The JA-82K and JA-80K difference sheet
1.1. Modular system
• The JA-82K main board provides 4 wired inputs. Unused
inputs are not balanced via resistors in terminals. Instead,
they must be switched OFF via DIP switches:
1 2 3 4
ON
OFF
• JA-82K control panel modularity allows custom assembly.
Modules can be plugged in according to whether they are
necessary for the particular installation.
o The JA-82C wired input extension module provides 10
additional wired inputs. Unused inputs must be switched
off by DIP switch, as with main board inputs.
o The JA-82R radio module provides wireless connectivity,
e.g. for wireless detectors.
o Up to 50 devices can be enrolled to the control panel
(including hardwired inputs).
1.2. Wired input connection
• Wiring the terminals can be done as with the JA-80K. A loop
must be balanced via a 1kΩ resistor wired in series with
detectors. Every activation contact must be wired in parallel
to a 1kΩ resistor.
• A single loop allows up to 5 detectors to be wired. However,
it is recommended to use only one detector in one loop so
that the precision of locating alarm sources is not affected.
1 2 3 4
ON
OFF
01
02
COM
03
04
EW
IW
PGX
PGY
GND
A
B
+U
1k
1k
Fig. 1: Wiring an SA-200 magnetic detector
1 2 3 4
ON
OFF
01
02
COM
03
04
EW
IW
PGX
PGY
GND
A
B
+U
1k
1k
Fig. 2: Wiring a JS-20
123 4
ON
OFF
01
02
COM
03
04
EW
IW
PGX
PGY
GND
A
B
+U
1k
1k
Fig. 3: Wiring a JS-25 in one loop
1 2 3 4
ON
OFF
01
02
COM
03
04
EW
IW
PGX
PGY
GND
A
B
+U
1k
1k
1k
1k
Fig. 4: Wiring a JS-25 in two loops
1.3. Wiring an external siren
The EW (external warning) output switches to GND during
alarms (as opposed to the JA-80K). As the primary option for
the JA-82K control panel, an external siren of the type
OS-360A/365A has been designed. Wiring the OS-360/365
siren requires a relay to be connected in the circuit such that
the siren input activation logic is properly adjusted.
01
02
COM
03
04
EW
IW
PGX
PGY
GND
A
B
+U
JA-82K
OS-360/365
1k
1.4. Backing up the system
The control panel can be equipped with a 1.3 Ah to 2.6 Ah
backup battery. Before system installation, consumption of
particular devices should be taken into consideration. Should
the detector consumption significantly shorten the back-up
time, it is appropriate to use a battery with a greater capacity
positioned in an external case with a protected connection.
1.5. Configuration and programming
Use the OLink software for JA-82K programming. The current
version is downloadable from www.jablotron.com, in the
Download/Software section.
The JA-82K and JA-80K difference sheet 2 / 2 MKH51901