Fujitsu AJG090JATAH Handleiding

Fujitsu Airco AJG090JATAH

Bekijk gratis de handleiding van Fujitsu AJG090JATAH (24 pagina’s), behorend tot de categorie Airco. Deze gids werd als nuttig beoordeeld door 79 mensen. Heb je een vraag over Fujitsu AJG090JATAH of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 23/24
En-1
PART No. 9378945746-02
INSTALLATION MANUAL
For authorized service personnel only.
VRF SYSTEM OUTDOOR UNIT (Cooling only)
AJG072JATAH
AJG090JATAH
AJG108JATAH
AJG126JATAH
AJG144JATAH
AJG162JATAH
AJG180JATAH
Contents
1. SAFETY PRECAUTIONS ........................................................................................1
2. ABOUT THIS PRODUCT .........................................................................................2
2.1. Precautions for using R410A refrigerant .......................................................2
2.2. Special tools for R410A .................................................................................2
2.3. Accessories ..................................................................................................2
2.4. Combinations ................................................................................................3
2.5. Optional parts................................................................................................3
3. INSTALLATION WORK ............................................................................................3
3.1. Selecting an installation location ...................................................................3
3.2. Drain processing ...........................................................................................3
3.3. Clearance requirement .................................................................................4
3.4. Transporting the unit .....................................................................................5
3.5. Installing the unit ...........................................................................................6
3.6.Removingthecompressorxture .................................................................6
4. SYSTEM CONFIGURATION ...................................................................................6
4.1.Systemconguration ....................................................................................6
4.2. Pipe selection................................................................................................7
4.3. Protection of pipes ........................................................................................8
5. PIPE INSTALLATION ...............................................................................................9
5.1. Brazing ..........................................................................................................9
5.2. Indoor unit pipe connections .........................................................................9
5.3. Opening for piping .........................................................................................9
5.4. Pipe connection ............................................................................................9
5.5. Multiple connections ...................................................................................10
6. ELECTRICAL WIRING ...........................................................................................12
6.1. The precautions of electrical wiring .............................................................12
6.2. Wiring method .............................................................................................12
6.3. Opening for wiring .......................................................................................12
6.4. Selecting power supply cable and breaker .................................................13
6.5. Transmission line ........................................................................................13
6.6. Wiring procedure.........................................................................................14
6.7.Externalinputandexternaloutput ..............................................................15
7. FIELD SETTING ....................................................................................................16
7.1. Field setting switches ..................................................................................16
7.2. DIP switch setting .......................................................................................16
7.3. Rotary switch setting ...................................................................................17
7.4. Push button setting .....................................................................................17
7.5.AddresssettingforSignalampliers ...........................................................19
7.6. Indoor unit address setting ..........................................................................19
7.7. Resistance measurement of transmission cable
(Measure with breaker OFF) .......................................................................19
8. PIPE INSTALLATION II ..........................................................................................20
8.1. Sealing test .................................................................................................20
8.2. Vacuum process .........................................................................................20
8.3. Installing thermal insulation .........................................................................21
9. TEST RUN .............................................................................................................22
9.1. Pre-check for test run..................................................................................22
9.2. Test run method ..........................................................................................22
9.3. Checklist .....................................................................................................22
10. STATUS DISPLAY .................................................................................................23
10.1. Normal operation codes ..............................................................................23
10.2. Error codes .................................................................................................23
1. SAFETY PRECAUTIONS
• Be sure to read this Installation manual thoroughly before installation.
• The warnings and precautions indicated in this Installation manual contain important
information pertaining to your safety. Be sure to observe them.
• After installing the unit, perform a test run to make sure the unit operates normally. Then,
explaintothecustomerhowtooperateandmaintaintheunit.
• Please pass this Installation manual together with the Operating manual to the customer.
Please ask the customer to keep the Operating manual and Installation manual at hand
for future reference during the moving or repair of the main unit.
WARNING
This mark indicates procedures which, if improperly per-
formed, might lead to the death or serious injury of the user.
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
Using non-specified parts will cause serious accidents such as falling unit, refrigerant
leakage, water leakage, electric shock, and fire.
To install a unit that uses the R410A refrigerant, use dedicated tools and pipe materials
that have been manufactured specifically for R410A use.
BecausethepressureoftheR410Arefrigerantisapproximately1.6timeshigherthan
the R22, failure to use dedicated pipe material or improper installation can cause
rupture or injury.
It will also cause serious accidents such as refrigerant leakage, water leakage, electric
shock, and fire.
Do not use this equipment with air or any other unspecified refrigerant in the refrigerant
lines.
Excesspressurecancausearupture.
Be sure to install the unit as prescribed, so that it can withstand earthquakes and
typhoons or other strong winds.
Improper installation can cause the unit to topple or fall, or other accidents
.
Ensure that the outdoor unit is securely installed at a place that can withstand the
weight of the unit.
Improper installation will cause injuries caused by falling unit.
Ifthereisarefrigerantleakage,makesurethatitdoesnotexceedtheconcentration
limit.
Ifarefrigerantleakageexceedstheconcentrationlimit,itcanleadtoaccidentssuchas
oxygenstarvation.
If a refrigerant leakage occurs during operation, immediately vacate the premises and
thoroughly ventilate the area.
Iftherefrigerantisexposedtofire,itwillcreateahazardousgas.
Electrical work must be performed in accordance with this Installation manual by a
person certified under the national or regional regulations. Be sure to use a dedicated
circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
therearenoexternalforcesofthecablesappliedtotheterminalconnections.
Improperly connected or secured cables can cause serious accidents such as overheat-
ing the terminals, electric shock, or fire.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such
as electric shock or fire.
After the installation, make sure there is no refrigerant leakage.
Iftherefrigerantleaksintotheroomandbecomesexposedtoasourceoffiresuchasa
fan heater, stove, or burner, it will create a hazardous gas.
Use a wall hole pipe. Otherwise, it may cause a short circuit.
Do not place the outdoor unit near the handrail of the balcony.
Children may climb onto the outdoor unit, lean over the handrail and fall over.
Useonlyaspecifiedpowercable.Poorconnection,poorelectricalinsulation,andexceed-
ing the allowable current will lead to electric shock and fire
.
Attach the connecting cables securely to the terminal. Or secure it firmly with a "wiring
suppressor".
Loose connection will lead to malfunction, electric shock, and fire.
Install a breaker to cut off all AC main current at the same time.
If you do not install a breaker, it may cause electric shock and fire.
During installation, make sure that the refrigerant pipe is attached firmly before you run
the compressor.
Do not operate the compressor under the condition of refrigerant pipes not attached
properly with the valves open. This may cause abnormal pressure in the refrigeration
cycle that leads to rupture and even injury.
During the pump-down operation, make sure that the compressor is turned off before
you remove the refrigerant pipes. Do not remove the connection pipe while the com-
pressor is in operation with the valves open. This may cause abnormal pressure in the
refrigeration cycle that leads to breakage and even injury.
If there is a possibility of touching the fan during maintenance, make sure to turn OFF
the power before implementing the maintenance. Even if operations are suspended,
the fan of outdoor unit sometimes rotates, so if the fan rotates suddenly while in contact
with you may cause serious injury.
9378945746-02_IM_En_240404_2.indd 19378945746-02_IM_En_240404_2.indd 12024/04/04 16:25:562024/04/04 16:25:56

Beoordeel deze handleiding


Product specificaties

Merk: Fujitsu
Categorie: Airco
Model: AJG090JATAH

Foutcodes Fujitsu AJG090JATAH

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing Pagina
E13.1 Communicatiefout tussen buitenunits
E14.1 Netwerkcommunicatiefout 1 buitenunit
E14.2 Netwerkcommunicatiefout 2 buitenunit
E14.5 Tekort aan aantal binnenunits
E28.1 Fout bij automatische adresinstelling
E28.4 Fout bij automatische adressering van signaalversterker
E5U.1 Diverse fout binnenunit 23
E61.2 Onderspanningsfout buitenunit
E61.5 Omgekeerde fase, ontbrekende fasedraad buitenunit
E63.1 Inverterfout buitenunit
E68.2 Fout temperatuurstijging inschakelstroombegrenzingsweerstand buitenunit (beveiligingswerking)
E71.1 Fout persthermistor 1 buitenunit
E72.1 Fout temperatuursensor 1 compressor buitenunit
E74.1 Fout buitenluchtthermistor
E75.1 Fout zuiggasthermistor buitenunit
E77.1 Fout koellichaamthermistor buitenunit
E82.2 Fout gasuitlaatthermistor subkoelwarmtewisselaar buitenunit
E83.1 Fout vloeistofleidingthermistor 1 buitenunit
E83.2 Fout vloeistofleidingthermistor 2 buitenunit
E84.1 Fout stroomsensor 1 buitenunit (permanente stop)
E86.1 Fout persdruksensor buitenunit
E86.3 Fout zuigdruksensor buitenunit
E86.4 Fout hogedrukschakelaar 1 buitenunit
E93.1 Opstartfout invertercompressor buitenunit
E94.1 Uitschakeldetectie (trip) buitenunit
E95.5 Synchronisatieverlies compressormotor buitenunit
E97.1 Blokkeringsfout ventilatormotor buitenunit
E97.5 Temperatuurfout ventilatormotor buitenunit (beveiligingsactie)
E97.9 Fout driver ventilatormotor buitenunit
E98.1 Blokkeringsfout ventilatormotor 2 buitenunit
E98.5 Temperatuurfout ventilatormotor 2 buitenunit (beveiligingsactie)
E98.9 Fout driver ventilatormotor 2 buitenunit
E9A.1 Fout spoel 1 (expansieventiel 1) buitenunit 23
E9A.3 Fout spoel 3 (expansieventiel 3) buitenunit 23
EA1.1 Fout perstemperatuur 1 buitenunit
EA3.1 Temperatuurfout compressor 1 buitenunit
EA4.1 Hogedrukfout buitenunit
EA4.2 Hogedrukbeveiliging 1 buitenunit
EA5.1 Lagedrukfout buitenunit
EAC.4 Temperatuurfout koellichaam buitenunit

Alle foutcodes Fujitsu Airco