Festo CPX-2ZE2DA Handleiding


Bekijk gratis de handleiding van Festo CPX-2ZE2DA (2 pagina’s), behorend tot de categorie Niet gecategoriseerd. Deze gids werd als nuttig beoordeeld door 44 mensen en kreeg gemiddeld 4.2 sterren uit 5 reviews. Heb je een vraag over Festo CPX-2ZE2DA of wil je andere gebruikers van dit product iets vragen? Stel een vraag

Pagina 1/2
CPX-2ZE2DA
input/output module
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description
8101596
2018-11a
[8101598]
CPX-2ZE2DA input/output moduleEnglish................................
For all available product documentation è www.festo.com/pk
1Intended use
When used in combination with a CPX terminal, the CPX-2ZE2DA input/output
module enables
the processing, analysis and generation of pulses and measured values
the output of signals and voltages.
The module is intended for use in an industrial environment. Outside of industrial
environments, e.g. in commercial and mixed-residential areas, actions to suppress
interference may have to be taken.
The module is exclusively intended for use in CPX terminals from Festo and for
installation in machines or automated systems, and it may only be used as follows:
in perfect technical condition
in original status without unauthorised modifications, except for the adapta
tions described in this documentation
within the limits of the product defined by the technical data (è Chap. 9).
2Safety
This documentation is directed exclusively at technicians trained in control and
automation technology.
Detailed information can be found in the module description
(è P.BE-CPX-2ZE2DA-...) as well as in the CPX system description
(è P.BE-CPX-SYS-...).
Warning
Electric shock
Injury to people, damage to the machine and system.
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).
Observe the general requirements of IEC 60204-1 for PELV circuits.
Use only voltage sources which guarantee reliable electrical isolation of the
operating and load voltage in accordance with IEC 60204-1.
Always connect all circuits for operating and load voltage supplies U
EL/SEN
,
U
VAL
and U
OUT
.
Note
Electrostatic charge
Damage to the internal electronics.
Ensure assembly personnel are electrostatically discharged before
conducting any assembly work.
Note
Take into consideration the specifications and instructions in the module de
scription and the assembly instructions for the components.
Commission the module only if fully mounted and wired.
3Transport and storage conditions
Protect the product during transport and storage from the following
mechanical loads
impermissible temperatures
moisture
aggressive atmospheres.
Only store and transport the product in its original packaging.
4Connection and display components
1
2
3
4
5
6
7
8
aA
aB
9
aJ
aC
aD
aE
Status - inputs for channel 0
1Encoder input 1 (green)
2Encoder input 2 (green)
3Encoder input 3 (green)
4Digital input DI (green)
Status - inputs for channel 1
5Encoder input 1 (green)
6Encoder input 2 (green)
7Encoder input 3 (green)
8Digital input DI (green)
Status - outputs
9Digital output DO channel 0 (yellow)
aJDigital output DO channel 1 (yellow)
Diagnostics
aAModule error (red)
aBDigital output DO channel 0 (red)
aCDigital output DO channel 1 (red)
aDEncoder supply 24 V (red)
aEEncoder supply 5 V (red)
Fig. 1
The assignment illustrated here may vary in individual operating modes.
For details regarding the operating modes, please refer to the module
description.
Fig. 2
Channel 0Channel 1
TerminalAllocationTerminalAllocation
X1.0+X5.0+Encoder input 1Encoder input 1
.1.1
.2+.2+Encoder input 2Encoder input 2
.3.3
X2.0+X6.0+Encoder input 3Encoder input 3
.1.1
.2Encoder supply 5 V
1)
+.2Encoder supply 5 V
1)
+
.3.3
X3.0Encoder supply 24 V
1)
+X7.0Encoder supply 24 V
1)
+
.1.1
.2Encoder supply 24 V
for DI
1)
+.2Encoder supply 24 V
for DI
1)
+
.3.3Digital input DIDigital input DI
X4.0Reference potential for
encoder supply 24 V
for DI
X8.0Reference potential for
encoder supply 24 V
for DI
.1.1Digital output DODigital output DO
.2.2Reference potential for DOReference potential for DO
.3Functional earth (FE)Functional earth (FE).3
1)Protected against short circuit and overload
Fig. 3

Beoordeel deze handleiding

4.2/5 (5 Beoordelingen)

Product specificaties

Merk: Festo
Categorie: Niet gecategoriseerd
Model: CPX-2ZE2DA

Heb je hulp nodig?

Als je hulp nodig hebt met Festo CPX-2ZE2DA stel dan hieronder een vraag en andere gebruikers zullen je antwoorden