IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC
power outlet with fuse or circuit breaker protection. DO NOT
plug the UPS into an outlet that is not grounded. If you need to
power-drain this equipment, turn oļ¬€ and unplug the unit.
CAUTION! The battery can power hazardous components
inside the unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed near the connected
equipment and easily accessible.
CAUTION! To prevent the risk of ļ¬re or electric shock, install
in a temperature and humidity controlled indoor area, free of
conductive contaminants. (Please see speciļ¬cations for
acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric
shock, do not remove cover. No user serviceable parts inside.
Refer servicing to qualiļ¬ed service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric
shock, battery circuit is not isolated from AC power source;
hazardous voltage may exist between battery terminals and
ground. Test before touching.
CAUTION! To reduce the risk of ļ¬re, connect the UPS to a
branch circuit with 10 amperes (OLS1000 / OLS1500) / 16
amperes (OLS2000/ OLS3000) maximum over-current
protection in accordance to CE requirement.
CAUTION! The AC outlet where the UPS is connected should
be close to the unit and easily accessible.
CAUTION! Please use only VDE-tested, CE-marked mains
cable, (e.g. the mains cable of your equipment), to connect the
UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power
cables to connect any equipment to the UPS.
CAUTION! When installing the equipment, ensure that the
sum of the leakage current of the UPS and the connected
equipment does not exceed 3.5mA.
CAUTION! The OLS1000 / OLS 00 / OLS2000 / OLS3000 / 15
Battery module models are only qualiļ¬ed maintenance
personnel may carry out installations.
CAUTION! Do not unplug the unit from AC Power during
operation, as this will invalidate the protective ground
insulation.
CAUTION! To avoid electric shock, turn oļ¬€ and unplug the
unit before installing the input/output power cord with a ground
wire. Connect the ground wire prior to connecting the line
wires!
CAUTION! Do not use an improper size power cord as it may
cause damage to your equipment and cause ļ¬re hazards.
CAUTION! Wiring must be done by qualiļ¬ed personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE
SUPPORT EQUIPMENT! Under no circumstances this unit
should be used for medical applications involving life support
equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!
To reduce the risk of ļ¬re, do not use with or near aquariums.
Condensation from the aquarium can come in contact with
metal electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in ļ¬re as the battery
may explode.
CAUTION! Do not open or mutilate the battery, released
electrolyte is harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and
high short circuit current. The following precaution should be
observed when working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage.
When the UPS indicators is on, the units may continue to
supply power thus the unitā€™s outlets may have a dangerous
amount of voltage even when itā€™s not plugged in to the wall
outlet.
CAUTION! Make sure everything is turned oļ¬€ and
disconnected completely before conducting any maintenance,
repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety
conductor before any other cables are connected.
WARNING! (Fuses): To reduce the risk of ļ¬re, replace only
with the same type and rating of fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE
EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG
HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND
THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS
HAIR DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
SUPERVISED BY PERSONNEL KNOWLEDGE OF
BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP
UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
Copyright Ā© 20 CyberPower Systems, Inc.12
UNPACKING
2
UPS
Userā€™s manual
Phone line
USB communication cable
Input power cord
Output power cords x2pcs
PowerPanelĀ® Business Edition software CD


Product specificaties

Merk: CyberPower
Categorie: UPS
Model: OLS1500E
Kleur van het product: Zwart
Gewicht: 15300 g
Breedte: 151 mm
Diepte: 225 mm
Hoogte: 394 mm
LED-indicatoren: Ja
Vormfactor: Tower
Accu/Batterij voltage: 12 V
Aantal USB 2.0-poorten: 1
Aantal Ethernet LAN (RJ-45)-poorten: 1
RS-232 port: 1
Meegeleverde software: PowerPanel Business Edition
Uitgangsvermogen: 1200 W
Batterij capaciteit: 9000 Ah
Accu/Batterij oplaadtijd: 5 uur
Stroomspanning bescherming: Overbelasting
Frequentie: 40/70 Hz
Type koeling: Actief
Modem (RJ-11) poort: 1
Stekker: C14 stekker
Auto-herstart: Ja
Efficientie: 95 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Aantal AC uitgangen: 4 AC-uitgang(en)
Stopcontacttypes: C13 stekker
Golf protectie functies: Fax,Modem,Network,Telephone
Output power capacity: 1.5 kVA
Ingang operation voltage (min): 120 V
Ingang operation voltage (max): 280 V
Uitgang operation voltage (min): 208 V
Uitgang operation voltage (max): 240 V
UPS-topologie: Dubbele conversie (online)
Typische backup tijd op halve lading: 14 min
Typische backup tijd op volledige lading: 5 min
Emergency Power Off (EPO): Ja
Golfvorm: Sinus
Koude start: Ja