Eastron SDM220-MT Handleiding


Lees hieronder de šŸ“– handleiding in het Nederlandse voor Eastron SDM220-MT (16 pagina's) in de categorie Meetapparatuur. Deze handleiding was nuttig voor 393 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/16
Eastron SDM220-MT User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573- Fax: 0086-573- 83698881 83698882 83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn sales@eastron.com.cn Email:
- -1
SDM220- MT
Single-Phase Mul-Tari Energy Meter
 Measures 4 TARIFFS’ kWh/me.
And Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
 Bi-directional measurement IMP & EXP
 Two pulse outputs
 RS485 Modbus
 Din rail mounng 35 mm
 100A direct connecon
 Beī‡ˆer than Class 1 / B accuracy
User Manual V1.8
2016
Eastron SDM220-MT User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573- Fax: 0086-573- 83698881 83698882 83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn sales@eastron.com.cn Email:
- -2
Applicaon
The energy-meters ā€œwith a blue back-lighted LCD screen for prefect readingā€ are used to measure single-phase like
residenal, ulity and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communicaon port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Speciī…†caon
General Specifications
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) 5A
Max. Current (Imax) 100A
Mini Current (Imin) 2 0. 5A
Starting current 0.4% of Ib
Power consumpon <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
100/10/1 imp/kWh/kVarh (conī…›gurable)
Display LCD with blue backlit
Max. Reading 99999.99kWh
Tariī…ƒ speciī…†caons
Tariī…˜ number 4
Time segments 10
Clock accuracy ≤0.5S (every 24 hours)
Baī‡ˆery Voltage 3.6V DC, ≄1.2Ah
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Acve power 1% of range maximum
Reacve power 1% of range maximum
Apparent power 1% of range maximum
Eastron SDM220-MT User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd. Tel: 0086-573- Fax: 0086-573- 83698881 83698882 83698883
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn sales@eastron.com.cn Email:
- -3
Acve energy Class 1 IEC62053- 21
Class B EN50470-3
Reacve energy 1% of range maximum
Environment
Operang temperature - to +5525ā„ƒ ā„ƒ
Storage and transportaon temperature - to +70 40ā„ƒ ā„ƒ
Reference temperature 223ā„ƒĀ± ā„ƒ
Relave humidity 0 to 95%, non-condensing
Altude up to 2500m
Warm up me 10s
Installaon category CAT II
Mechanical Environment M1
Electromagnec environment E2
Degree of polluon 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is conī…šgurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-conī…šgurable. It is ī…šxed up with total kwh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communicaon parameters can be conī…šgured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 36x90x62 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-exnguishing UL94V-0


Product specificaties