Eastron SDM230-2T Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Eastron SDM230-2T (13 pagina's) in de categorie Meetapparatuur. Deze handleiding was nuttig voor 5 personen en werd door 3 gebruikers gemiddeld met 4.9 sterren beoordeeld

Pagina 1/13
Eastron SDM230-2T User Manual
Z hejiang Eastron Electronic Co.,Ltd. Tel: 0086 Fax: 0086-573-83698881 -573-83698883
Add:No.1369Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
- -1
SDM230- 2T
Single-Phase Two Module DIN Rail Meters
Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Two tariffs measurement
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
U 1 ser Manual V1.
Eastron SDM230-2T User Manual
Z hejiang Eastron Electronic Co.,Ltd. Tel: 0086 Fax: 0086-573-83698881 -573-83698883
Add:No.1369Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
- -2
Application
The energy- meters with a white back-lighted LCD screen for prefect reading are used to measure single-phase
like residential, utility iand ndustrial application. The unit measures and displays various important electrical
parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Specification
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) A 10
Max. Current (Imax) 100A
Mini Current (Imin) 5A 0.
Starting C urrent 0.4% of Ib
Power C onsumption <2W/10VA
Frequency 50/60Hz(±10%)
AC Voltage Withstand 4KV for 1 minute
Impulse Voltage Withstand 6KV-1.2uS wavform
Overcurrent Withstand 30Imax for 0.01s
Pulse Output Rate
- 0 0 Pulse Output 1 100 /10 /10/1 imp/Exp/kWh/kVArh (configurable)
- Pulse Output 2 1000imp/kWh (default) for import kWh
Display LCD with white backlit
Max. Reading .9 999999 kWh/kVArh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency -0.2% of mid frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Active energy - Class 1 IEC62053 21
Class B EN50470- 3 1/
Reactive energy - Class 2 IEC62053 23
Eastron SDM230-2T User Manual
Z hejiang Eastron Electronic Co.,Ltd. Tel: 0086 Fax: 0086-573-83698881 -573-83698883
Add:No.1369Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastrongroup.com Email: sales@eastrongroup.com
- -3
Environment
Operating temperature - 25to +55
Storage and transportation temperature to +70 - 40
Reference temperature 23℃±2
Relative humidity -0 to 95%, non condensing
Altitude 0 up to 2 00m
Warm up time 5s
Installation category CAT II
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVArh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed to import kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured from the set- up menu.
Baud rate: 1200, 2400, 4800, 9600 bps. Default: 2400 bps
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
2T for dual source measurement
This unit supplies. xample, when public and can measure energy from two different power eFor grid is power off el
ectric generator 2 is on, the meter switches to tariff measurement automatically.
The be meter can also a used as tariff meter. The tariff is an controlled by external time relay.
Mechanics
Din rail dimensions 36x100x63 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Ingress protection IP51 (indoor)