Mounting Instructions
Inductive nonflush mountable rectangular switches - adjustable / CSA Div. 2
Nonflush mountable rectangular switches should have a metal-free zone surrounding the sensing face in accordance with the diagrams
shown here.
Metal
B
Sensing Face
‡1.5xB
B = width of sensing face
Sn = nominal sensing range
Metal
B
‡3xSn
‡2xB
Sensing Face
Non-target
backgroundmetal
‡2x
B
B = width of sensing face
Sn = nominal sensing range
B2xB
Sensing Face
B
Metal B = width of sensing face
8xSn
Sensing Face
Sn = nominal sensing range
Wiring
The output of the switch can be programmed normally open or
normally closed. It will be shipped normally open unless specified nor-
mally closed when ordered. To change from normally open to normally
closed, remove the wire from terminal 4 and insert in terminal 5.
To access the terminal block, loosen the four screws on the switch
housing and remove the switch from the base. To remove or insert a
wire into the terminal block, apply firm downward pressure to the top
of one of the numbered rectangular openings with a screwdriver or
similar tool. The pressure from the screwdriver will open the spring
contact enabling you to remove or insert a wire.
Adjustment to Range
Place the target in position where detection is to take place. If the
factory setting of the sensitivity adjustment has not been disturbed,
the indicator LED should be on. Factory setting of the sensitivity range
involves tuning the switch so the LED just turns on when a target is
placed at the maximum sensing range of the switch. The target should
be made of mild steel and be at least as large as the sensing area of
the switch. Further adjustment is not usually required.
If the indicator LED is not on, the application is beyond the range
of the switch. No increase in sensitivity above this setting should
be used even it it seems to work. If there is a known position where
the switch must be off, move the target to that position and observe
that the indicator LED turns off. If it doesn’t, decrease the sensiti-
vity (ccw) until it turns off and continue an additional quarter turn.
Verify that it still turns on when the target is returned to its original
position.
CSA for Hazardous Locations
When wired in accordance with CEC and this mounting instructions.
Class I, Div. 2, Groups A, B, C and D
Class II, Div. 2, Groups E, F and G
Class III, T4
Enclosure: Type 4/4x
Temp. range: -13° to 176°F (-25° to 80°C)
ELECTRICAL
DO NOT operate an incandescent light bulb as a load.
The current inrush when the bulb is cold can cause a
current overload.
DO NOT operate a proximity sensor directly from a
voltage supply without a load. This is a short circuit and
can cause damage. Note: insert a miniature fuse accor-
ding to the technical data sheet, if specified.
Concerning Safety... ifm efector makes every effort to build a de-
pendable product, but every product will eventually fail. Therefore,
your equipment must be designed to prevent property damage and
personal injury if our products fail. ifm efector proximity switches
are not designed to be used as stand-alone devices to protect or
guard human life or limb.
WARNING
Explosion Hazard – substitution of components may impair suitability
of Class 1, Div. 2. Do not disconnect while circuit is live unless area is
known to be non-hazardous.
AVERTISSEMENT
Risque d'explosion - La Substitution de composants peut rendre ce
matérielle inacceptable pour les emplacements de classe I division 2.
Ne pas débrancher tant que le circuit est sous tensions, à moins qu'il
ne s'agisse d'un emplacement non dangereux.
CAUTION
Use only ifm efector conduit adapters (U30029, U30030, U30031) or
other CSA ceritifed conduit adapters.
ATTENTION
Utiliser uniquement les adaptateurs tube d'ifm efector (U30029,
U30030, U30031) ou d'autres adaptateurs tube certifiés par CSA.


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: ID0036

Heb je hulp nodig?

Als je hulp nodig hebt met IFM ID0036 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM DP4302 Handleiding

12 April 2024
IFM

IFM EVCB02 Handleiding

11 Maart 2024
IFM

IFM EVCB03 Handleiding

11 Maart 2024
IFM

IFM EVF666 Handleiding

11 Maart 2024
IFM

IFM TM4599 Handleiding

8 Januari 2024
IFM

IFM ZB0074 Handleiding

8 Januari 2024
IFM

IFM EVF661 Handleiding

8 Januari 2024
IFM

IFM IIP201 Handleiding

7 Januari 2024
IFM

IFM DP4200 Handleiding

7 Januari 2024
IFM

IFM IIP200 Handleiding

7 Januari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd