Apc Smart-UPS On-Line SRC1KXLI Handleiding

Apc UPS Smart-UPS On-Line SRC1KXLI

Lees hieronder de 📖 handleiding in het Nederlandse voor Apc Smart-UPS On-Line SRC1KXLI (28 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 11 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/28
Important Safety Information
Read the instructions carefully to become familiar with the equipment before
trying to install, operate, service or maintain it. The following special
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies
a procedure.
The addition of this symbol to a Danger or Warning safety label
indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical
injury.
User Manual Smart-UPSâ„¢ On-Line
SRC1KXLI
Smart-UPS On-Line SRC1KXLI2
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
Read the Safety Guide supplied with this unit before installing the UPS.
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC
could void the warranty.
• This UPS is for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or
where there is excessive dust or high humidity.
• Do not operate the UPS near open windows or doors.
• Be sure the air vents on the UPS are not blocked. Allow adequate space
for proper ventilation.
Note: Allow 20 cm clearance on both front and rear sides of the UPS.
• Use only the mains and communication cables provided along with the
UPS.
• The equipment is heavy. Always practice safe lifting techniques
adequate for the weight of the equipment.
Electrical safety
• Use tools with insulated handles.
• Do not handle any metallic connector before power has been
disconnected.
• For models with a hardwired input, the connection to the branch circuit
(mains) must be performed by a qualified electrician.
• Output cord connected to the UPS must not exceed 10 meters in length.
• The protective earth conductor for the UPS carries the leakage current
from the load devices (computer equipment). An insulated ground
conductor is to be installed as part of the branch circuit that supplies the
UPS. The conductor must have the same size and insulation material as
Smart-UPS On-Line SRC1KXLI 3
the grounded and ungrounded branch circuit supply conductors. The
conductor will typically be green, with or without a yellow stripe.
• Leakage current for a pluggable, Type A UPS may exceed 3.5 mA when
a separate ground terminal is used.
• The UPS input ground conductor must be properly bonded to protective
earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the
ground conductor must be properly bonded at the supply transformer or
motor generator set.
Battery safety
• Replace batteries with the same number and type of batteries as
originally installed in the equipment.
• Schneider Electric uses Sealed Maintenance-Free (SMF) batteries.
Under normal use and handling, there is no contact with the internal
components of the battery. Over charging, over heating or other misuse
of batteries can result in a discharge of battery electrolyte. Released
electrolyte is toxic and may be harmful to the skin and eyes.
• CAUTION: Before installing or replacing the batteries, remove
conductive jewelry such as chains, wrist watches and rings. High energy
through conductive materials could cause severe burns.
• CAUTION: Do not dispose of batteries in a fire. The batteries may
explode.
• CAUTION: Do not open or mutilate batteries. Released material is
harmful to the skin and eyes and may be toxic.
Hardwire safety
• Check that all branch circuit (mains) and low voltage (control) circuits
are deenergized, and locked out before installing cables or making
connections, whether in the junction box or to the UPS.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• Strain relief is required for all hardwiring (supplied with select
products).
Snap in type strain reliefs are recommended.
• All openings that allow access to UPS hardwire terminals must be
covered. Failure to do so may result in personal injury or equipment
damage.
• Select wire size and connectors according to national and local codes.


Product specificaties

Merk: Apc
Categorie: UPS
Model: Smart-UPS On-Line SRC1KXLI

Heb je hulp nodig?

Als je hulp nodig hebt met Apc Smart-UPS On-Line SRC1KXLI stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding UPS Apc

Handleiding UPS

Nieuwste handleidingen voor UPS