Bekijk gratis de handleiding van Schneider TeSys D LR97D25 (4 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 30 mensen en kreeg gemiddeld 4.3 sterren uit 6 reviews. Heb je een vraag over Schneider TeSys D LR97D25 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/4
W9 1636662 01 A03
02 - 2011
1/4
www.schneider-electric.com
A
B
DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Disconnect all power before servicing
equipment.
Failure to follow these instructions
will result in death or serious injury.
LR97Dppp
0.3 - 1.5 A
1.2 - 7 A
5 - 25 A
20 - 38 A
Relay setting range
LR97D015
LR97D07
LR97D25
LR97D38
Type
Power
supply
(1) Select function by dip switch:
b dip switch 1: 1 phase / 3 phase
b dip switch 2: Manual / Auto reset
Available for 3 phase utilisation only (Dip SW on "3P" position)
Combined signals from red and green LEDs indicate
motor status including trip causes.
Condition
LED Signal (Pulse Chart)
Green LED
On
On
On
Off
Off
Off
Off
Off
Off
Off
On
Red LED
Power on
Starting
Steady state
Overloading
Overcurrent
Trip
Locked rotor
Phase
Loss
L1
L2
L3
2T14T26T3
A1A298NONC9596
Test/Stop
Reset
Relay output
Green LED
(LED OK)
Load
O-Time
D-Time
Red LED
(LED OL)
PLEASE NOTE:
b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
b No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
website at www.schneider-electric.com.
Operating and Function
b LR97D, solid state overload relay, compares motor
current with preset load current threshold (LOAD).
b Three phase motor currents are monitored through
three internal current transformers.
b D-Time counts down and is only available for
motor starting.
During steady state, if motor current is greater than the current setting (overloaded), LR97D
switches its contacts after O-Time.
In case of phase failure and locked rotor, trip delay time is 3 s and 0.5 s respectively.
b For shear-pin (mechanical shock) protection, set O-Time knob to its minimum in order to trip in 0.2-0.3 s.

Beoordeel deze handleiding

4.3/5 (6 Beoordelingen)

Product specificaties

Merk: Schneider
Categorie: Niet gecategoriseerd
Model: TeSys D LR97D25
Gewicht: 172 g
Breedte: 45 mm
Diepte: 67.5 mm
Hoogte: 67.5 mm
Gewicht verpakking: 182 g
Breedte verpakking: 76 mm
Diepte verpakking: 69 mm
Hoogte verpakking: 50 mm
Internationale veiligheidscode (IP): IP20
Temperatuur bij opslag: -30 - 80 °C
Frequentie: 50/60 Hz
Bedrijfstemperatuur (T-T): -25 - 60 °C
Nominale input voltage: 600 V
Garantieperiode: 1.5 jaar
Nominale isolatiespanning: 600 V
Nominale impulsweerstandsspanning (Uimp): 6 kV

Heb je hulp nodig?

Als je hulp nodig hebt met Schneider TeSys D LR97D25 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden