W9 1636662 01 A03
02 - 2011
1/4
www.schneider-electric.com
A
B
DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Disconnect all power before servicing
equipment.
Failure to follow these instructions
will result in death or serious injury.
LR97Dppp
0.3 - 1.5 A
1.2 - 7 A
5 - 25 A
20 - 38 A
Relay setting range
LR97D015
LR97D07
LR97D25
LR97D38
Type
Power
supply
(1) Select function by dip switch:
b dip switch 1: 1 phase / 3 phase
b dip switch 2: Manual / Auto reset
Available for 3 phase utilisation only (Dip SW on "3P" position)
Combined signals from red and green LEDs indicate
motor status including trip causes.
Condition
LED Signal (Pulse Chart)
Green LED
On
On
On
Off
Off
Off
Off
Off
Off
Off
On
Red LED
Power on
Starting
Steady state
Overloading
Overcurrent
Trip
Locked rotor
Phase
Loss
L1
L2
L3
2T14T26T3
A1A298NONC9596
Test/Stop
Reset
Relay output
Green LED
(LED OK)
Load
O-Time
D-Time
Red LED
(LED OL)
PLEASE NOTE:
b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
b No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
website at www.schneider-electric.com.
Operating and Function
b LR97D, solid state overload relay, compares motor
current with preset load current threshold (LOAD).
b Three phase motor currents are monitored through
three internal current transformers.
b D-Time counts down and is only available for
motor starting.
During steady state, if motor current is greater than the current setting (overloaded), LR97D
switches its contacts after O-Time.
In case of phase failure and locked rotor, trip delay time is 3 s and 0.5 s respectively.
b For shear-pin (mechanical shock) protection, set O-Time knob to its minimum in order to trip in 0.2-0.3 s.
Product specificaties
| Merk: | Schneider |
| Categorie: | Niet gecategoriseerd |
| Model: | TeSys D LR97D015 |
| Gewicht: | 172 g |
| Breedte: | 45 mm |
| Diepte: | 67.5 mm |
| Hoogte: | 67.5 mm |
| Gewicht verpakking: | 195 g |
| Breedte verpakking: | 76 mm |
| Diepte verpakking: | 69 mm |
| Hoogte verpakking: | 50 mm |
| Internationale veiligheidscode (IP): | IP20 |
| Temperatuur bij opslag: | -30 - 80 °C |
| Frequentie: | 50/60 Hz |
| Bedrijfstemperatuur (T-T): | -25 - 60 °C |
| Nominale input voltage: | 600 V |
| Garantieperiode: | 1.5 jaar |
| Nominale isolatiespanning: | 600 V |
| Nominale impulsweerstandsspanning (Uimp): | 6 kV |
Heb je hulp nodig?
Als je hulp nodig hebt met Schneider TeSys D LR97D015 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Schneider
Schneider Homeline HOM2175SB Handleiding Schneider EVlink Wallbox EVH2S22P02K Handleiding Schneider LC1F1400MD Handleiding Schneider TeSys LT LT4706 Handleiding Schneider XVUC29P Handleiding Schneider TeSys D LR97D25 Handleiding Schneider TeSys GS GS1DD3 Handleiding Schneider EVlink Wallbox EVH2S11P02K Handleiding
Populair in Niet gecategoriseerd
Schneider MTN6705-0008 Handleiding Schneider Express 775 Handleiding Schneider NSYS3D4620P Handleiding