Bekijk gratis de handleiding van Intermatic AG6503L3 (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 2 mensen en kreeg gemiddeld 4.3 sterren uit 1.5 reviews. Heb je een vraag over Intermatic AG6503L3 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/2
347/600 VAC Four wire plus Ground
Found in Main Disconnect Switches,
Main Distribution panels, Load Centers
Sub panels and equipment locations.
Line
Line
Line
Neutral
Ground
WHITE
BLACK
BLACK
BLACK
600 VAC Three wire plus Ground
Found at Service Entrances and
Meter Cabinets.
Line
Line
Line
Neutral/Grounded
WHITE
BLACK
BLACK
BLACK
Type 1 installation:
A typical installation of a type 1 SPD will be connected between the secondary of the service transformer and the line side of
the service panel. This installation is intended to be installed without overcurrent protection to the SPD.
Type 2 installation:
A typical installation of a type 2 SPD will be connected to the load side of the service panel and is intended to be installed with
overcurrent protection to the SPD.
1. Determining location:
Ensure conductor lengths are as short and straight as possible for best performance. Do not coil excess wire. The SPD
functions best if all bends in wires are rounded, ideally to a 4” radius. Hard 90 degree bend will reduce efficiency. Cut
all leads to the correct length. Do not coil excess leads.
Install appropriate weatherproof fittings if the unit is to be mounted outside.
Bracket part number AG1BRKT is also available if needed.
2. Connect wires as shown within diagrams. If your application does not match one of the diagrams below consult your
supplier.
3. Ensure all mounting and electrical connections are correct and securely fastened. Once energized the green indicator
LED will be ON.
Maintenance:
AC Voltage SPD:
Periodically check SPD to ensure green indicator LED is ON. If green LED is OFF, protection has diminished and the
SPD should be replaced immediately.
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Model AG65033/AG6503C3/AG6503L3
Type 1 or Type 2 Surge Protection Device (SPD)
347/600 VAC WYE 3 PHASE
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code and/or Canadian Electrical Code requirements.
• Installation and service to be performed by a qualied licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 50,000 rms symmetrical amperes.
• This unit contains no serviceable parts.
WARNING
Risk of Fire or Electric Shock
NOTICE
NOTICE
NOTICE
NOTICENOTICE
Thoroughly read instructions before installing SPD Unit.
This product does not protect against lightning strikes.
• L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité local en vigueur et/ou du Code canadien de l’électricité.
• L’installation et l’entretien doivent être effectués par un technicien ou électricien qualié.
• Convient à un circuit capable de fournir PAS plus de 50 000 A efcaces symétriques.
• Cet appareil ne contient aucune pièce réparable.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
LIMITED PRODUCT WARRANTY
For
INTERMATIC SURGE PROTECTIVE DEVICES
Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing
a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, 1950 Innovation Way, Suite 300,
Libertyville, IL 60048. For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000.
INTERMATIC INCORPORATED
LIBERTYVILLE, ILLINOIS 60048
http://www.intermatic.com
158--02348


Product specificaties

Merk: Intermatic
Categorie: Niet gecategoriseerd
Model: AG6503L3

Heb je hulp nodig?

Als je hulp nodig hebt met Intermatic AG6503L3 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden