Bekijk gratis de handleiding van Ei Electronics Ei146 Optical (2 pagina’s), behorend tot de categorie Rookmelder. Deze gids werd als nuttig beoordeeld door 106 mensen en kreeg gemiddeld 4.5 sterren uit 2 reviews. Heb je een vraag over Ei Electronics Ei146 Optical of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.Fx. +353 61 471277 +353 61 471053
Email. eielect[email protected]
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei146 DataSht RevA
Model Ei146 Optical
Easi-Fit base
9V Alkaline Battery back up
High performance optical chamber with integral
insect screen
Test/Hush button
Advanced suppression and calibration technology
Interconnectable to other Ei mains powered alarms
Built in auto self test feature
Low power cell warning
Kitemarked to BS EN14604:2005
5 year guarantee
Product Description
The Ei146 is an Optical Smoke Alarm that runs on 230V
AC mains power, and has a 9V alkaline battery back up
in the event of mains failure. The 9V battery will last for
up to 4 years in standby mode, and capable of powering
the smoke detector for up to 2 years in the event of
mains failure.
The Ei146 is supplied with the Easi-Fit base that allows
very quick and simple installation of the smoke alarm,
combined with simple detector head removal and
replacement. The Easi-Fit base automatically connects
both mains power and battery as the detector head
slides on to the Easi-Fit base.
The Ei146 has other advanced features such as high
performance optical chambers fitted with integral insect
screens to reduce the chances of false alarms, as well
as the ability to interconnect up to twelve alarms to allow
all alarms to sound if just one of the interconnected
alarms should be triggered.
The Ei146 has built in circuitry to aid suppression of
voltage transients and RF interference to further reduce
the chances of false alarms under such conditions.
Operation
The green indicator will illuminate to show mains
power is present
The red indicator will flash every 40 seconds to
show that the detector has performed an automatic
self test
The red indicator will flash rapidly to show an alarm
condition for the smoke detector
The “Test/Hush” button will either silence false
alarms or perform a unit self test
In “Test” mode the alarm will perform a self test and
sound the horn
In “Hush” mode the alarm enters a ten minute period
of reduced sensitivity to overcome false alarm
conditions, and will then automatically reset itself
When interconnected to other Ei mains powered
alarms, an alarm on one detector will trigger all other
interconnected alarms within one second (only the
triggered alarm will flash a red indicator)
The smoke detector will emit a beep and flash the
red light every 40 seconds to indicate that the
battery back up is depleted and needs replacing
MAINS POWERED 230V~
9V Alkaline Battery Back- Up
Product specificaties
| Merk: | Ei Electronics |
| Categorie: | Rookmelder |
| Model: | Ei146 Optical |
Heb je hulp nodig?
Als je hulp nodig hebt met Ei Electronics Ei146 Optical stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Rookmelder Ei Electronics
15 November 2024
23 Juni 2023
13 Mei 2023
29 April 2023
29 April 2023
22 April 2023
19 April 2023
18 April 2023
14 April 2023
1 April 2023
Handleiding Rookmelder
Nieuwste handleidingen voor Rookmelder
7 Januari 2026
5 Januari 2026
31 December 2026
31 December 2026
29 December 2026
21 December 2025
10 December 2025
10 December 2025
10 December 2025
10 December 2025