Tripp Lite PDUMH20HVATNET Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Tripp Lite PDUMH20HVATNET (60 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 37 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/60
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright Š 2019 Tripp Lite. All rights reserved.
Owner’s Manual
Switched/Metered Rack PDU
with Automatic Transfer Switch
Models: PDUMH15AT, PDUMH15ATNET, PDUMH15HVAT,
PDUMH15HVATNET, PDUMH20AT, PDUMH20ATNET,
PDUMH20HVAT, PDUMH20HVATNET
Series Number: AGAC7625
1. Important Safety Instructions 2
2. Installation 3
2.1 Mounting the PDU 3
2.2 Connecting the PDU 3
2.3 Networking the PDU 6
3. Features 7
4. Conguration and Operation 10
4.1 Automatic Transfer Switch 10
5. Technical Support 12
6. Warranty and Product Registration 12
EspaĂąol 13
Français 25
РусскиК
37
Deutsch 49
WARRANTY REGISTRATION
Register your product today and be
automatically entered to win an ISOBAR
surge protector in our monthly drawing!
www.tripplite.com/warranty
21-03-429-933721.indb 1
2
SAVE THESE INSTRUCTIONS
• This manual contains instructions and warnings that should be followed
during the installation, operation and storage of this product. Failure to
heed these instructions and warnings may affect the product warranty.
• Warning: This equipment is compliant with Class A of CISPR 32. In a
residential environment, this equipment may cause radio interference.
CAUTION Only those who are properly trained or qualified to use this device should
do so. Anyone who is not trained or qualified should not use this device unless it is under
the supervision of someone who is properly trained or qualified to do so.
Children must be supervised to ensure that they do not use the device as a toy.
Never use the device if the cord and plug are damaged; if it is not working properly,
or if it has been dropped or damaged, take it to an authorized service center for
inspection and repair.
If the power cord is damaged, it must be replaced by the manufacturer, its authorized
service agent, or by qualified personnel in order to avoid a danger.
• The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or line noise
protection for connected equipment.
• The PDU is designed for indoor use only, in a controlled environment, away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Keep indoor ambient temperature between 32°F and 122°F (0°C and 50°C).
• The PDU must be installed by a qualified technician only.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
• Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
• The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• Individual equipment connected to the PDU should not draw more current than the individual
PDU’s outlet’s rating.
• The total load connected to the PDU must not exceed the maximum load rating for the PDU.
• Do not attempt to modify the PDU, input plugs or power cables.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended.
1. Important Safety Instructions
21-03-429-933721.indb 2
PDUMH15AT, PDUMH15ATNET,
PDUMH20AT, PDUMH20ATNET
PDUMH15HVAT, PDUMH15HVATNET
PDUMH20HVAT, PDUMH20HVATNET
3
Primary InputSecondary Input
Primary Input
Secondary Input
Outlets
PDUMH20AT
PDUMH20ATNET
PDUMH15HVAT
PDUMH15HVATNET
PDUMH15AT
PDUMH15ATNET
Primary Input Primary Input Primary Input Primary Input
PDUMH20HVAT
PDUMH20HVATNET
Primary Input (120V Models) Primary Input (208-240V Models)
2.1 Mounting the PDU
The PDU supports 1U Rack configurations.
Note: The user must determine the fitness of
hardware and procedures before mounting. The PDU
and included hardware are designed for common
rack and rack enclosure types and may not be
appropriate for all applications. Exact mounting
configurations may vary.
1U Rack Mounting: Attach the PDU to the
rack by inserting four user-supplied screws A
through the PDU mounting brackets B and
into the mounting holes of the rack rail as
shown.
2. Installation
B
B
B
A
A
A
2.2 Connecting the PDU
All PDU models include a primary and secondary AC power input (see diagram). The reference
table below lists each model’s primary and secondary inputs:
Model Primary Input Secondary Input
PDUMH15AT NEMA 5-15P (permanent cord) IEC C14 inlet
PDUMH15ATNET NEMA 5-15P (permanent cord) IEC C14 inlet
PDUMH15HVAT* IEC C14 inlet (detachable cord) IEC C14 inlet
PDUMH15HVATNET* IEC C14 inlet (detachable cord) IEC C14 inlet
PDUMH20AT NEMA L5-20P (permanent cord) IEC C20 inlet
PDUMH20ATNET NEMA L5-20P (permanent cord) IEC C20 inlet
PDUMH20HVAT* IEC C20 inlet (detachable cord) IEC C20 inlet
PDUMH20HVATNET* IEC C20 inlet (detachable cord) IEC C20 inlet
*PDU includes one C13 to C14 (PDUMH15HVAT/NET) or two C19 to C20 (PDUMH20HVAT/NET) interconnection
cables for the two primary and secondary inlets, which may be used to connect to upstream UPS sources.
Alternately, the user can supply IEC cables fitted with country-specific plugs.
21-03-429-933721.indb 3


Product specificaties

Merk: Tripp Lite
Categorie: Niet gecategoriseerd
Model: PDUMH20HVATNET
Kleur van het product: Zwart
Gewicht: 4690 g
Breedte: 440.2 mm
Diepte: 375.2 mm
Hoogte: 43.7 mm
Snoerlengte: 3.6 m
Gewicht verpakking: 7710 g
Breedte verpakking: 528.3 mm
Diepte verpakking: 594.4 mm
Hoogte verpakking: 137.2 mm
Materiaal behuizing: Metaal
LED-indicatoren: Ja
Land van herkomst: Taiwan
Certificering: UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico)
Duurzaamheidscertificaten: RoHS
Temperatuur bij opslag: -15 - 50 °C
Hoogte, in bedrijf: 0 - 3000 m
Afmetingen (B x D x H): 439 x 376 x 44 mm
Montage: Horizontaal
Stekker: C20 stekker
Hoeveelheid per (buitenste) hoofdverpakking: 1 stuk(s)
Rackcapaciteit: 1U
AC-ingangsfrequentie: 50 - 60 Hz
Aantal AC uitgangen: 10 AC-uitgang(en)
Nominale input voltage: 200-240 V
Stopcontacttypes: C13 coupler,C19 coupler
Stroom (max.): 20 A
PDU types: Geschakeld
Netspanning, in bedrijf: 200-240 V