Operating instructions
SC teach button
E40211
E40212
704653 / 00 05 / 2010
UK
2
1 Functions and features
E40211 Teach button for setting the SC flow sensors with PNP output
E40212 Teach button for setting the SC flow sensors with normally open relay
output
2 Electrical connection
1 2
1: Connector (socket) - connection to SC flow sensor
2: Connector (plug) - connection to supply voltage
E40211
SC E40211
4
1
3
2n.c.
L1
L+
N
L
n.c.
1
2
4
5
3
n.c.
E40212
L1
L+
N
L
SC E40212
4
1
3
2n.c.
n.c.
1
2
4
5
3
n.c. = not connected
3
UK
3 Switch point setting
â–ºPress button briefly and release it.
â–ºAfter 1 - 2 s press it again and keep it pressed for the time indicated.
> The flow sensor gives its output signals to the teach button. They are displayed
by the illuminated pushbutton:
Output closed (OUT = 1) button lights
Output closed (OUT = 0) button does not light
1...5> 1 3...67 5 5...65 5
A B D E FC
Button
OUT = 1
OUT = 0
Time window
Duration [s]
Within the time windows A, B, C the output is switched depending on the flow: output closed
(OUT = 1/ button lights) if flow SP / output open (OUT = 0 / button does not light) if flow < SP.≥
If flow rises or falls within the time windows A, B, C the switching status / display of the il-
luminated pushbutton can change.
In the time windows D, E, F the output is used for feedback signals (-> table below). It does
not react to flow changes.
Time window Operation
A Initialisation of the setting operation.
B Confirmation of the initialisation.
C Setting of the switch point (SP)*
Push of the button in s 5 10 15 20 ... 55 60 65
corresponds to SP in
cm/s min. 10 15 20 ... 55 60 max.
D The last switching status from C is maintained (= internal monitoring).
E Output signal is inverted (= confirmation of the setting);
duration = setting time of the selected switch point
F Output signal is inverted again (= internal monitoring), then this new switch
point is active.
* Accuracy: ± 1s
min.: flow < 10 cm/s; max.: flow > 60 cm/s


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: E40211

Heb je hulp nodig?

Als je hulp nodig hebt met IFM E40211 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM DP4302 Handleiding

12 April 2024
IFM

IFM EVCB02 Handleiding

11 Maart 2024
IFM

IFM EVCB03 Handleiding

11 Maart 2024
IFM

IFM EVF666 Handleiding

11 Maart 2024
IFM

IFM TM4599 Handleiding

8 Januari 2024
IFM

IFM ZB0074 Handleiding

8 Januari 2024
IFM

IFM EVF661 Handleiding

8 Januari 2024
IFM

IFM IIP201 Handleiding

7 Januari 2024
IFM

IFM DP4200 Handleiding

7 Januari 2024
IFM

IFM IIP200 Handleiding

7 Januari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd