Dormakaba RCI 3525PRX Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor Dormakaba RCI 3525PRX (4 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 96 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/4
INSTALLATION
RCI 3525PRX
ELECTROMECHANICAL SERVER RACK HANDLE
WITH PROXIMITY READER
© 2020 dormakaba Canada Inc
www.dormakaba.us • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.comIS3525PRX
PCN2013
R09-20GR-1
Specifications
Package Contents
• 3525PRX Electromechanical Server Rack Handle with
Proximity Reader
• M3x25 Mounting Screws (qty 4)
• M3x14 Mounting Screw
• Rotation Limiter Standard
• Rotation Limiter - Extended (for thicker panels)
• Cam Bolt
• Top Mounting Bracket
• Bottom Mounting Bracket
• Installation Instructions
• Keys (qty 3)
Actuator Module
Supply
Voltage
12VDC to 24VDC (NOTE: Status LED will blink red if
the supply voltage is out of range.)
Standby
Current 50mA maximum at 12VDC"
Operating
Current
200mA maximum at 12VDC (with no external
mechanical load applied to handle)
Stall Current 1A maximum at 12VDC (limited to 2 seconds)
Operating
Transit Time
1 second maximum ( Power must be present NOTE:
during transit times. If power is removed while the lock
slide is in transit, it will complete it’s cycle when power
is restored.)
Electronic
Unlock Time 3 seconds minimum
Open
Collector
Outputs
Rated for supply voltage, maximum load
Alarm
Outputs 100mA/ output maximum
Fig. 1
Data Rack Handle
Proximity Reader
Tri-Color Status LED
Key Cylinder
Proximity Reader Module
Voltage 12VDC to 24VDC
Operating
Current 20mA maximum
Transmit
Frequency 125kHz
DATA Signal
Voltage 5VDC
DATA Pulse
Interval Time 40µs
DATA Signal
Delay 2ms
3525PRX
Overall
Dimensions
8-1/4" H x 1-12" W x 1" D*
210 x 37 x 25mm* (* depth from cabinet face)
2
Rotation Limiter
Viewed from back.
Handle rotation is counter
clockwise from front.
Bottom Mounting Bracket
Viewed from back.
Key rotation is counter clockwise
from front.
Rotation Limiter
Viewed from back.
Handle rotation is
clockwise from front.
Bottom Mounting Bracket
Viewed from back.
Key rotation is clockwise
from front.
Handle Mounting
1. Assemble handle according to the proper handing required.
2. Rotation Limiter & Bottom Mounting bracket determine handing.
(Fig. 3)
3. If existing cam or rod mechanism are installed on original handle
remove and install on new handle. (minimum torque 4Nm)
4. Ensure the proper cutout in the door. (See Fig. 2)
5. Install handle though cutout and install top & bottom mounting
brackets. (Pozidrive with maximum 0.5Nm)
6. Install wiring harness and route to hinge side of door securing in
place to ensure that nothing will bind or catch.
7. Proceed to wiring. (See Figs. 4, 5 & 6)
NOTE:
1. Cut-out dimensions.*
2. Handing is determined by rotation limiter and bottom mounting bracket.
Fig. 2
select appropriate
Rotation Limiter
CAM
Top Mounting
Bracket
CAM Bolt
M3x14mm Screw
(1 place)
M3x25mm Screw
(4 places)
5.9” *
150mm
1” *
25mm
Bottom
Mounting Bracket
Fig. 3
3
Wiring
The 3525PRX contains two separate
functional modules:
The proximity module reads the
contents of a compatible proximity
card and converts it to Wiegand
format.
The actuator module controls and
monitors the locking function of the
swinghandle.
These two modules operate
independently of each other and
require connection to an access
control unit (not provided), to be fully
functional.
The proximity reader module of the swinghandle is accessed with
a four pin connector attached to a harness connected to the module’s
circuit board. The module’s connector pinout is:
Wire Color Description Note
Black GND ground
Red Positive 12 to 24VDC power supply input
Green DATA0 DATA0 output
White DATA1 DATA1 output
The actuator module of the swinghandle is accessed with a six pin
connector on the rear of the unit, shown below.
Wire Color Description Note
Black GND ground
Red Positive 12 to 24 VDC power supply input
Pin 3 no connectN/C
Orange Input Trigger command input (9VDC up to
supply voltage, 100 milliseconds
minimum)
Brown Electronic
Lock Status
open collector output (sink to
ground, 100mA max. load)
Blue Mechanical
Lock Status
open collector output (sink to
ground, 100mA max. load)
Input Trigger
This signal is used to control the electronic lock slide position.
For UNLOCKED position: Supply 9VDC minimum (do not exceed
supply voltage) for at least 100 milliseconds. The lock will remain
unlocked for as long as the signal is present, or a minimum of 3
seconds.
Signal timing can typically be adjusted through the access control
device.
The input trigger current draw is less than 10mA.
Electronic Lock Status Output Signal
This output will provide a 100mA MAX sink to GND when the lock slide
is electromechanically moved to the unlocked position.
Mechanical Lock Status Output Signal
This output will provide a 100mA MAX sink to GND when the handle
is in the open position or when the keylock in the actuator is manually
unlocked.
NOTE: These outputs are open collector outputs rated for input voltage
with a maximum load of 100mA. To avoid damage to the 3525PRX, do
not exceed voltage and current ratings.
Positive Red
GND Black
DATA1 White
DATA0 Green
Positive Red
GND Black
Input Trigger
Electronic Lock Status
Mechanical Lock Status
Fig. 4


Product specificaties

Merk: Dormakaba
Categorie: Niet gecategoriseerd
Model: RCI 3525PRX

Heb je hulp nodig?

Als je hulp nodig hebt met Dormakaba RCI 3525PRX stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Dormakaba

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd