Light Management Relay insert
with potential-free contact
Ref.-no.: 1201-1 URE
Relay insert with potential-free contact
1. Warning
Caution: The installation and assembly of electrical equipment may
only be performed by a skilled electrician.
Not suitable for disconnecting.
To prevent electric shocks, always shut off the mains supply (by
cutting out the circuit-breaker) before working on the device or
before replacing the lamp.
Non-observance of the installation instructions may cause fire or
other hazards.
2. Function
Relay insert with potential-free contact for the switching of extensive
lighting installations:
• 230 V incandescent lamps.
• 230 V halogen lamps.
The switching actions are triggered by pressing the button attachment of
the relay insert with potential-free contact, the button of extension units or
of radio-control transmitters.
The present operating instructions describe the functions that can be
obtained when used with the manual multi-function pushbutton.
A detailed description of the functions in conjunction with other
attachments or with the remote control can be found in the corresponding
operating instructions.
3. Operation
Press on the TOP, BOTTOM and center surface:
Switching on, switching off (toggling).
Stand: Nov-08 825 548 03
Light Management Relay insert
with potential-free contact
Ref.-no.: 1201-1 URE
4. Installation Instructions
Install the relay insert with potential-free contact in a flushmounting box
as per DIN 49073 (Fig. A).
The connecting terminals of the insert (1) must be at the bottom.
The relay insert with potential-free contact can only be used in
combination with an attachment. Plug the attachment (2) together with
frame (3) on the insert (1).
The electrical contact is established by means of connector (4).
The attachment must be plugged into the insert before switching on the
mains voltage.
Mains failures of more than 1 second will cause the relay insert with
potential-free contact to switch off.
2
Light Management Relay insert
with potential-free contact
Ref.-no.: 1201-1 URE
5. Short-Circuit Protection
For device protection, connect in series a 10 A automatic cut-out.
Connect the relay insert with potential-free contact as shown in Fig. B.
Observe the maximum connected load and the specified load as per
Specifications.
Depending upon the type of installation, reduce the maximum connected
load by:
- 10 % per 5 °C exceeding of the ambient temperature of 25°C.
- 15% for installation in wooden, gypsum plaster or hollow walls.
- 20% for installation in multiple combinations.
Switching from different places, see fig. B.
relay insert with potential-free contact (1), ‘2-wire’ extension insert (2), ‘3-
wire’ extension insert (3), mechanical pushbutton (4), to further
extensions (5), load ,
Observe the technical connection regulations of the power supply
companies.
6. Using Extensions
Control from an extension unit is possible only if the attachment on the
main unit is in place.
‘2-wire’ extension insert: same functions as in case of multi-function
pushbutton on relay insert with potential-free contact
Mechanical key (normally open): ON / OFF (toggling)
Illuminated mechanical pushbuttons must have a separate N terminal.
7. Specifications
Rated voltage: 230 V AC ~, 50 / 60 Hz
Operating temperature: 5 °C ... +35 °C
Connected load:
230 V incandescent lamps: 800 W
230 V halogen lamps: 750 W
Mixed loads of the types of loads specified
Minimum load: 12 V, 100 mA
μ switching contact: relay contact, potential-free, suitable
for switching of a second phase
conductor, not SELV
Number of Extensions:
‘2-wire’ extension insert,
mechanical push-button: unlimited
‘3-wire’ extension insert: 10
Different types of extension units can be combined
Total length of
extension connecting cable: max. 100 m
Circuit-breaker: provide in acc. with local
requirements, do not exceed 10 A
max
3