Eastron SDM230-Modbus Handleiding

Eastron Meetapparatuur SDM230-Modbus

Bekijk gratis de handleiding van Eastron SDM230-Modbus (13 pagina’s), behorend tot de categorie Meetapparatuur. Deze gids werd als nuttig beoordeeld door 579 mensen en kreeg gemiddeld 4.4 sterren uit 290 reviews. Heb je een vraag over Eastron SDM230-Modbus of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/13
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -1
SDM230-Modbus
Single-Phase Two Module DIN rail Meters
Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounng 35 mm
100A direct connecon
Beer than Class 1 / B accuracy
User Manual V1.4
2015
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -2
Applicaon
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residenal, Ulity and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communicaon port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Specicaon
General Specicaons
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) A 10
Max. Current (Imax) 100A
Mini Current (Imin) 5A 0.
Starting current 0.4% of Ib
Power consumpon <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
1000/100/10/1 imp/kWh/kVarh (congurable)
Display LCD with blue backlit
Max. Reading 999999.9kWh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Acve power 1% of range maximum
Reacve power 1% of range maximum
Apparent power 1% of range maximum
Acve energy Class 1 IEC62053- 21
Class B EN50470-3
Reacve energy 1% of range maximum
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -3
Environment
Operang temperature - to +5525℃ ℃
Storage and transportaon temperature - to +70 40℃ ℃
Reference temperature 23℃±2
Relave humidity 0 to 95%, non-condensing
Altude up to 2500m
Warm up me 10s
Installaon category CAT III
Mechanical Environment M1
Electromagnec environment E2
Degree of polluon 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is congurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-congurable. It is xed up with import kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communicaon. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communicaon parameters can be congured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 36x99x63 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0


Product specificaties

Merk: Eastron
Categorie: Meetapparatuur
Model: SDM230-Modbus

Heb je hulp nodig?

Als je hulp nodig hebt met Eastron SDM230-Modbus stel dan hieronder een vraag en andere gebruikers zullen je antwoorden