Bekijk gratis de handleiding van Emko ATS-10 (7 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 30 mensen en kreeg gemiddeld 4.3 sterren uit 15.5 reviews. Heb je een vraag over Emko ATS-10 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/7

Description
Operation
The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- The ledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
- TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellow ledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgota TEST modefeature. Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning. Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16

2
Automatic Transfer Switch, 72x72 DIN Size
Specifications
EquipmentUse Electricalcontrolequipmentforgeneratingsets
Housing&Mounting 72mmx72mmx95mm(includingconnectors)DIN43700plastichousingforpanelmounting
PanelCut-out 69mmx69mm
Protection NEMA4X(IP65atfrontpanel,IP20atrearside)
Weight Approximately0.27kg
EnvironmentalRating Standard,indooratanaltitudeoflessthen2000meterswithnon-condensinghumidity
Operating/Storage Temperature -25ºCto+70ºC/-40ºCto+85ºC
Operating/StorageHumidity 90%max.(Non-condensing)
InstallationOverVoltageCat. IIappliances,portableequipment
PollutionDegree II,Normalofficeorworkplace,non-conductivepollution
ModeofOperation Continuous
EMC EN-61000-6-4,EMCgenericemissionstandardforindustrialequipment
EN-61000-6-2,EMCgenericimmunitystandardforindustrialequipment
ElectricalSafety EN-61010-1,safetyrequirementsforelectricalequipmentformeasurement,controland
laboratoryuse
BatterySupplyVoltage( )Z8-32V max.Operatingcurrentis240mAZ
CrankingDropouts Batteryvoltagecanbe0V formax.100msnduringcranking(batteryvoltageshouldbeZ
atleastnominalvoltagebeforecranking)
MainsVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
GeneratorVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
Display 4Digits,7segmentsLEDdisplayshowing:
MainsVoltage(Phase-PhaseandPhase-Neutral)
AlternatorVoltage.( )
IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1)
ProgramParameters
StatusIndicators TEST ModeLED
MainsContactorClosedLED
GeneratorContactorClosedLED
ContactSensingInputs LoadGeneratorSignal(NO)
EngineRunningSignal(NO)
RelayOutputs RemoteStartRelay(1NO+1NC.12A@32V )Z
MainsContactorRelay(1NC.5A@250V )V
GeneratorContactorRelay(1NO.5A@250V )V
MainsVolgageOkayLED
GeneratorRunningLED
PROGModeLED

3
Automatic Transfer Switch, 72x72 DIN Size
Maximum15mm/0.590inch
83.5mm/3.287inch11.5mm/0.452inch
72mm
72mm
Dimensions
PanelCut-Out
V GENV.L12 VL23 VL31
TEST
PROG
TEST
ATS-10
69mm/2.72inch
69mm/2.72inch
Product specificaties
Merk: | Emko |
Categorie: | Niet gecategoriseerd |
Model: | ATS-10 |
Heb je hulp nodig?
Als je hulp nodig hebt met Emko ATS-10 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Emko
2 Mei 2025
21 Februari 2025
16 November 2024
16 November 2024
16 November 2024
16 November 2024
16 November 2024
16 November 2024
14 Maart 2024
14 Maart 2024
Handleiding Niet gecategoriseerd
- CaterCool
- Clatronic
- Gefen
- Janitza
- R-Vent
- WarmlyYours
- Akrobat
- Acros
- Gamesir
- JL Cooper
- AMS Neve
- Gamdias
- Stairville
- Lewitt
- PSC
Nieuwste handleidingen voor Niet gecategoriseerd
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
3 Augustus 2025
2 Augustus 2025
2 Augustus 2025