CyberPower Smart App Online OL10KRT Handleiding

CyberPower UPS Smart App Online OL10KRT

Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower Smart App Online OL10KRT (47 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 31 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/47
©2020 Cyber Power Systems, Inc. All rights reserve. K01-0000754-02
SAVE TH E INST CTIONSES RU
Please read this m l and follow the instructions for ins llation d operation.anua ta an
INSTALLATION AND OPERATION NUALMA
SMART APP ONLINE
UPS SYSTEM
OL RT | OL8KRT | OL10KRT6K
II
©2 e f th020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are th property o eir respective owners.
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of
the UPS and batteries.
The Smart App Online 6-10kVA UPS models that are covered in this manual are intended for installation in
an environment within 32°F to 104°F (0°C to 40°C), free of conductive contaminants.
SPECIAL SYMBOLS
Warning: High voltage – Risk of Electric Shock
Caution - Important Instructions: must always be followed.
Do Not Discard: the UPS or UPS batteries in trash. The batteries
contain lead acid. For more information, contact your local recycling
or hazardous waste facility.
Information, advice, help
See applicable user manual
III
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
SAFETY INSTRUCTIONS CONT.
PERSONAL SAFETY
CAUTION
To reduce the risk of fire, connect the UPS to a branch circuit with 40 amperes
(6,000 VA)/50 amperes (8,000 VA)/70 amperes (10,000 VA) maximum over-current
protection in accordance with the National Electric Code, ANSI/NFPA 70.
The AC electrical service where the UPS is connected should be close to the unit and
easily accessible.
Please use only UL-marked mains cable, (e.g. the mains cable of your equipment), to
connect the UPS to the AC outlet.
Please use only UL-marked power cables to connect any equipment to the UPS.
When installing the equipment, ensure that the sum of the leakage current of the UPS
and the connected equipment does not exceed 3.5mA.
Do not unplug the unit from AC power during operation, as this will disconnect the
protective ground insulation.
Do not use an improper size power cord as it may cause damage to your equipment
and cause fire hazards.
Make sure everything is turned o and disconnected completely before conducting
any maintenance, repairs or shipment.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT
OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS
OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY
PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS.
KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
FOR PERMANENTLY CONNECTED EQUIPMENT, A READILY ACCESSIBLE
DISCONNECT DEVICE SHALL BE INCORPORATED IN THE BUILDING
INSTALLATION WIRING.
RISK OF ELECTRIC SHOCK
A battery can present a risk of electric shock and high short circuit current. The
following precaution should be observed when working on batteries:
Remove watches, rings or other metal objects. Use tools with insulated handles.
The UPS must be connected to a grounded AC power outlet with fuse or circuit
breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you
need to power-drain this equipment, turn o and unplug the unit.


Product specificaties

Merk: CyberPower
Categorie: UPS
Model: Smart App Online OL10KRT
Kleur van het product: Zwart
Gewicht: 103000 g
Breedte: 433 mm
Diepte: 660 mm
Hoogte: 266 mm
Geluidsniveau: 65 dB
Materiaal behuizing: Staal
LED-indicatoren: Ja
Vormfactor: Rackmontage/toren
USB-poort: Ja
Meegeleverde kabels: Phone (RJ-11), Serial, USB cable
Accu/Batterij voltage: 12 V
Aantal USB 2.0-poorten: 1
Soort serieële aansluiting: RS-232
Aantal Ethernet LAN (RJ-45)-poorten: 2
Ondersteund aantal accu's/batterijen: 20
RS-232 port: 1
Geluidsalarm(en): Ja
Duurzaamheidscertificaten: RoHS
Uitgangsvermogen: 10000 W
Batterij capaciteit: 9 Ah
Temperatuur bij opslag: -20 - 45 °C
ECO mode: Ja
Stroomspanning bescherming: Overload, Short circuit
Frequentie: 40 - 70 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Snelle installatiehandleiding: Ja
Veiligheid: UL 1778 5th Ed., CSA C22.2 NO.107.3-05, FCC 5 A
Hoogte, in bedrijf: 0 - 3000 m
Hoogte bij opslag: 0 - 15000 m
Rubberen voetjes: Ja
Modem (RJ-11) poort: 2
Rackcapaciteit: 6U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Surge energy rating: 2430 J
Aantal AC uitgangen: 4 AC-uitgang(en)
Stopcontacttypes: NEMA L6-30R, Terminal
Rekbevestigingspakket: Ja
Output power capacity: 10 kVA
Ingang operation voltage (min): 120 V
Ingang operation voltage (max): 280 V
Uitgang operation voltage (min): 200 V
Uitgang operation voltage (max): 240 V
Crest factor: 3:1
UPS-topologie: Dubbele conversie (online)
Typische backup tijd op halve lading: 10 min
Typische backup tijd op volledige lading: 3.6 min
Hot-swap batterij: Ja
Seriële interface: Ja
Output frequentie: 50/60 Hz
Hoorbare alarmstanden: Alarm when on battery, Fault, Low battery alarm, Overload alarm
Emergency Power Off (EPO): Ja
Input vermogensfactor: 0.99
EMI/RFI geluidsfiltering: Ja
Golfvorm: Sinus
Noodstop-aansluiting (EPO): Ja
Koude start: Ja
Oplaadduur batterij: 5 uur
Output vermogensfactor: 1
USB-poorttype: USB Type-B
Overdrachtstijd (Lijnmodus naar batterijmodus): 0 ms
Overbelastingscapaciteit (1 minuut): 125 procent
Overbelastingscapaciteit (10 seconden): 130 procent

Heb je hulp nodig?

Als je hulp nodig hebt met CyberPower Smart App Online OL10KRT stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding UPS CyberPower

Handleiding UPS

Nieuwste handleidingen voor UPS