PowerWalker VFI 1000 C LCD Handleiding


Bekijk gratis de handleiding van PowerWalker VFI 1000 C LCD (5 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 9 mensen en kreeg gemiddeld 4.3 sterren uit 5 reviews. Heb je een vraag over PowerWalker VFI 1000 C LCD of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/5
ENGLISH
PowerWalker VFI 1000 3000 C LCD-
Quick Guide
I. LCD Panel
Display
Indicates the remaining backup me in pie chart.
Indicates the remaining backup me in numbers.
H: hours, M: minute, S: second
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in
details in 3-5 secon.
Indicates that the UPS alarm is disabled.
Indicates the output voltage, frequency or baery voltage.
Vac: output voltage, Vdc: baery voltage, Hz: frequency
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Indicates the UPS connects to the mains.
Indicates the baery is working.
Indicates the bypass circuit is working.
Parameter 1
Parameter 2
Parameter 3
ENGLISH
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Indicates the Baery level by 0-25%, -50%, 51-75%, and 76-26
100%.
Indicates the baery is fault.
Indicates low baery level and low baery voltage.
Indicates the input voltage or frequency or baery voltage.
Vac: Input voltage, Vdc: baery voltage, Hz: input frequency
II. Rear panel view
1.AC input
5.SNMP intelligent slot (opon)
2.Input circuit breaker
6.Output receptacles
3.USB communicaon port
7.Output terminal (only 3kVA unit)
4.RS 232 communicaon port-
III. Communicaon connecon
USB port
RS-232 port
Intelligent slot
Apart from standard USB Port, the UPS is equipped with RS 232. Those two ports do not work -
at the same me.
ENGLISH
IV. Modes and warnings
Warning
Icon
Alarm
Muted
Online mode
No Alarm
N/A
ECO mode
No Alarm
N/A
Frequency Converter
mode
No Alarm
N/A
Baery mode
Sounding every 4 seconds
Yes
Bypass mode
Sounding every 10
seconds
Yes
Standby mode
No Alarm
N/A
Low Baery
Sounding every second
Yes
Overload
Sounding twice every
second
No
Baery is not
connected
Sounding every second
No
Over Charge
Sounding every second
No
Over temperature
Sounding every second
No
Charger failure
Sounding every second
No
Baery fault
Sounding every second
No
Out of bypass voltage
range
Sounding every second
No
Bypass frequency
unstable
Sounding every second
No
EEPROM error
Sounding every second
No
Fault
Connuously sounding
Yes
V. Frequency Converter Mode
When input frequency is within 40 Hz to 70 Hz, the UPS can
be set at a constant output frequency, 50 Hz or 60 Hz. The
UPS will sll charge baery under this mode. Frequency
Converter requires de rang of the UPS Power to 80%.-
VI. Buon operaon
ON/Mute Buon
Press and hold ON/Mute buon for at least 2 seconds to turn on the UPS.
When the UPS is on baery mode, press and hold this buon for at least 5 seconds to


Product specificaties

Merk: PowerWalker
Categorie: Niet gecategoriseerd
Model: VFI 1000 C LCD