Bekijk gratis de handleiding van Speakman SE-575 (2 pagina’s), behorend tot de categorie Kraan. Deze gids werd als nuttig beoordeeld door 13 mensen en kreeg gemiddeld 4.4 sterren uit 8 reviews. Heb je een vraag over Speakman SE-575 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
02/21/18 www.speakman.com 92-1451-08
SPEAKMAN
®
SE-575
Installation, Operation & Maintenance Instructions
EYESAVER® EYE/FACE WASH
DESCRIPTION
Wall mounted emergency eye/face wash. Supplied with stay-open full flow ball valve; activated by stainless
steel paddle handle; twin spray heads with individual flow restrictors, and flip-off dust covers.
SPECIFICATIONS
SPRAY HEADS: (2) Aerated Yellow Abs Plastic Spray Outlets and Dust Cover
VALVE: 1/2” NPT Female Brass, Chrome-Plated
ACTIVATOR: Stainless Steel Push Handle
INLET: 1/2” NPTM
SHIPPING WEIGHT: 4.43 LBS
EMERGENCY SIGN: 7-7/8” X 7-7/8” Plastic Wall Sign
INSTALLATION
NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing
pressure of 30 PSI and a maximum static pressure of 125 PSI.
Review rough-in drawing to assure proper installation. If unit is being mounted on a wall, drill a hole in wall
38-1/2” above floor for piping eye/face wash to a supply. Be sure to leave a minimum of 6-1/2”
between center of valve and finished wall, for handle clearance when operating. Connect a water supply
to the unit (use pipe sealant on all joints) that is a 1/2” minimum uninterrupted source of potable water.
Failure to use potable water can result in emergency units producing impure or contaminated water
causing possible further injury. Make sure unit is level so that an even spray pattern will be produced by
eye/face wash.
OPERATION
The eye/face wash is activated by pushing the paddle handle forward 90 degrees. Once the unit is activated,
water will discharge from the spray outlets until the trigger bar is manually pulled back to the "Off" position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be
activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a
testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspector’s initials
should be noted.
MAINTENANCE
The valve and the eyewash are the only portions of the unit that may require maintenance. Should you need
parts to repair this unit, please reference the parts listing below for correct part numbers. Before any
maintenance is done be sure to shut the water supply off.
Product specificaties
| Merk: | Speakman |
| Categorie: | Kraan |
| Model: | SE-575 |
Heb je hulp nodig?
Als je hulp nodig hebt met Speakman SE-575 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Kraan Speakman
30 December 2026
29 December 2026
29 December 2026
28 December 2025
28 December 2025
25 December 2025
25 December 2025
24 December 2025
24 December 2025
24 December 2025
Handleiding Kraan
Nieuwste handleidingen voor Kraan
14 Januari 2026
14 Januari 2026
13 Januari 2026
13 Januari 2026
13 Januari 2026
13 Januari 2026
13 Januari 2026
12 Januari 2026
12 Januari 2026
12 Januari 2026