Bekijk gratis de handleiding van Intermatic IOS-DOV-DT (6 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.3 sterren uit 5 reviews. Heb je een vraag over Intermatic IOS-DOV-DT of wil je andere gebruikers van dit product iets vragen? Stel een vraag
Pagina 1/6

Dual Technology
PIR/Ultrasonic
In-Wall Occupancy / Vacancy
Sensor Switch
MODEL: IOS-DOV-DT
Ratings:
Input Voltage: 120/277 VAC, 50/60 Hz
Electronic Ballast (LED): 600 VA, 120 VAC; 1385 VA, 277 VAC
Tungsten (Incandescent): 800 W, 120 VAC
Fluorescent / Ballast : 800 VA, 120 VAC
Resistive (Heater): 800 W, 120 VAC
Motor: 1/4 HP, 120 VAC
Time Delay: 15 Sec - 30 Min
Light Level: 10 fc - Daylight
Walk Through Mode: 3 min if no activity after 30 sec
PIR Sensitivity Adjustment: 50% or 100% (DIP switch)
Ultrasonic Sensitivity Adjustment: 30% to 100%
Coverage -PIR: up to 1200 ft
2
(110m
2
)
US: up to 400 ft
2
(37m
2
)
Operation Temperature: 32° - 131° F / 0° - 55° C
No minimum load required
Figure 4
INSTALLATION AND CONFIGURATION INSTRUCTIONS
Figure 1
Figure 2
DESCRIPTION:
The IOS-DOV-DT series Dual Technology Occupancy Sensors In-Wall sensor switch controls
a load based on occupancy, vacancy and ambient light levels. It combines passive infrared
(PIR) and ultrasonic technologies to help avoid false triggering while increasing presence
detection. Selectable modes allow the sensor to turn load ON and hold it ON as long as either
or both technologies detect occupancy. If no movement is detected for a user-specified time
of 15 seconds to 30 minutes, the load is turned OFF. The sensor provides a 180° coverage
pattern, up to 1200 ft
2
(110
m2
) for PIR and 400 ft
2
(37
m2
) for Ultrasonic sensor.
INSTALLATION
1. Make sure power is turned off at main disconnect.
2. Remove existing single pole switch or dimmer installation, if applicable.
3. Remove 3/4” (1.9 cm) of insulation from each circuit conductor. Make sure the ends of
wires are straight.
4. Connect lead wires as shown in WIRING DIAGRAM (see Figure 2): Black lead to Line
(Hot), Red lead to Load wire, White lead to Neutral wire, Green lead to Ground.
5. Gently position wires in wall box, attach sensor switch to the box.
6. Mount device “TOP” up.
7. Restore power at circuit breaker or fuse, wait one minute.
8. Remove the small cover plate by lifting from bottom edge (see Figure 3).
9. Locate the adjustment knobs on the control panel to perform tests and adjustments
(see Figure 4).
10. Replace the small cover plate after testing and adjusting.
11. Attach the wall plate.
Figure 3
WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or fuses before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code
requirements.
• Use COPPER conductors ONLY.
• Indoor dry location use only.
• Do not exceed electrical ratings.
LOCATION/MOUNTING
Since this device responds to temperature changes, care should be taken when mounting
the device. DO NOT mount directly above a heat source, in a location where hot or cold drafts
will blow directly on the sensor, or where unintended motion will be within the sensor’s
field-of-view.
SENSOR ADJUSTMENT
Remove the cover from the sensor.
NOTE: There is a 40 sec warm-up period when power is first applied to unit.
The sensors are factory preset to allow for quick installation in most applications. Follow
this procedure to verify the sensor coverage and customize the settings.
BAND SWITCH
Sensor has the ability to be set as an occupancy or vacancy sensor. The main difference is that when set to
vacancy mode the load will only turn ON with the push button.
Mode
PositionDescriptionReact to the push button
OFF
LeftCircuit is permanently openNone
OCC
CenterOccupancy Mode: Automatic ON, Automatic OFF
after set time delay.
Manually toggles the load
ON/OFF.
VAC
RightVacancy Mode: Manual ON only, Automatic OFF
after set time delay
Manually toggles the load
ON/OFF.
PIR Coverage: 1200 ft
2
(110
m2
)
Ultrasonic Coverage: 400 ft
2
(37
m2
)
Product specificaties
| Merk: | Intermatic |
| Categorie: | Niet gecategoriseerd |
| Model: | IOS-DOV-DT |
Heb je hulp nodig?
Als je hulp nodig hebt met Intermatic IOS-DOV-DT stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Niet gecategoriseerd Intermatic
8 Juni 2026
8 Juni 2026
8 Juni 2026
19 April 2026
18 April 2026
18 April 2026
17 April 2026
16 April 2026
16 April 2026
16 April 2026
Handleiding Niet gecategoriseerd
Nieuwste handleidingen voor Niet gecategoriseerd
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026
8 Juni 2026