i 6000s Flex
AC Current Probe
Instruction Sheet
Introduction
The i6000s 24 Flex and i6000s 36 Flex C P s (tAC urrent robe he
Probe) are used with oscilloscopes, digital multimeters, recorders
or data loggers. can be used to measure AC current PThe robes
up to 6000 A. The flexible measuring head allows current
measurements on conductors that are hard to reach or
inaccessible using typical on current probes.clamp-
The Probes provide a low voltage (3- V ac) output that is
proportional to the current being measured. The provideProbes
full-scale direct readings for 60 A, 600 A, and 6000 A.
Safety Instructions
A Warning identifies conditions and procedures that are
dangerous to the user. A Caution identifies conditions and
procedures that can cause damage to the Product or the
equipment under test.
 Warning
To prevent electric shock or personal injury:
If the Probes are used in a manner not
specified in these operating instructions,
protection provided by the Probes may be
impaired.
Use the Probes only if qualified.
Use caution during installation and use of the
Probes; high voltages and currents may be
present in circuit under test.
Have maintenance performed by only qualified
service personnel.
Protect the Probes against water and
humidity.
PN 2842359
June 200 7, Rev. 2 6/21 ,
©2007 20- 21 Fluke Corporation. All rights reserved.
S pecifications are subject to change without notice.
All product names are trademarks of their respective companies.
Wear protective clothing and gloves as
required.
Do not install this product on live conductors.
Always de- zenergi e the circuit under test
before installing the flexible measuring head.
Always inspect the electronics unit,
connecting cable, and flexible measuring head
for damage before using the Probe.
Do not use the Probe if damaged.
Always connect Probe to display device
before installing the flexible measuring head.
Never change batteries while measurement
head is installed on conductor.
Use only the provided original or specified
accessories.
Comply with local and national safety codes.
Use personal protective equipment (approved
rubber gloves, face protection, and flame-
resistant clothes) to prevent shock and arc
blast injury where hazardous live conductors
are exposed.
CAT III equipment is designed to protect
against the transients in the equipment in
fixed equipment installations, such as
distribution panels, feeders and short branch
circuits, and the lighting systems in large
buildings.
Symbols
The following table shows the symbols used on the product
and/or in this manual.
Symbol Description
This product complies with the WEEE Directive
marking requirements. The affixed label indicates that
you must not discard this electrical/electronic product in
domestic household waste. Product Category: With
reference to the equipment types in the WEEE
Directive Annex I, this product is classed as category 9
"Monitoring and Control Instrumentation" product. Do
not dispose of this product as unsorted municipal
waste.
WARNING - RISK OF DANGER.
WARNING. HAZARDOUS VOLTAGE. Risk of electric
shock.
Consult user documentation.
Measurement Category III is applicable to test and
measuring circuits connected to the distribution part of
the building’s low voltage MAINS installation.-
Double Insulated
Do not apply around or remove from uninsulated
hazardous live conductors without taking additional
protective measures.
Conforms to European Union directives.
Specifications
Electrical Characteristics
Current Ranges
60 A / 600 A / 6000 A ac rms
Output S ensitivity
(AC Coupled)
50 mV / 5 mV / 0.5 mV per A
Load Impedance
100 k minimum
Accuracy (at 25 ºC)
±1 % of range (45 65 Hz)Hz to
Linearity
(10 % to 100 % of range)
±0.2 % of reading
Noise
8 mV A) ac rms (60
2 mV ac rms (600/6000 A)
Frequency Range
10 Hz to 50 kHz ( 3 dB- typical)
Phase error
< ± (45 Hz to 65 Hz),
±10° (at 20 kHz)
Position sensitivity
From 2 % up to 4 % of range
with cable, depending on
distance from the center (see
figure below). Measurements
closer than 25 mm from the
coupling are typically greater
than 4 % of range.


Product specificaties

Merk: Fluke
Categorie: Niet gecategoriseerd
Model: i6000s Flex

Heb je hulp nodig?

Als je hulp nodig hebt met Fluke i6000s Flex stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Fluke

Fluke

Fluke TiX885 Handleiding

7 December 2023
Fluke

Fluke TiX875 Handleiding

7 December 2023
Fluke

Fluke TiX880 Handleiding

7 December 2023
Fluke

Fluke TiX870 Handleiding

7 December 2023
Fluke

Fluke EI-162BN Handleiding

9 Augustus 2023
Fluke

Fluke CNX C3003 Handleiding

8 Augustus 2023
Fluke

Fluke 80i-2010s Handleiding

8 Augustus 2023
Fluke

Fluke TiS20+ Handleiding

8 Augustus 2023
Fluke

Fluke i1010 Handleiding

8 Augustus 2023

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd