Silent Knight SD505-6IB Handleiding


Bekijk gratis de handleiding van Silent Knight SD505-6IB (1 pagina’s), behorend tot de categorie Detector. Deze gids werd als nuttig beoordeeld door 31 mensen en kreeg gemiddeld 5.0 sterren uit 16 reviews. Heb je een vraag over Silent Knight SD505-6IB of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/1
P/N 151175
SILENT
KNIGHT
®
SD505-6IB (6” Isolator Base)
Installation Instructions
The SD505-6IB is a 6 inch isolator base that fits
underneath the 6 inch detector base.
Class A (Style 7) Configuration
An isolator base is used to isolate a short circuit
wiring fault on a Class A (Style 7) SLC loop.
Normally if the control panel detects a short on
the SLC loop the entire loop is disabled. When
isolator modules are used (as shown in Figure 1)
and a short, open or ground fault occurs on the
SLC loop, it will be detected as a trouble but all
the SLC devices will continue to operate.
Figure 1: Class A (Style 7) Example
Class B (Style 4) Configuration
Figure 2: Class B (Style 4) Example
1. If a short occurs at point A (Figure 2),
isolator base 1 will activate, isolating SLC
devices 2 and 3 from the rest of the loop.
2. If a short occurs at point B (Figure 2),
isolator base 2 will activate, isolating SLC
devices 5 and 6 from the rest of the loop.
3. If a short occurs at point C (Figure 2),
isolator base 3 will activate, isolating SLC
devices 8 and 9 from the rest of the loop.
SD505-6IB Specifications
Specification Parameter Rating
Operating Temperature: 32° - 12 F
(0° - 49° C)
Dimensions:
Length: 4-7/8”
Width 4-7/8
Depth: 7/8”
Operating Voltage: 32 VDC
Battery Current Draw dur-
ing AC loss:
Alarm/Standby: 92 uA
SLC Current: 50 uA
Max. SLC Loop Resistance: 50
For indoor use only
0-50 devices,
up to 10 per
branch


Product specificaties

Merk: Silent Knight
Categorie: Detector
Model: SD505-6IB
Kleur van het product: Wit
Breedte: 123.82 mm
Diepte: 22.2 mm
Hoogte: 123.82 mm
Montagewijze: Opbouwmontage
Certificering: UL, CSFM, MEA 284-91-E Vol. III
Ingangsspanning: 32 V
Bedrijfstemperatuur (T-T): 0 - 49 °C
Relatieve vochtigheid in bedrijf (V-V): 10 - 85 procent

Heb je hulp nodig?

Als je hulp nodig hebt met Silent Knight SD505-6IB stel dan hieronder een vraag en andere gebruikers zullen je antwoorden