I-00753 Rev -
PET-K-EXT
Bonding Kit
Instruction Sheet
Page 1
INSTALLATION
Thank you for purchasing the PET-K-EXT Bonding Kit. Please read these instructions
thoroughly before installing this product.
THANK YOU
HARDWARE/ITEMS SUPPLIED
Protective Earth Terminals (PET) are located on the bottom frame of the enclosure. These terminals are marked
with the symbol. Enclosure accessory parts contain or are provided with bonding points for connection to the
frame / PET. Protective earth and bonding connections shall be in accordance with Article 250 of the National
Electric Code. When removing any bonded accessory for servicing the enclosure, make sure to disconnect the
bonding terminal from the accessory. NOTE: The bonding terminal MUST be reconnected to the accessory when
the part is replaced after servicing.
NOTE: The main protective earth conductor needs to be the first terminal placed on the PET and
this terminal needs to be secured on its own with a nut. (FIGURE A)
Upper Bonding Stud (10-32)
FIGURE B
PARTS LIST
• Extender bonding wire [12 Gauge Wire
(#10 ring terminal to #10 ring terminal) 9”]
• M4 Screw Thread Cutting
• Locking Nut 10-32
QTY
(1)
(1)
(1)
FIGURE A
PET Stud
(1/4”-20)
Lower
Bonding
Studs (10-32)