMALLY CLOSED, move clock motor
lead from terminal 3 to 1, and connect LINE to 1, LOAD to 2. To wire as SINGLE POLE DOUBLE THROW,
install
jumper (the same gauge as line wire) between 2 and 3 and connect LINE 1 to 2; N.O. LOAD to Terminal 4
and N.C. LOAD to Terminal 1. Connect LINE 2 to Terminal A and also to LOADS.
UL
HOLOGRAM
LABEL
MODEL: T106R
24 HOUR DIAL TIME SWITCH
TYPE 3R RAINPROOF ENCLOSURE
SUITABLE FOR POOL EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE
OF POOL. ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS. MAY BE
WIRED AS SINGLE POLE DOUBLE THROW. 40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY PER POLE - 120-277 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC