Seco-Larm SA-025Q Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Seco-Larm SA-025Q (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 18 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
- 1 -
The SA-025Q Programmable Timer Module is suitable for a wide range of timed security
and access control operations, such as door unlock timing, siren or bell timer, VCR timer,
and so on. Auto-sensing of input voltage and DIP switches for programming make
installation easy.
Features / Specifications:
• Timer can be set from 1 second to 60 minutes
• Can be triggered via a N.O. positive (+) trigger input signal or a N.C. negative (-) trigger
device or by powering up the unit
• Relay can be programmed to activate at the start or at the end of the timing cycle
• Relay can also be set to activate for one second at the end of the timing cycle
• Relay can be programmed to pulse (flash) or be steady on
• Built-in reset function to manually reset timing cycle
• Form-C relay, contacts rated 8A @ 120VAC/24VDC
• LED indicates relay is energized
• 12VDC/24VDC operation (auto sensing)
• Current draw – Less than 1mA (standby) or 50mA (relay energized)
• Board measures 2-7/8” x 2-1/2” (73 x 63 mm)
• Functions programmed via DIP switches – no jumpers to cut
Fig. 1 – DIP switch settings
Switch
#1
#2
#3
#4
#5
#6
Off
Fixed 1 sec. Relay
output time
Relay energizes at start
of timing cycle
REPEAT timing cycle
Time in MINUTES
Timing controlled by
TRG input
Counter begin at START
of TRG
On
Variable Relay output
time
Relay energizes at
end of timing cycle
SINGLE timing cycle
Timing in SECONDS
Timing controlled by
Power Up
Counter begin at END
of TRG
Wiring:
•TRG – N.O. Positive (+) trigger input
signal or
– N.C. Negative (
-
) trigger input
signal
(1K ohm resistor
required - included)
•(-) – Ground input
•(+) – +12VDC to +24VDC input
•NO – Relay output (normally open)
•COM – Relay output (common)
•NC – Relay output (normally closed)
DIP Switch Settings (Programming):
The SA-025Q is programmed via a
series of six DIP switches which can be
turned on or off. See fig. 1.
b. Action – If the TRG terminal is connected to (+) for the time set by the timer, the
relay activates and remains activated. To reset the latched relay, connect the TRG
terminal momentarily to (+) again.
c. Triggering by powering unit up – If DIP switch #5 is set to ON, the delay period set
by the timer starts when the SA-025Q is powered up. At the end of the delay period,
the relay latches on and remains on until the SA-025Q is disconnected from power.
5. Pulsing or Flashing Output, instant or delay (Fig. 6):
a. DIP switch settings:
1 – Relay output mode, see below
2 – Instant/delay start, see below
3 – OFF
4 – Timer setting (ON or OFF)
5 – OFF
6 – OFF
b. Action – If the TRG terminal is connected to (+) momentarily, the SA-025Q waits for
the time set by the timer, and then starts pulsing/flashing. The pulse/flash output lasts
until the TRG terminal is disconnected from (+).
c. Triggering by powering unit up – If DIP switch #5 is set to ON, the output works the
same, but instead of triggering via the TRG terminal, the SA-025Q is triggered by
being powering up.
d. Instant/delay start – If DIP switch #2 is set to ON, the SA-025Q waits for the time set
by the timer after triggered or powered up, and then starts pulsing/flashing. If DIP
switch #2 is set to OFF, the SA-025Q starts pulsing/flashing as soon as it is triggered
or powered up.
e. Relay output time – If DIP switch #1 is set to ON, the relay on and off time depends
on how the timer is set. If DIP switch #1 is set to OFF, the relay on time is fixed at
about 1 second, and the relay off time depends on how the timer is set.
6. Optional Negative Trigger or Closed-Circuit Trigger (Fig. 7):
If a closed-circuit negative trigger is required, it is necessary to install a 1K
(1,000-ohm) resistor as shown (included).
- 2 -
Setting the Timer:
The relay output time can be programmed for either 1 to 60 seconds, or 1 to 60 minutes,
using the round, black thumbwheel:
1. Determine and set DIP switch #4 according to whether the timing should be measured in
seconds or minutes (see DIP Switch Settings above).
2. Turn the thumbwheel on the SA-025Q clockwise to increase time, and counter-clockwise to
decrease time.
3. Test the time, and make adjustments as needed.
NOTE – You should carefully test the time period once it is set.
Sample Installations for Common Timer Applications:
NOTE – The following only represents a few of the many possible ways to use this Timer
Module. For your specific application, it may be necessary to experiment with the DIP
switch settings.
1. Momentary trigger, no delay (for timed annunciator or supervisory circuit) (Fig. 2):
a. DIP switch settings:
1 – ON
2 – OFF
3 – ON
4 – Timer setting (ON or OFF)
b. Action – If the TRG terminal is connected to (+) momentarily, the relay output
immediately turns on. The output stays on for the time set by the timer, after which it
turns off regardless of whether the trigger is connected or disconnected.
NOTE – If the momentary trigger time is less than the time set by the timer, the relay
output is triggered only once. If the trigger time is longer than the timer time, the relay
will be activated a second time when the trigger is removed.
c. N.O. vs. N.C. output – For a timed door annunciator, connect a buzzer or chime to
the N.O. and COM outputs. For a closed-loop supervisory circuit, connect a dialer or
transmitter to the N.C. and COM outputs.
2. Momentary trigger, no delay (for swinger eliminator) (Fig. 3):
a. DIP switch settings:
1 – ON
2 – OFF
3 – ON
4 – Timer setting (ON or OFF)
b. Action – If the TRG terminal is connected to (+) momentarily, the relay output
immediately turns on, and stays on for as long as the TRG terminal is connected to
(+). Once the TRG connection is broken, the relay output remain activated for as long
as the time period set by the timer, and then turns off.
c. Triggering by powering unit up – If DIP switch #5 is set to ON, the output works the
same, but instead of triggering via the TRG terminal, the SA-025Q is triggered by
powering it up. Once powered up, the relay remains activated for the time set by the
timer, or until power is removed, whichever comes first.
3. One-time 1-sec. momentary trigger, no delay (Fig. 4):
a. DIP switch settings:
5 – OFF
6 – OFF
5 – OFF
6 – ON
1 – OFF
2 – OFF
3 – ON
4 – Timer setting (ON or OFF)
5 – OFF
6 – ON
- 3 -
Fig. 2 – Momentary trigger, no delay
Fig. 7 – Optional negative or
closed-circuit trigger
Fig. 6 – Pulse/flash o/p, instant/delay
Fig. 5 – Latched output, delayedFig. 4 – 1-time mom. trigger, no delay
Fig. 3 – Momentary trigger, no delay
*(1K ohm resistor included)
*
DIP #1 setting Function
OFF 1-sec. momentary relay output
ON (DIP #3 ON) Relay output latches on
ON (DIP #3 OFF) Relay output equals 1 sec.
b. Action – If the TRG terminal is connected to (+) momentarily, the relay output
immediately activates for about one second. To reset the SA-025Q, the TRG must be
disconnected from (+) for at least two seconds. The timer has no effect.
c. Triggering by powering unit up – If DIP switch #5 is set to ON, the output works the
same, but instead of triggering via the TRG terminal, the SA-025Q is triggered by
being powered up.
4. Latched Output, delayed (Fig. 5):
a. DIP switch settings:
1 – ON
2 – ON
3 – ON
4 – Timer setting (ON or OFF)
5 – OFF
6 – OFF


Product specificaties

Merk: Seco-Larm
Categorie: Niet gecategoriseerd
Model: SA-025Q

Heb je hulp nodig?

Als je hulp nodig hebt met Seco-Larm SA-025Q stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Seco-Larm

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd