Midea Oasis MSOW Handleiding

Midea Airco Oasis MSOW

Lees hieronder de đź“– handleiding in het Nederlandse voor Midea Oasis MSOW (2 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 17 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
1. Determine hole positions according to left and right
side of the installation plate. The hole center is obtained
by measuring the distance as shown in the diagram above.
2. Dirll the piping plate hole with 65mm hole-core drill.
3. Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
4. Always take steps to protect the pipe when drilling metal
grid,metal plate or the like.
INSTALLATION MANUAL FOR
ROOM AIR CONDITIONER
(Split Wall-Mounted Type)
DRILL A HOLE IN THE WALL
INSTALLATION PLATE MOUNTING
2
1
I
N
D
O
O
R
U
N
I
T
Please read these safety precautions carefully before installation
Be sure to follow all the precautions below, they are all important for ensuring safety.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
1) This equipment must be grounded and installed with ground leakage current breaker. It may cause
electrical shock if grounding is not perfect.
2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and
accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water
may enter the room and damage the furniture.
1) Install according to this installation instructions strictly. If installation is defective, it will cause water
leakage, electrical shock,or fire.
2) Use the included accessories parts and specified parts for installation. otherwise, it will cause the set
to fall, water leakage, electrical shock,or fire.
3) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not
enough or installation is not properly done, the set will drop and cause injury.
4) For electrical work, follow the local national wiring standard, regulation and this installation instructions.
An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or
defect found in electrical work, it will cause electrical shock,or fire.
5) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted
on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
6) Wiring routing must be properly arranged so that control board cover is fixed properly. If control board
cover is not fixed perfectly, it will overheat at connection point of terminal, fire or electrical shock.
7) When carrying out piping connection, take care not to let air substances other than the specified
refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity,abnormal high pressure
in the refrigeration cycle, explosion and injury.
8) Do not modify the length of the power supply cord or use of extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
SAFETY PRECAUTIONS
CAUTION
WARNING
CAUTION
WARNING
Please read this installation manual carefully before operating the unit to ensure correct installation.
If the power cord is damaged, replacement work shall be performed by authorised personnel only.
Installation work must be performed in accordance with the national wiring standards by authorised
personnel only.
Contact an authorized service technician for repair, maintenance and installation of this unit.
This appliance is not intended for use by persons(including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by persons responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
All the pictures in the instructions are for explanation purposes only. The actual shape should prevail.
The design and specifications are subject to change without prior notice for product improvement.
Consult with the sales agency or manufacturer for details.
There should not be any heat source or stream
near the unit.
There should not be any obstacles blocking the
air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall,ceiling,fence or other obstacles.
There should not be any direct sunlight. If unavoidable,
sunlight prevention should be taken into consideration.
Outdoor unit dimension
mm(WxHxD)
A(mm) B(mm)
530 290
560
549
640
335
325
404
481
549
276
276
Mounting dimensions
670x540x265
780x540x250
760x590x285
845x700x320
810x558x310
940x810x375
Indoor unit
Outdoor unit
If an awning is built over the unit to prevent
direct sunsight or rain,be careful that heat
radiation from the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrow from wall
ceiling, fence or other obstacles.
Do not place any obstacles which may cause
a short circuit of the discharged air.
Anchor the outdoor unit with a bolt and nut 10 or
8 tightly and horizontally on a concrete or rigid mount.
Settlement of outdoor unit
NOTE: The outdoor unit you purchase may be like one
of the following. Install the outdoor unit according to the
dimension as indicated in the table below:
A
W
B
D
Air inlet
Air outlet
Air inlet
INSTALLATION PRECAUTIONS
CONNECT THE CABLE TO THE INDOOR UNIT
3
,
Terminal block of indoor unit
Connect the cable to the indoor unit
Before performing any electrical work, turn off the main power to the system.
1. The inside and outside connecting cable can be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and
interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw.
4. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor s
respectively.
5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch
any electrical components. Secure the cable onto the control board with the cord clamp.
NOTE:
Electronic box
cover
Front Panel
To outdoor unit
Model A Model B
To outdoor unit
L(1)
2(N)
S
1
W
2(N)
S
1(L)
1
2
3
4
5
7
8
9
10
6
Installation Plate
Clip Anchor
Self-tapping Screw A ST3.9x25
Seal(For cooling & heating models only)
Drain Joint(For cooling & heating models only
Connecting
pipe
Assembly
Liquid side
Gas side
Remote controller
Self-tapping Screw B ST2.9x10
6.35
9.52
9.52
12.7
16
Parts you must purchase. The pipe
size differ from appliance to appliance.
Consult the technician for the proper
size.
1
5-8(depending on models)
5-8(depending on models)
1
1
1
2
1
1
Except the above parts provided,the other parts needed during installation you must
purchase.
Remote controller holder
ACCESSORIES
Number
Name of Accessories Qty
NOTE:
optional
parts
SELECT THE BEST LOCATION
NOTE: If used as MONO unit, for the standby control needs, the cross section area of cable connected
to L(1)/W, 1/1(L), 2(N) must be sufficient for the maximum system current. The maximum system current
is equal to the sum of indoor unit and outdoor unit rated current. If used as MULTI unit, L(1)/W on the
terminal block does not need to be connected.
4
CONNECTIVE PIPE AND DRAINAGE INSTALLATION
1. Run the drain hose sloping downward.
Do not install the drain hose as illustrated
in wrong figures.
2. When connecting extension drain hose,
insulate the connecting part of extension
drain hose with a shield pipe, do not let
the drain hose slack.
Drainage
Right Wrong
Correct orientation
of Installation Plate
1. Fit the installation plate horizontally on
structural parts of the wall withspaces
around the installation plate.
2. If the wall is made of brick, concrete
or the like, drill five or eight 5mm
diameter holes in the wall. Insert
clip anchor for appropriate mounting
screws.
3. Fit the installation plate on the wall
with five or eight type A screws.
Mount the Installation Plate and drill
holes in the wall according to the wall
structure and corresponding mounting
points on the installation plate. The
installation plate providedwith the
machine differ from appliance
to appliance.(Dimensions are in
mm unless otherwise stated)
NOTE:
NOTE:
"
"
Installation Plate Mounting
The mounting wall is strong and solid enough
to prevent it from the vibration.
45
45
280
120mm or
more to wall
120mm or
more to wall
120mm or
more to wall
150mm or more to ceiling
150mm or more to ceiling
Left rear side
refrigerant
pipe hole 65
36.5
835
140 110
Left rear side
refrigerant
pipe hole 65
Right rear side
refrigerant
pipe hole 65
Right rear side
refrigerant
pipe hole 65
Indoor unit outline
Indoor unit outline
120mm or
more to wall 120mm or
more to wall
Indoor unit outline
990
315
135
260
150mm or more to ceiling
Left rear side
refrigerant
pipe hole 65 Right rear side
refrigerant pipe
hole 65
Model C
Model B
Model A
120mm or
more to wall
45
45
36.5
750
180 110
280
202000192486 CS159I1-BP11M(L) 20140515
Air freshening filter(used to install on Air filter)
Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse to install
the air conditioner and explain to the client until the problem is solved.
2. Power voltage should be in the range of 90%~110%of rated voltage.
3. The surge protector and main power switch with a 1.5 times capacity of Max. Current of the unit should
be installed in power circuit. Ensure the air conditioner is grounded well.
4. The appliance shall be installed in accordance with national wiring regulations. Do not operate your air
conditioner in a wet room such as a bathroom or laundry room.
5. An all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage
current that may exceed 10mA, the residual current device(RCD) having a rated residual operating
current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance
with the wiring rules.
6. For the unit adopts auxiliary electric heater, keep at least 1 meter away from the nearest combustible
materials.
7. According to the attached Electrical Connection Diagram located on the panel of the indoor & outdoor
unit to connect the wire.
8. All wiring must comply with local and national electrical codes and be installed by qualified and
skilled electricians.
9. An individual branch circuit and single receptacle used only for this air conditioner must be
available. See the following table for suggested wire sizes and fuse specifications:
Minimum cross-sectional area of conductors:
Rated curr ent
of appliance
(A)
>3 and 6
>6 and 10
>10 and 16
>16 and 25
>25 and 32
>32 and 40
Nominal cross-sectional
area
(mm2)
0.75
1
1.5
2.5
4
6
Electrical work
The wire size of power supply cord and
interconnected wire and the current of
the fuse or switch are determined by the
maximum current indicated on the
nameplate which located on the side
panel of the unit. Please refer to the
nameplate before selecting the wire size,
fuse or switch.
The controller of the air conditioner
designed with a fuse protection function
under abnormal conditions, the
specifications of the fuse have printed on
the circuit board, such as: T3.15A/250VAC,
T5A/250VAC, etc.
NOTE:
Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
Determine the air outlet direction where the discharged air is not blocked.
In the case that the installation place is exposed to strong wind such as a seaside, make
sure the fan operating properly by putting the unit lengthwise along the wall or using a dust
or shield plates.
Specially in windy area, install the unit to prevent the admission of wind. If need suspending
installation, the installation bracket should accord with technique requirement in the
installation bracket diagram. The installation wall should be solid brick, concrete or the same
intensity construction, or actions to reinforce, damping supporting should be taken.
The connection between bracket and wall, bracket and the air conditioner should be firm,
stable and reliable.
Be sure there is no obstacle which block radiating air.
Strong
wind
Strong
wind
Barrier
Incorrect Correct
Seal
Drain joint
Base pan hole
of outdoor unit
(A) (B)
The drain joint is slightly different according to the
different outdoor unit.
For the drain joint with the seal(Fig.A), first fit the seal onto
the drain joint, then insert the drain joint into the base pan
hole of outdoor unit, rotate 90 to securely assemble them.
To install drain joint as shown in Fig.B, insert the drain
joint into the base pan hole of outdoor unit until it remains
fixed with a clicking sound. Connecting the drain joint with
an extension drain hose (Locally purchased), in case of the
water draining off the outdoor unit during the heating mode.
2
DRAIN JOINT INSTALLATION
OUTDOOR INSALLATION PRECAUTION
3
REFRIGERANT PIPE CONNECTION
1. Cut a pipe with a pipe cutter.
2. Put flare nuts on pipe/tube having
completed burr removal and flare the pipe.
3. Firmly hold copper pipe in a die in the
dimension shown in the table below.
Align pipes to be connected.
Sufficiently tighten the flare nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Excessive torque can break nut depending
on installation conditions.
Outer diam.
(mm)
A(mm)
Max. Min.
6.35 1.3 0.7
9.52
1.6 1.0
12.7
1.8 1.0
12.7
16
1.8
2.2
1.0
2.0
Bar
Copper pipe Clamp handle
Handle
Bar
"A"
Indoor unit tubing Flare nut Pipings
Outer
diam. Tightening
torque(N.cm) Additional tightening
torque(N.cm)
6.35mm
12.7mm
16mm
9.52mm
1500
(153kgf.cm) 1600
(163kgf.cm)
3500
(357kgf.cm)
4500
(459kgf.cm)
3600
(367kgf.cm)
4700
(479kgf.cm)
2500
(255kgf.cm)
2600
(265kgf.cm)
AIR PURGING AND TEST OPERATION
4
5
1. Remove the electrical control board cover from the outdoor unit by loosening the screw.
2. Connect the connective cables to the terminals as identified with their respective matched numbers
on the terminal block of indoor and outdoor units.
3. Secure the cable onto the control board with the cord clamp.
4. To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation
diagram of indoor and outdoor units.
5. Insulate unused cords (conductors) with PVC-tape. Process them so they do not touch any electrical
or metal parts.
Cover
Screw
Terminal block of outdoor unit
Liquid side: 6.35mm
R22: (Pipe length-5)x30g/m
R410A: (Pipe length-5)x15g/m
Liquid side: 9.52mm:
R22: (Pipe length-5)x60g/m
R410A: (Pipe length-5)x30g/m
Connective pipe length
Less than 5m
More than 5m
Air purging method
Use vacuum pump
Additional amount of refrigerant to be charged
Open the valve stem until it hits against
the stopper. Do not try to open it further.
Securely tighten the valve stem cap with
a spanner or the like.
Valve stem cap tightening torque. See
Tightening torque table.
Flare nut
Stopper
Cap
Valve body
Valve stem
Use vacuum pump
For the R410A refrigerant model, make sure the refrigerant added into air conditioner is liquid
form in any cases.
When relocating the unit to another place, using vacuum pump to perform evacuation.
The indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated
to remove any noncondensables and moisture from the system.
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test run has been completed.
Pipe length and refrigerant amount:
Outdoor
unit
Indoor
unit
Refrigerant
Packed valve
Flare nut
Gas side
Liquid side
AC
D
B
1. Completely tighten the flare nuts, A, B, C, D, connect
the manifold valve charge hose to a charge port of the
packed valve on the gas pipe side.
2. Connect the charge hose connection to the vacuum
pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting
evacuation, slightly loose the flare nut of the packed
valve on the gas pipe side and check that the air is
entering. (Operation noise of the vacuum pump changes
and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the handle
Lo of the manifold valve and stop the operation of the
vacuum pump.
Make evacuation for 15 minutes and more and check
5
that the compound meter indicates -76cmHg(-1.0x10 Pa).
O
6. Turn the stem of the packed valve B about 45 counter-
clockwise for 6~7 seconds after the gas coming out, then
tighten the flare nut again. Make sure the pressure display
in the pressure indicator is a little higher than the atmosphere
pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.
Manifold valve
Compound meter
-76cmHg
Handle Lo Handle Hi
Charge hose Charge hose
Vacuum pump
Pressure gauge
Packed valve
Perform test operation after completing gas leak check at the flare nut connections and electrical
safety check.
Check that all tubing and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions works
well.
O
3. When the ambient temperature is too low(lower than 17 C), the unit cannot be controlled by the
remote controller to run at cooling mode, manual operation can be taken. Manual operation is
used only when the remote controller is disable or maintenance necessary.
Hold the panel sides and lift the panel up to an angle until it remains fixed with a clicking sound.
Press the Manual control button to select the AUTO or COOL, the unit will operate under Forced
AUTO or COOL mode(see User Manual for details).
4. The test operation should last about 30 minutes.
Flaring
Tightening connection
1. Air purging
2. When using the Vacuum Pump
4. Test running
3. Safety and leakage check
A: Lo packed valve B: Hi packed valve
C and D are ends of indoor unit connection.
CAUTION
1. Soap water method:
Apply a soap water or a liquid neutral detergent on the indoor
unit connections and outdoor unit connections by a soft brush
to check for leakage of the connecting points of the piping. If
bubbles come out, it indicates that the pipes have leakage.
2. Leak detector
Use the leak detector to check for leakage.
O
U
T
D
O
O
R
U
N
I
T
CONNECT THE CABLE TO THE OUTDOOR UNIT
CAUTION
1
Indoor unit
check point D
B
C
A
Outdoor unit
check point
Cover
NOTE:
To indoor unit To indoor unit
Power supply
Model A Model B
Power supply
Oblique
Roughness
Burr
O
90
AUTO/COOL
AUTO/COOL
AUTO/COOL
AUTO/COOL
AUTO/COOL
Manual control button
Connect the indoor unit first, then the
outdoor unit.
Do not allow the piping to let out from the
back of the indoor unit.
Be careful not to let the drain hose slack.
Heat insulation should be done to the
extension drain hose of indoor unit.
Be sure that the drain hose is located at
the lowest side of the bundle. Locating at
the upper side can cause drain pan to
overflow inside the unit.
Never intercross nor intertwist the power
wire with any other wiring.
1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion
of installation plate(Engage the indoor unit with
the upper edge of the installation plate). Ensure
the hooks are properly seated on the installation
plate by moving it in left and right.
3. Piping can easily be made by lifting the indoor
unit with a cushioning material between the
indoor unit and the wall. Get it out after finish
piping.
4. Press the lower left and right side of the unit
against the installation plate until hooks
engages with the their slots.
CAUTION
Indoor unit installation
1. For the left-hand and right-hand piping,
remove the pipe cover from the side panel.
2. For the right back and left back piping,
install the piping as shown.
NOTE:
3. Bundle the tubing, connecting cable, and
drain hose with tape securely, evenly as
shown in Figure on the right.
For 9K/12K model, there is only one
side drainage structure design. For 18k
model, one side drainage structure is standard.
Both sides drainage structure is optional
and can only be customized from factory.
For both sides drainage structure, it can be
choosen for right, left or both sides drainage
connection. If choosing both sides drainage
connection, another proper drain hose is
needed as there is only one drain hose offered
by factory. If choosing one side drainage
connection, make sure the drain hole on the
other side is well plugged. The connection of
the drain hose is supposed to be done by
qualified installer in case of water leakage.
Connective pipe installation
Because the condensed water from rear
of the indoor unit is gathered in ponding
box and is piped out of room. Do not put
anything else in the box.
I
N
D
O
O
R
U
N
I
T
NOTE: Connective pipe length will affect the capacity and energy efficiency of the unit. The
nominal efficiency is tested basing on the pipe length of 5 meters.


Product specificaties

Merk: Midea
Categorie: Airco
Model: Oasis MSOW

Heb je hulp nodig?

Als je hulp nodig hebt met Midea Oasis MSOW stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco Midea

Handleiding Airco

Nieuwste handleidingen voor Airco