Eastron SDM120CT-MV User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn E mail: sales@eastrongroup.com
SDM120CT-MV
Single ail- RPhase Multifunction DIN Meter
Measures kWh, kVArh, KW, VA, PF, Hz, dmd, V, A, etc. kVAr, k
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail 35mm
0.1V AC CT connection
Better than Class 1 accuracy
User Manual V1.6

Eastron SDM120CT-MV User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn E mail: sales@eastrongroup.com
Application
The energy-meters are used to measure single-phase applications like residential, utility and Industrial. The unit
measures and displays various important electrical parameters. It equipped with a white back-lighted LCD screen
for prefect reading. As well as a RS485 communication port for remote reading and monitoring. Bi-directional
energy measurement makes it a good choice for solar PV energy metering. The compact design and din rail
installation provides an easy and economical solution for your metering demand.
PART 1 Specification
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) 0.1V AC
Power consumption <2W/10VA
Frequency 50/ 60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand -6KV 1.2uS wave form
Overcurrent withstand 2 5s 0Imax for 0.
Pulse output 1 1000imp/kWh (default)
Pulse output 2 0.001(default) /0.01/0.1/1 kWh/kVA rh (configurable)
Display LCD with white backlit
Max. Reading 999999kWh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency -0.2% of mid frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Active energy - Class 1 IEC62053 21
Class B EN50470- 3 1/
Reactive energy - Class 2 IEC62053 23

Eastron SDM120CT-MV User Manual
Zhejiang Eastron Electronic Co.,Ltd. Tel: 0086-573-83698881 Fax: 0086-573-83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn E mail: sales@eastrongroup.com
Environment
Operating temperature - 25℃to +55℃
Storage and transportation temperature to +70 - 40℃ ℃
Reference temperature 23℃±2 ℃
Relative humidity -0 to 95%, non condensing
Altitude 0 up to 2 00m
Warm up time 3s
Installation category CAT II
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total /import/ export
kWh or kVA rh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1 kWh/kVA rh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed to total kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured by the Modbus command.
Baud rate: 1200, 2400, 4800, 9600 bps. Default: 2400 bps
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 18 8 4 x11 x6 (WxHxD) DIN 43880
M ounting DIN rail 35mm
In gress protection IP51 (indoor)
Material -self extinguishing UL94V-0
Product specificaties
Merk: | Eastron |
Categorie: | Meetapparatuur |
Model: | SDM120CT-MV |
Heb je hulp nodig?
Als je hulp nodig hebt met Eastron SDM120CT-MV stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Meetapparatuur Eastron

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025

23 Mei 2025
Handleiding Meetapparatuur
- Meetapparatuur Sonel
- Meetapparatuur Omnitronic
- Meetapparatuur Hazet
- Meetapparatuur Megasat
- Meetapparatuur Flir
- Meetapparatuur Voltcraft
- Meetapparatuur Fluke
- Meetapparatuur TFA
- Meetapparatuur Pioneer
- Meetapparatuur DeWalt
- Meetapparatuur Rossmax
- Meetapparatuur Tempest
- Meetapparatuur Qubino
- Meetapparatuur Livington
- Meetapparatuur Trumeter
Nieuwste handleidingen voor Meetapparatuur

2 Juni 2025

2 Juni 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025

30 Mei 2025