Foutcodes Gree VIR18HP230V1AO
Foutcodes uit de officiële handleiding, met betekenis en oplossing.
| Code | Betekenis | Oplossing | Pagina |
|---|---|---|---|
| C5 | System Configuration C5 1) No jumper cap inserted on the control board. Malfunction 2) Incorrect or damaged jumper cap on control board. | 27 | |
| E1 | System High Pressure E1 1) Over charged with refrigerant. 2) Blocked or dirty outdoor coil . | 27 | |
| E2 | Indoor Anti-Freeze Protection E2 3 flashes 1) Low return airflow. and 2) Indoor fan speed is too low. | 27 | |
| E4 | Compressor High Discharge E4 7 flashes Please refer to the malfunction analysis (discharge Temperature Protection and temperature, overload) in service manual. | 27 | |
| E5 | Overcurrent Protection E5 5 flashes 1) Supply voltage is unstable. and 2) Supply voltage is too low and system load is too high. | 27 | |
| E6 | Communication Malfunction E6 Continuous 1) Communication cable is mis-wired between indoor On and outdoor units. | 27 | |
| E8 | High Temperature E8 6 flashes 1) Incorrect refrigerant charge level. Resistant Protection and 2) Refrigerant metering device malfunction. | 27 | |
| F0 | Refrigerant Leakage Protection F0 9 flashes 1) refrigerant leak(s). and 2) Indoor coil temperature sensor no calibrated. | 27 | |
| F1 | Indoor Ambient Temperature F1 1) Loose or bad connection between sensor and control board. Sensor Malfunction 2) Indoor ambient temperature sensor damaged. | 28 | |
| F2 | Indoor Coil Temperature F2 1) Loose or bad connection between sensor and control board. Sensor Malfunction 2) Indoor coil temperature sensor damaged. | 28 | |
| F3 | Outdoor Ambient Temperature F3 6 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Outdoor ambient temperature sensor damaged. | 28 | |
| F4 | Outdoor Coil Temperature F4 5 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Outdoor coil temperature sensor damaged. | 28 | |
| F5 | Outdoor Discharge Temperature F5 7 flashes 1) Loose or bad connection between sensor and control board. Sensor Malfunction and 2) Discharge temperature sensor damaged. | 28 | |
| H3 | Compressor Overload Protection H3 8 flashes 1) Wiring terminal OVC-COMP is loose. and 2) Refer to the malfunction analysis in Service Manual. | 28 | |
| L1 | High DC Bus Voltage Protection PH 13 flashes 1) Supply voltage on L1 and N is above 265Vac. and 2) Capacitor on control board malfunction. | 28 | |
| P5 | Compressor Phase Current P5 1) IPM module malfunction. Protection 2) Outdoor control board malfunction | 28 | |
| P7 | Module Temperature Sensor P7 Outdoor control board malfunction Malfunction | 28 | |
| P8 | Module Temperature Protection P8 1) Lack of thermal grease on IPM module. 2) Heat sink (radiator) not tightly mounted. | 28 |