Vemer EVA-2DIN Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Vemer EVA-2DIN (1 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 21 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
3CONNECTION DIAGRAMS
2
V3IS00261–100
DIMENSIONS
1User Manual
TRMS DIGITAL AMMETER
 Read all the instructions carefully
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: info@vemer.it - web site: www.vemer.it
Mod. EVA-2DIN
EVA-R
EVA-2DIN
EVA-R
36 60
45
65
88
5
72 75
72
66
EVA-2DIN
EVA-R
EVM is an electronic device to measure true effective value (TRMS) of
alternate currents in single-phase systems.
Code Model Description
VM257300 EVA-2DIN Ammeter AC 2DIN
VM324100 EVA-R VAmmeter AC 72x72mm
SAFETY WARNINGS
During the installation and operation of the device, proceed in accordance
with the instructions below:
1) The device should be installed by a competent operator following the
connection diagrams carefully
2) Do not power or connect the device if any part of it is damaged
3) The device should be installed in a panel from which no access can be
gained to the terminals after installation
4) The electrical system of the building in which the instrument is to be
installed should have a switch and a protective device against over-currents
5) The device is designed for installations with over-voltage category III and
pollution level 2, in accordance with the EN 61010-1 standard.
6) The device must be installed and put into operation in accordance with the
current regulations regarding electrical systems.
TECHNICAL SPECIFICATIONS
• Power supply
- 230 V AC (-15% ÷ +10%) 50/60Hz
- Maximum consumption: 2 VA
• Current measurements:
- direct connection up to 10A
- resolution: 10mA
- minimum measurable signal: 300 mA
- accuracy: ± 0.5% of full scale ± 1 digit (from 3% to 100% of F.S.)
- maximum power consumption: 1.5 VA
• Terminals for links:
- connection blocks for cables with 6 mm² maximum cables section for EVA-
2DIN
- plug-in terminal block for cables with 2.5 mm² maximum cables section up
for EVA-R
• 3-digits 7-segments LED display for viewing the measured quantity
• Operating temperature: -10°C to + 45°C
• Storage temperature: -20°C to + 70°C
• Relative humidity: 10% to 90% non-condensing
• Insulation: power supply circuits and electrically insulated measurement at
the level of main insulation (EN 61010-1). Accessible parts and other insulated
terminals at reinforced insulation level
• Protection degree: IP20 / IP51 on the front
4OPERATION
During normal operation, the device displays the
measured value of the current.
Error messages
• Memory error: EEE
Indicates a damage of the device that affect the
operation
• Overload Error: KKK
Indicates that the current is higher than the maximum
allowed value: I > 9.99A
Reset is automatic
• Error: 000
Indicates that the measured curent is lower than
300 mA
REFERENCE STANDARS
Conformity to the EU directives:
2014/35/UE (LDV), 2014/30/UE (EMCD)
is declared with reference to the following harmonised standards:
• EN 61010-1, EN 61000-6-2 and EN 61000-6-4
03-2018
5 4 3 12
2
3
0
V
~
5
0
-
6
0
H
z
~
A
+
2
3
0
V
~
5
0
-
6
0
H
z
~
+
A
2
3 4
1
6
7 8
5


Product specificaties

Merk: Vemer
Categorie: Niet gecategoriseerd
Model: EVA-2DIN

Heb je hulp nodig?

Als je hulp nodig hebt met Vemer EVA-2DIN stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Vemer

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd