Haws 7603 Handleiding


Bekijk gratis de handleiding van Haws 7603 (9 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 9 mensen en kreeg gemiddeld 3.9 sterren uit 5 reviews. Heb je een vraag over Haws 7603 of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/9
10/19 Model 7603/7603T/7603T240 Page 1 of 9
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: website: www.hawsco.comhaws@hawsco.com
No. (4) 0510000480
Model 7603/7603T/7603T240
LIMITED WARRANTY
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of . HAWS liability under this warranty one year from date of shipment
shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof,
which shall appear to the Company upon inspection to be of defective material or not of first class
workmanship, provided that claim is made in writing to Haws within a reasonable period after
receipt of the product. Where claims for defects are made, the defective part or parts shall be
delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs,
alterations or replacements, or for any expense connected therewith made by the owner or his
agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any
damages caused by defective materials or poor workmanship, except for replacements, as provided
above. Buyer agrees that Haws has made no other warranties either expressed or implied in
addition to those above stated, except that of title with respect to any of the products or
equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential
damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation and
maintenance instructions provided are adhered to. The units also must be used for the purpose for
which they were intended. This product is intended to supplement fir -aid treatment. Due to st
widely varying conditions, Haws cannot guarantee that the use of this emergency equipment will
prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR GIVEN BY
HAWS.
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1- -640-4297 888
10/19 Model 7603/7603T/7603T240 Page 2 of 9
CAUTION : A GROUND FAULT DEVICE MUST BE USED WITH THIS HEATING DEVICE.
ATTENTION : CE PRODUIT DOIT ÊTRE UTILISÉ AVEC UNE PROTECTION DE MISE À LA
TERRE.
RECOMMENDED TOOLS: Assorted tools as needed for installing power cord (7603T240
only).
LOCATION OF UNIT: The Model 7603/7603T/7603T240 eyewash units should be placed in
close proximity to potential accident areas. It should be clearly identied, free from
obstructions and easily accessible. IMPORTANT: Model 7603 e wash units (non-ye
insulated) shall be protected from freezing. Models 7603/7603T/7603T240 shall not have
internal temperatures exceeding C (100 and shall not be exposed to ambient 38 F)
temperatures exceeding 38°C (100°F). Be careful of direct sunlight.
WARNING: Use only the handles and the tank skirt when lifting or moving this unit;
doing otherwise may damage the unit. Do not lift the eyewash by the insulation blanket
(if installed).
ELECTRICAL CONNECTIONS: (reference manual supplied with heating blanket)
Model 7603T 60 Hz, 1.38A. Requires a three-prong outlet and is supplied with a 120VAC,
heavy-duty 8 foot power cord with GFCI plug. Unit is suitable for installation and use in
NEMA/TYPE 3R areas. Must be used with NEMA/TYPE 3R certied covered outlet (not
supplied). DURING POTENTIAL FREEZING PERIODS INSURE THAT UNIT IS
CONNECTED TO A CONTINUOUS POWER SUPPLY.
Model 7603T240 VAC, 50/60 Hz, 0.64A. Requires a 240VAC outlet and is not supplied 240
with power cord which must be installed by the user. Unit is suitable for installation and use a
in NEMA/TYPE 4 areas. Power connection to be per local code using exible conduit or cable
rated NEMA/TYPE 4 no rigid connection permitted. MUST BE PROTECTED BY Class A a
GROUND FAULT CIRCUIT INTERRUPTER (GFCI). DURING POTENTIAL FREEZING
PERIODS INSURE THAT UNIT IS CONNECTED TO A CONTINUOUS POWER SUPPLY.
NOTICE: Under ideal conditions, Model 7603 eyewash tank should last for 1600 cycles or 30
years, whichever comes rst. Due to diering environments and end user conditions, caution
should be observed and the product should be regularly monitored for wear, corrosion, and/or
rough service, which can shorten the life of the product. The product should be removed om fr
service if any wear or detrimental service issues occur and should, at minimum, be inspected
annually.
AMBIENT TEMPERATURE RATINGS:
-20°F (- °C) TO 100°F (38°C) 29
10/19 Model 7603/7603T/7603T240 Page 3 of 9
INSTALLATION INSTRUCTIONS
NOTE: Instructions apply to all models unless otherwise specied.
STEP 1: Models 7603T/7603T240 : Install the blanket and connect to power source per the
Installation Manual provided with the heating blanket. Make sure eyewash tank is
sitting on the plastic spacers on bottom of the blanket and not crushing the heat
trace cable.
CAUTION DO NOT ENGERIZE THE HEATING BLANKET POWER SOURCE
UNTIL THE EYEWASH IS FILLED WITH FLUSHING FLUID (UP TO FILL LINE).
NOTICE: MODEL 7603T240 REQUIRES MINIMUM NEMA/TYPE 4 COMPLIANT
EQUIPMENT. ALL POWER CONNECTIONS MUST BE MADE ACCORDING TO
NEC/ CEC CODE USING FLEXIBLE CONDUIT OR CABLE RATED FOR
NEMA/TYPE 4 NO RIGID CONNECTION PERMITTED.
STEP 2: Use potable water to ush and drain the tank.
STEP 3: Apply a small bead of Dow Corning 832 sealant around the threaded end of the dip
tube, approximately at the second thread from the end of the tube.
Thread and hand-tighten the dip tube into the bottom of the eyewash plumbing.
STEP 4: Fill the tank with 10 gallons of clean, potable water (note ll line on label or
blanket A Antimicrobial Preservative Haws Model 9082 as directed (see Step 3 ). dd
under Maintenance section).
STEP 5: Place the eyewash plumbing onto the tank opening, with the gasket sandwiched
between the two.
STEP 6: Install the clamp to secure and seal the bottom of the eyewash plumbing to the
tank opening. Tighten clamp bolts to 10 ft. lb. of torque. Tighten each bolt
incrementally until both sides are tightened appropriately. sert cotter pins into In
holes in clamp bolts. NOTE: If the optional Haws Model 8901B was purchased for
this unit, remove the plug from the back of the 7603’s eyewash plumbing and install
drench hose now. Seal this connection with pipe joint sealant PST #567 (Loctite)
(not supplied).
STEP 7: Charge the tank with clean compressed air to 75 PSI through the tire-type air
valve.
STEP 8: Model 7603T/7603T240 : Energize power source and verify operation of heating
blanket. (Refer to Operation Manual supplied with the heating blanket)
STEP 9: Attach the supplied inspection tag to a convenient location on the tank. The unit is
ready for operation.
IMPORTANT SAFETY NOTICE
THE NATIONAL ELECTRICAL CODE REQUIRES GROUND-FAULT EQUIPMENT PROTECTION ON EACH
HEATING CABLE BRANCH CIRCUIT. TO REDUCE THE RISK OF FIRE CAUSED BY DAMAGE OR IMPROPER
INSTALLATION, CIRCUIT BREAKERS SUCH AS SQUARE D QO-EPD AND QOB-EPD OR EQUIVALENT, WITH
A 30mA TRIP LEVEL, SHOULD BE USED. PLEASE SUBSTITUTE THESE BREAKERS WHEREVER
REFERENCE IS MADE TO CONVENTIONAL BREAKERS IN THIS DOCUMENT. ALTERNATIVE DESIGNS
PROVIDING COMPARABLE LEVELS OF GROUND-FAULT PROTECTION MAY ALSO BE ACCEPTABLE.


Product specificaties

Merk: Haws
Categorie: Niet gecategoriseerd
Model: 7603

Heb je hulp nodig?

Als je hulp nodig hebt met Haws 7603 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden