Assembly and
operating instructions
Gas condensing boilers
MGK-130
MGK-170
MGK-210
MGK-250
MGK-300
Document no. 3062880_201305Subjecttotechnicalmodications
These installation instructions are to be retained by the user.
We cannot accept any warranty claims if these operating instructions have not been
observed.
GB
Wolf GmbH · Postfach 1380 · D-84048 Mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztechnik.de

Beoordeel deze handleiding


Foutcodes Wolf MGK-130

Foutcodes uit de officiële handleiding, met betekenis en oplossing.

Code Betekenis Oplossing Pagina
1 TBV excess temperature, water pressure too low, fault condensate pump Check the system pressure. Check the heating circuit pump. Vent the system. Press the reset button. Check the condensate pump. Increase system pressure 48
11 Flame pretence Press the reset button 48
12 Faulty flow sensor, gas pressure too low Check lead. Check the flow sensor. Check gas pressure. Check the gas pressure switch settings 48
14 Cylinder sensor faulty Check sensor and lead 48
15 Outside temperature sensor faulty Check lead. Check the outside temperature sensor 48
16 Return sensor faulty Check lead. Replace the return sensor 48
20 Fault, gas valve "1" Replace the gas combination valve 48
21 Fault, gas valve "2" Replace the gas combination valve 48
24 Gas fan fault Check the gas fan supply cable and the gas fan; press the reset button 48
25 Gas fan fault Check the gas fan supply cable and the gas fan; press the reset button 48
26 Gas fan fault Check the gas fan supply cable and the gas fan; press the reset button 48
30 CRC fault, gas condensing boiler Switch the power supply OFF and ON. If unsuccessful, replace the control PCB 48
31 CRC fault burner Switch the power supply OFF and ON. If unsuccessful, replace the control PCB 48
32 24VAC supply faulty Check the gas fan 48
33 CRC fault; default values Replace the control PCB 48
34 CRC error BCC Exchange parameter plug 48
35 BCC missing Plug in the correct parameter plug 48
36 CRC error BCC Exchange parameter plug 48
37 Wrong BCC Plug in the correct parameter plug 48
38 BCC no. invalid Exchange parameter plug 48
39 BCC system error Exchange parameter plug 48
4 No flame builds Check the gas supply line and open the gas valve, if necessary. Check the ignition electrode and ignition cable. Press reset 48
41 Flow monitoring Vent the heating system, check the system pressure. Check the heating circuit pump 48
43 Burner starts >20 per hour Check the flow rate; Header sensor must measure the common feed temperature of the cascade 48
5 Flame failure during operation Check CO values. Check ionisation electrode and cable. Press the reset button 48
50 Activation of the parameter plug Press the reset button twice 48
52 Activation of the parameter plug Press the reset button twice 48
6 TW excess temperature Check the system pressure. Vent the system. Increase pump speed 48
60 Ionisation current fluctuates Clean siphon, check flue gas system, check ventilation air, check monitoring electrode 48
61 Ionisation current fails Check monitoring electrode and lead 48
7 TBA excess temperature, overpressure in the flue gas system Clean the heat exchanger, check the flue gas system. Check ventilation air system. Check flue gas pressure switch 48