Bekijk gratis de handleiding van Henry Engineering Back Failsafe (2 pagina’s), behorend tot de categorie UPS. Deze gids werd als nuttig beoordeeld door 3 mensen en kreeg gemiddeld 4.4 sterren uit 4 reviews. Heb je een vraag over Henry Engineering Back Failsafe of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

BackUPS
FAILSAFE UPS POWER SWITCH
DESCRIPTIONRead this manual thoroughly before installation or use.
BackUPS is a power controller for ensuring reliable AC power to critical equipment that is powered with an Uninterruptible
Power Supply (UPS). BackUPS constantly monitors the output of the UPS, and automatically bypasses the UPS if its
output fails or becomes unstable. This keeps the load powered-up, and allows the UPS to be disconnected for battery
replacement or other maintenance. BackUPS provides a Status output for remote monitoring, and can Bypass the UPS
via a remote GPI input. BackUPS can also be used as a “Remote Reboot” device, to remotely reset equipment.
THEORY OF OPERATION
BackUPS has two AC inputs: LINE and UPS. Line is connected to a local AC socket. The UPS input is also connected
to this socket, and the UPS output is connected to the UPS input on the BackUPS unit. Whenever the UPS is operating,
its output is sent to the LOAD via the duplex outlet on the BackUPS. If the UPS output fails, BackUPS will instantly bypass
the UPS, and route direct-LINE power to the load.
Whenever the UPS powers-up, the DELAY TIMER is activated. BackUPS monitors the UPS during the Delay Time
interval, which is set via DIP switches. If UPS power is stable during this interval the UPS will be enabled, supplying
power to the LOAD. Any interruption during or after the Delay will cause the unit to instantly bypass the UPS.
INSTALLATION
BackUPS is supplied with two power cables. Plug the longer cable into a local AC outlet, and plug other end into the IEC
connector labeled INPUT FROM LINE. Plug the shorter cable into the output of the UPS, and plug the other end into the
IEC connector labeled INPUT FROM UPS. Connect the UPS input to the local AC outlet. The load should be plugged
into the duplex outlet on the back of the BackUPS unit.
SETUP
The DELAY TIME DIP switches are used to set the Delay Time and optional modes, as follows:
Switches 1 thru 7 set the Delay Time. See the chart on the top cover, and set one switch down to select the time desired.
There are two Delay Time ranges: HI and LO. Set Switch 8 to select either range: UP=HI, DOWN=LO.
To completely disable the delay timer, set Switch 9 down. (Leave this switch UP for initial installation.)
To enable the Fast Reset mode, set Switch 10 down. (Leave this switch UP for initial installation.)
OPERATION
BackUPS has three modes of operation, set by the MODE switch:
DEL: In Delay mode, BackUPS instantly switches to LINE power if the UPS fails or becomes unstable. When the UPS
powers-up, the Delay Timer monitors its output. If the UPS output is stable during the Delay interval, the UPS will be
switched back online after the Delay interval times-out.
AUT:In Automatic mode, BackUPS instantly switches to LINE power if the UPS fails. When the UPS powers-up,
BackUPS instantly switches back to UPS power. There is no Delay Timer function (even if DIP switch #9 is up).
BYP: In Bypass mode, BackUPS bypasses the UPS at all times, sending LINE power to the LOAD. Select this mode to
remove the UPS for battery replacement or other maintenance.
LEDs provide visual confirmation of BackUPS operation, as follows:
The RED LEDs indicate presence of AC power at the two inputs and at the duplex output socket.
The GREEN LED indicates when the UPS is active and is supplying power to the load. If the green LED is off, the UPS is
bypassed and the load is being powered via the LINE input.
The BLUE LED shows the status of the Delay Timer: If it’s flashing, the timer is operating. When the timer has “timed-out”,
the blue LED will be solid-on. If the Timer is disabled (switch #9 down), the blue LED will be off.
To check/restart the timer: Unplug the INPUT FROM UPS, wait about one second, then plug it back in. The BLUE LED
will flash during the Delay interval. Another way to restart the timer is to momentarily set Switch #9 down, then back up.
Note that the timer will function only if the UPS output is on. (Red UPS LED must be on.)
HENRY ENGINEERING
PO Box 3796
Seal Beach, CA 90740
Tel: 562.493.3589
www.henryeng.com
TM
Product specificaties
| Merk: | Henry Engineering |
| Categorie: | UPS |
| Model: | Back Failsafe |
Heb je hulp nodig?
Als je hulp nodig hebt met Henry Engineering Back Failsafe stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Henry Engineering
26 Maart 2026
Handleiding UPS
Nieuwste handleidingen voor UPS
26 Maart 2026
26 Maart 2026
23 Maart 2026
13 Maart 2026
13 Maart 2026
21 Februari 2026
21 Februari 2026
21 Februari 2026
21 Februari 2026
21 Februari 2026