Userโ€™s Manual
Professional Rack Mount UPS
PR1500 / PR2200
๎€ƒ
K01-1500S0A-04
1๎€ƒ
๎€ƒ
TABLE OF CONTENTS
IMPORTANT๎€ƒSAFETY๎€ƒWARNINGS .......................................................................................................2
UNPACKING ......................................................................................................................................... 2
HARDWARE๎€ƒINSTALLATION๎€ƒGUIDE.......................................................................................................2
BASIC๎€ƒOPERATION .............................. ......3........................................................................................
FRONT๎€ƒPANEL๎€ƒDESCRIPTION ................................................................................................................ 3
REAR๎€ƒPANEL๎€ƒDESCRIPTION ................................................................................................................... 5
BATTERY๎€ƒREPLACEMENT ......................... .........................................................7.................................
BATTERY๎€ƒREPLACEMENT๎€ƒPROCEDURE: ................................................................................................8
DEFINITIONS๎€ƒFOR๎€ƒLED๎€ƒINDICATORS...................................................................................................9
TROUBLESHOOTING ................... ................................................................ ....................................10
TECHNICAL๎€ƒSPECIFICATIONS ....... ....... ............... ........................ ................................ ......................11
PRODUCT๎€ƒREGISTRATION........................ ....................................................... 12.................................
1๎€ƒYEAR๎€ƒLIMITED๎€ƒWARRANTY ...........................................................................................................12
CONFORMANCE๎€ƒAPPROVALS ..........................................................................................................15
Thank you for purchasing a CyberPower Systems Product. To enjoy all the
features and benefits of this Uninterruptible Power System (UPS), please
read and follow all installation and operation instructions completely. This
UPS is designed to provide guaranteed power protection for connected
electronic equipment. The accompanying PowerPanel Business Edition
software saves data, closes open applications and automatically shuts
down your computer system in an intelligent and orderly manner.
๎€ƒ
2๎€ƒ
๎€ƒ
๎€ƒ
Important safety warnings
This manual contains important instructions that should be followed during
installation and maintenance of the UPS and batteries. Please read and follow all
instructions carefully during installation and operation of the unit. Read this
manual thoroughly before attempting to unpack, install, or operate.
CAUTION! The UPS must be connected to an AC power outlet with fuse or
circuit breaker protection. DO NOT plug the machine into an outlet that is not
grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT
EQUIPMENT! CyberPower Systems does not sell products for life support or
medical applications. DO NOT use in any circumstance that would affect
operation or safety of any life support equipment, with any medical applications, or
patient care.
CAUTION! The battery can energize hazardous live parts inside even when
the AC input power is disconnected.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature
and humidity controlled indoor area, free of conductive contaminants. (Please see
specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover,
except to service the battery. No user serviceable parts inside, except for the
battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC
power source before servicing the battery or installing a computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of
fire, do not use with or near aquariums. Condensation from the aquarium can
come in contact with metal current contacts and cause the machine to short out.
CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of
laser printers are too large for a UPS.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
UPS Unit; (1) Userโ€™s Manual for UPS; (2) Rack mount Brackets; (2) Stands; (1)
Telephone Cable (1) PowerPanel Business Edition Software CD; (1) Userโ€™s
Manual; (2) Serial Interface Cable (DB-9); (1) Serial-to-USB cable; (1) Warranty
Registration Card.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging
the battery for at least four hours is recommended to insure that the
batteryโ€™s maximum charge capacity is achieved. Charge loss may occur
during shipping and storage. To recharge the battery, simply leave the unit
plugged into an AC outlet. The unit will charge in both the on as well as the off
position.
2. If you wish to use the software, connect the enclosed serial interface cable to
the serial port on the UPS and an open serial port on the computer. If you
would like to use USB interface, please connect the USB adapter with the


Product specificaties

Merk: CyberPower
Categorie: UPS
Model: PR1500SWRM2U
Kleur van het product: Zwart
Gewicht: 26308 g
Aantal USB 2.0-poorten: 1
Aantal Ethernet LAN (RJ-45)-poorten: 1
Certificering: UL1778, cUL, FCC DOC Class B
Geluidsalarm(en): Ja
Responstijd: 4 ms
Uitgangsvermogen: 950 W
Accu/Batterij oplaadtijd: 8 uur
Frequentie: 50/60 Hz
Gewicht (imperiaal): 58 lbs
Bedrijfstemperatuur, bereik: 32 - 95 ยฐF
Afmetingen (B x D x H): 438.15 x 400 x 89 mm
Seriรซle poort(en): 2
Modem (RJ-11) poort: 1
Bedrijfstemperatuur (T-T): 0 - 40 ยฐC
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Afmetingen (B x D x H) (Brits): 17.25 x 15.75 x 3.5 "
Surge energy rating: 1780 J
Input-connectietype: NEMA 5-15P
Output power capacity: 1.5 kVA
Typische backup tijd op halve lading: 15 min
Typische backup tijd op volledige lading: 5 min
Hot-swap batterij: Ja
Output-aansluitingen: NEMA 5-15R
Vervangings-batterij cartridge: BB - BP7-12