Bekijk gratis de handleiding van Whirlwind PL-PM1RJK1 (4 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 14 mensen en kreeg gemiddeld 4.5 sterren uit 9 reviews. Heb je een vraag over Whirlwind PL-PM1RJK1 of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/4

Whirlwind PL-PM1/PL-PM1RJ Power Meter Technical Information.
Intended Use:
The Whirlwind PL-PM1/PL-PM1RJ Power Meter is intended to monitor 3 phase Y power with three 120 Volt AC legs or
single phase with two 120 Volt AC legs. It is intended to monitor the line side voltage and load current of both portable
AC distribution and permanent power distribution systems.
whirlwind PL-PM1 & PL-PM1RJ Power Meter
Display Mode Description:
ŸApply Power.
ŸThe power on sequence will illuminate all
LEDs on the front panel.
ŸThe Software Revision is then displayed in
the lower right hand display.
ŸMode A Voltage (blue LED) and current
measurements will display.
Mode A Voltage Display (blue LED
reference)
The TOP row of displays will show (left to right):
ŸX Leg to Neutral voltage
ŸY Leg to Neutral voltage
ŸZ Leg to Neutral voltage
ŸSafety Ground to Neutral voltage
Mode B Voltage Display (red LED reference)
The TOP row of displays will show (left to right):
ŸX-Leg to Y-Leg voltage
ŸY-leg to Z-Leg voltage
ŸZ-Leg to X-Leg voltage
ŸFrequency
Amperage Display (mode A and B)
The bottom row of displays will always show:
ŸX-Leg current
ŸY-Leg current
ŸZ-Leg current
ŸNeutral Leg current
Theory of operation: Voltage Measurement:
The first 3 of 4 Voltage displays are the primary voltage
measurements. Normal use is expected to be 3 phase
“Y” with three 120 Volt AC Legs or single phase with two
hot Legs. It also measures Leg to Leg voltages of 208
Volts AC. Maximum voltage Leg to Neutral or Leg to Leg
is 415 Volts AC.
The PL-PM1 also measures Neutral to Ground voltages
th
(4 display, normal mode). The range on the Neutral to
Ground is 0 to 99 Volts AC.
Accuracy is better than 2%, typically 1%.
The Voltage Input connector is a Wago 5 pin model with
the center pin (safety ground) designed to mate first, due
to a longer pin.
The connections are (Left to Right looking at the rear of
the chassis)
1. X- Leg
2. Y-Leg
3. Safety Ground (extended pin)
4. Z- Leg
5. Neutral
Current Measurement:
Current measurement utilizes 4 Current Transformers
part # TRCT600:1. The PL-PM1 presents a 1.5 Ohm
resistive load to the current transformer. It has a 600 to 1
current ratio. At 400 Amps AC in, the coil delivers 0.66
Amps AC. The maximum current the PL-PM1 measures
is 400 Amps AC.
Accuracy is better than 2%, typically 1%.
The Current Input connector is an 8 pin Wago to the PL-
PM1 from the current transformers.
The connections are:
1,2: X-Leg current loop
3,4: Y Leg current loop
5,6: Z-Leg current loop
7,8: Neutral Leg current Loop
Polarity of the current loop inputs does not matter,
although it is recommended to connect the red and black
in a consistent fashion on all the coils.
Frequency Measurement:
The PL-PM1 measures the frequency of the AC line
voltage from 47 Hz to 63 Hz with an accuracy of 0.1 Hz.
For technical assistance:
whirlwind
99 Ling Road - Rochester, New York 14612
800-733-9473 / 585-663-8820 Fax: 585-865-8930
whirlwindusa.com Made in U.S.A.
Product specificaties
| Merk: | Whirlwind |
| Categorie: | Niet gecategoriseerd |
| Model: | PL-PM1RJK1 |
Heb je hulp nodig?
Als je hulp nodig hebt met Whirlwind PL-PM1RJK1 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Whirlwind
7 Oktober 2025
7 Oktober 2025
7 Oktober 2025
7 Oktober 2025
1 Oktober 2025
30 September 2025
30 September 2025
30 September 2025
30 September 2025
30 September 2025
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026
10 Maart 2026