DANGER: Risk of electric shock. Disconnect power before installation.
The Retrot Kit includes LED tube, instruction, eld-applied label.
The product is intended to retrot Type IC or non-IC recessed mount listed
luminaires with instructions to remove the existing trim.
This product must be installed in accordance with the applicable installation code
by a person familiar with the construction and operation of the product and the
hazards involved.
WARNING: Risk of re or electric shock. The electrical rating of these products
luminaire before installation.
WARNING: LED Retrot Kit installation requires knowledge of luminaires electrical
systems. If not qualied, do not attempt installation. Contact a qualied electrician.
WARNING: Install this kit only in the luminaires that has the construction features
and dimensions shown in the photographs and/or drawings.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges
of sheet metal or other sharp objects. Do not make or alter any open holes in an
enclosure of wiring or electrical components during kit installation.
WARNING: To avoid potential re or shock hazard, do not use this retrot kit in luminaires employing shunted bi-pin lamp holders.
Installers should not disconnect existing wires from lamp holder terminals to make new connections at lamp holder terminals. Instead
installers should cut existing lamp holder leads away from the lamp holder and make new electrical connections to lamp holder lead
wires by employing applicable connectors.
Do not use with dimmers.
For use in dry and damp locations only.
Suitable for Type IC or non-IC recessed luminaires with through-branch wiring marked “Max. 4 of 12AWG conductors.”
This device is not intended for use with emergency exits.
8 " AND 12" T9 LED BALLAST
BYPASS CIRCLINE LAMPS
Models: S16500, S16501, S16502, S16503, S16504, S16505
Satco Products, Inc.
Brentwood, NY 11717
INSTALLATION:
Ballast bypass typical conguration.
INSTALLATION AND SAFETY INSTRUCTIONS
IMPORTANT: Read before installing lamp. Retain for future reference.
© Copyright 2019 Satco Products, Inc. 4/19
STEP 1: Remove trim/lens and existing lamp(s) from surface/
recessedxture. Un-install xture housing from junction box
and disconnect the Load and Neutral wires.
STEP 2: Cut the Load (L) and Neutral wire (N) or (L1) from
the ballast leaving an enough wire to reconnect the
120-277V power source. (Figure 1)
STEP 3: Cut all four socket wires on opposite side of
ballast. (Figure 1)
STEP 4: Remove the ballast from xture housing, discard
or recycle.
STEP 5: Strip the Load and Neutral wires from the rst set
of wires that were cut off from the main feed power line
and connect to group wires from the socket. Connect the
Load (L) wires from the socket to power source. Connect
the Neutral (N) or (L1) wires from the socket to the Neutral
from power source.
STEP 6: Use wire nuts to connect the grouped wires from
the previous step to the wires leading to the 120-277V.
STEP 7: Apply re-lamping label on a visible location inside
the xture.
STEP 8: Turn power on at the breaker panel and turn light
switch on.
WIRING:
Figure 1: Single Light
(Before)
Double Light
(Before)
(After)
(After)
X
BALLAST
X
N (L1)
120-277V
L
N (L1)
120-277V
L
BALLAST
N (L1)
120-277V
N (L1)
120-277V
L
N (L1)
L