Gree VIR18HP230V1AO Handleiding

Gree Airco VIR18HP230V1AO

Bekijk gratis de handleiding van Gree VIR18HP230V1AO (31 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 91 mensen en kreeg gemiddeld 4.3 sterren uit 5 reviews. Heb je een vraag over Gree VIR18HP230V1AO of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/31
Models:
VIR09HP115V1A
VIR12HP115V1A
VIR09HP230V1A
VIR12HP230V1A
VIR18HP230V1A
VIR24HP230V1A
VIR30HP230V1A
VIR36HP230V1A
HIGH-WALL DUCTLESS
AIR CONDITIONING &HEATING SYSTEM
INSTALLATION MANUAL

Beoordeel deze handleiding

4.3/5 (5 Beoordelingen)

Product specificaties

Merk: Gree
Categorie: Airco
Model: VIR18HP230V1AO

Foutcodes Gree VIR18HP230V1AO

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing
C5 System Configuration C5 1) No jumper cap inserted on the control board. Malfunction 2) Incorrect or damaged jumper cap on control board.
E1 System High Pressure E1 1) Over charged with refrigerant. 2) Blocked or dirty outdoor coil .
E2 Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow. and 2) Indoor fan speed is too low.
E4 Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and temperature, overload) in service manual.
E5 Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable. and 2) Supply voltage is too low and system load is too high.
E6 Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units.
E8 High Temperature E8 6 flashes 1) Incorrect refrigerant charge level. Resistant Protection and 2) Refrigerant metering device malfunction.
F0 Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s). and 2) Indoor coil temperature sensor no calibrated.
F1 Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board. Sensor Malfunction 2) Indoor ambient temperature sensor damaged.
F2 Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board. Sensor Malfunction 2) Indoor coil temperature sensor damaged.
F3 Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Outdoor ambient temperature sensor damaged.
F4 Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Outdoor coil temperature sensor damaged.
F5 Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Discharge temperature sensor damaged.
H3 Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose. and 2) Refer to the malfunction analysis in Service Manual.
L1 High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac. and 2) Capacitor on control board malfunction.
P5 Compressor Phase Current P5 1) IPM module malfunction. Protection 2) Outdoor control board malfunction
P7 Module Temperature Sensor P7 Outdoor control board malfunction Malfunction
P8 Module Temperature Protection P8 1) Lack of thermal grease on IPM module. 2) Heat sink (radiator) not tightly mounted.