Festo MS6-EE-1/2-V24-F1A-B Handleiding
Festo
Niet gecategoriseerd
MS6-EE-1/2-V24-F1A-B
Bekijk gratis de handleiding van Festo MS6-EE-1/2-V24-F1A-B (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.4 sterren uit 1.5 reviews. Heb je een vraag over Festo MS6-EE-1/2-V24-F1A-B of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

MS6-EE-...-B
On/off valve
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Operating instruction
8181863
2023-02a
[8181865]
8181863
Translation of the original instructions
© 2023 all rights reserved to Festo SE & Co. KG
1
Applicable documents
All available documents for the product
è
www.festo.com/sp.
Document Product Contents
Assembly instructions Wall mounting kit MS...-WPE(-B) –
Tab. 1:
Applicable documents
2 Safety
2.1 Safety instructions
–
Only use the product in its original condition without unauthorised modifica-
tions.
–Only use the product if it is in perfect technical condition.
–
Observe the identifications on the product.
–Take into account the ambient conditions at the location of use.
–Before working on the product, switch off the compressed air supply and lock it
to prevent it from being switched on again.
2.2
Intended use
The on-off valve pressurises and exhausts pneumatic systems. The on/off valve is
not suitable for continuous switching operation for pneumatic components.
3
Additional information
–Accessories
è
www.festo.com/catalogue.
4 Product design
1
2
3
4
6
5
7
Fig. 1:
Product design
1
Pneumatic port P1
2
Solenoid coil plug
(not in scope of delivery)
3
Manual override
4
Pilot valve
5
Pneumatic port P2
6
Orifice
7
Pneumatic port P3
5
Assembly
5.1 Preparing assembly
For use with reduced particle emission:
• Remove soil from the product.
5.2 Wall mounting
–
Space required above the product: 250mm³
–Space required under the product: 100mm³
–Space required left and right of the product: 30mm³
–
Shut-off valves are installed in the compressed air supply line.
• Fasten the product to the mounting surface with the mounting accessories
è
3 Additional information.
6 Installation, pneumatic
1. Screw the fittings into the pneumatic ports.
2. Note the maximum screw-in depth of the connector thread. Screwing in
deeper will reduce the flow rate and can damage the housing. Maximum
screw-in depth:13.5mm
3. Insert suitable tubing into the fitting to the stop.
–
Position tubing axial to the pneumatic ports.
–Do not bend the tubing more than the minimum bending radius.
7
Commissioning
1. Screw the silencers into pneumatic port P3 to the stop. Suitable silencers7
è
3 Additional information.
2.
Mount the solenoid coil plug on the pilot valve. Suitable plugs2
è
3 Additional information.
3. Pressurise the system.
4. Switch the pilot valve .4
–
The product can also be switched on and off with the integrated manual
override.
Ä
There is pressure at pneumatic port P2.
5.
When the pilot valve is switched off, the system is exhausted via pneu-4
matic port P3 .7
8 Cleaning
•
Clean the outside of the product as required with a soft cloth.
Permissible cleaning agents:
–Soap solution, maximum +60°C
–
Petroleum ether, free of aromatic compounds
9 Fault clearance
Malfunction Cause Remedy
Low flow rate (operating pres-
sure is lost with air consump-
tion).
Constriction in the supply line.
–
Check the line.
Continuous audible blowing off
at the exhaust outlet.
The valve seat is damaged.
–
Replace the product.
Tab. 2:
Fault clearance
10 Technical data
10.1
Technical data, mechanical
MS6-EE-...-B
Mounting position [°] Vertical±5
Manual override Non-detenting and detenting
Vibration resistance in accordance with
IEC60068-2-6
Severity level 2
Shock resistance in accordance with
IEC60068-2-27
Severity level 2
Pneumatic port P1 G1/2
Pneumatic port P2
Pneumatic port P3
Temperature of medium [°C] –5…+50
Ambient temperature [°C] –5…+50
Storage temperature [°C] –10…+60
Tab. 3:
Technical data, mechanical
Type of severity level (SL)
Vibration load
Frequency range [Hz] Acceleration [m/s
2
]
Deflection [mm]
SL1 SL2 SL1 SG2 SL1 SL2
2 8 2 8 – – 3.5 3.5… … ± ±
8 27 8 27 10 10 – –… …
27 58 27 60 – – 0.15 0.35… … ± ±
58 160 60 160 20 50 – –… …
160 200 160 200 10 10 – –… …
Shock load
Acceleration [m/s
2
]
Duration [ms] Shocks per direction
SL1 SL2 SL1 SL2 SL1 SL2
± ±150 300 11 11 5 5

Type of severity level (SL)
Continuous shock load
Acceleration [m/s
2
] Duration [ms] Shocks per direction
±150 6 1000
Tab. 4: Type of severity level (SL)
10.2
Technical data, pneumatic
MS6-EE-...-B
Operating medium Compressed air to ISO 8573-1:2010[7:4:4]
Inert gases
Information on the operating medium Lubricated operation not possible
Operating pressure [MPa] 0.3…0.7
[bar] 3…7
[psi] 43.5…101.5
Standard nominal flow rate [l/min] 5000
Standard exhaust flow rate [l/min] 4000³
Tab. 5: Technical data, pneumatic
10.3
Technical data, electrical
MS6-EE-...-B
Electrical connection Plug pattern C
Nominal voltage [VDC] 24±10%
Coil characteristics [VDC] 24
Tab. 6: Technical data, electrical
Product specificaties
Merk: | Festo |
Categorie: | Niet gecategoriseerd |
Model: | MS6-EE-1/2-V24-F1A-B |
Heb je hulp nodig?
Als je hulp nodig hebt met Festo MS6-EE-1/2-V24-F1A-B stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Festo
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
Handleiding Niet gecategoriseerd
- Revlon
- Manhattan
- Flover
- Grillmeister
- Brandt
- Timbersled
- Pulox
- Essenza
- Nitecore
- Stihl
- Befaco
- Winston
- Thermarest
- DSC
- Solo
Nieuwste handleidingen voor Niet gecategoriseerd
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025
15 Juni 2025