Moxa ioLogik R1214-T Handleiding
Moxa Niet gecategoriseerd ioLogik R1214-T
Bekijk gratis de handleiding van Moxa ioLogik R1214-T (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 124 mensen en kreeg gemiddeld 5.0 sterren uit 3 reviews. Heb je een vraag over Moxa ioLogik R1214-T of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/2

–1 –– 2 –– 3 –
P/N: 1802012002011
ioLogik R1200 Series
Quick Installation Guide
Second Edition, April 5 201
Overview
The ioLogik R1200 comes with 2 RS-485 serial ports, which can be
used in one of two ways:
1.For backup or asset monitoring, or
2.As an RS-485 repeater.
The ioLogik R1200 has the industry’s first all--one design and in
provides Automatic Field Configuration via USB. No technical
background is needed, and maintenance is easy since users can
upload a device’s configuration settings and firmware via USB,
without needing to take a PC to the field site.
Model Selection:
ioLogik
DI
DIO
Relay
AI
AO
R1210
16
–
–
–
–
R1212
8
8
–
–
–
R1214
6
–
6
–
–
R1240
–
–
–
8
–
R1241
–
–
–
–
4
Package Checklist
•1 ioLogik R1200 series remote I/O product
•Documentation and software CD
•Quick installation guide (printed)
Specifications
System
Serial IO
2 x -485-2W: Data+, Data-, GND RS
(5-contact terminal block)
Protection
8 KV ESD, 1 KV surge, 3 KV EFT
Protocols
Modbus/RTU
Power Input
24 VDC nominal, 12 to 48 VDC
Wiring
I/O cable max. 14 AWG
Dimensions
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight
under 200 g
Operating Temperature
Standard Models: -10 to 75°C (14 to
167°F)
Wide Temperature Models: -40 to 85°C
(-40 to 185°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative
Humidity
5 to 95% (non-condensing)
Altitude
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to
function properly at higher altitudes.
Standards and
Certifications
UL 508, CE, FCC Class A
Warranty Period
5 years (excluding ioLogik R1214*)
Details
See www.moxa.com/warranty
*Because of the limited lifetime of power relay, products that use
this component are covered by a 2-year warranty.
Communication Parameters (Initial mode)
Parity
None, Even, Odd (default = None)
Data Bits
8
Stop Bits
12 (default = 1),
Flow Control
None, XON/XOFF (default = None)
Baudrate
1200 to 921.6 kbps (default = 9600)
Digital Input
Sensor Type
NPN, PNP, and Dry contact
I/O Mode
DI or Event Counter
Dry Contact
• On: short to GND
• Off: open
Wet Contact
(DI to COM)
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Isolation
3K VDC or 2K Vrms
Counter/Frequency
2.5 kHz, power off storage
Digital Output
I/O Mode
DO or Pulse Output
Pulse Wave
Width/Frequency
0.1 ms / 5 kHz
Over-voltage
Protection
45 VDC
Over-current Protection
2.6 A (4 channels @650 mA)
Over-temperature
Shutdown
175°C (typical), 150°C (min.)
Current Rating
200 mA per channel
Isolation
3K VDC or 2K Vrms
Relay Output
Type
Form A (N.O.) relay outputs, 5A
Contact Rating
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110
VAC
Inductance Load
2 A
Resistance Load
5 A
Breakdown Voltage
500 VAC
Relay On/Off Time
1500 ms (Max.)
Initial Insulation
Resistance
1G min. @ 500 VDC
Expected Life
100,000 times (Typical)
Initial Contact
Resistance
30 milli-ohms (Max.)
Pulse Output
0.3 Hz at rated load
Analog Input
Type
Differential input
Resolution
16 bits
I/O Mode
Voltage / Current
Input Range
0 to 10 VDC, 4 to 20 mA
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -10 and 60°C
± 0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels)
12 samples/sec
Input Impedance
10M ohms (minimum)
Built-in Resistor for
Current Input
120 ohms
Analog Output
Resolution
12 bits
Output Range
0 to 10 VDC, 4 to 20 mA
Voltage Output
10 mA (Max.)
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -40 and 75°C
Load Resistor
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Installation
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik R1200’s
terminal block terminal; connect the ground from the power V+
supply to the V- terminal. Connect the ground pin () if earth
ground is available.
NOTE
For safety reasons, the wires attached to the power should
be at least 2 mm (12 gauge) in diameter.
Product specificaties
| Merk: | Moxa |
| Categorie: | Niet gecategoriseerd |
| Model: | ioLogik R1214-T |
| Stroom: | 0.207 A |
| Soort serieële aansluiting: | RS-485 |
| Relatieve luchtvochtigheid: | 5 - 95 procent |
| Aantal kanalen: | 6 kanalen |
| Afmetingen (B x D x H): | 27.8 x 124 x 84 mm |
| Signaal directie: | Invoer/uitvoer |
| Input voltage bereik: | 12 - 48 V |
Heb je hulp nodig?
Als je hulp nodig hebt met Moxa ioLogik R1214-T stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Moxa
31 Maart 2025
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
2 Augustus 2023
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
5 Februari 2026
5 Februari 2026
5 Februari 2026
5 Februari 2026
5 Februari 2026
5 Februari 2026
5 Februari 2026
5 Februari 2026
4 Februari 2026
4 Februari 2026