CyberPower PDU30SWHVT19ATNET Handleiding

CyberPower Niet gecategoriseerd PDU30SWHVT19ATNET

Lees hieronder de đź“– handleiding in het Nederlandse voor CyberPower PDU30SWHVT19ATNET (8 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 14 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/8
Copyright © 2018 Cyber Power Systems, Inc. All rights reserved.
Automatic Transfer Switch
USER'S MANUAL
4
Product Features
Technical Specifications
Switched Series Metered Series
Model Name PDU15SW10ATNET PDU15SWHVIEC12ATNET PDU15M10AT PDU15MHVIEC12AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 12A 12A(UL)/10A(CE) 12A 12A(UL)/10A(CE)
Plug Type (2) NEMA 5-15P (2) IEC-320 C14 (2) NEMA
5-15P (2) IEC-320 C14
Power Cord Type SR (14 AWG) Socket SR (14 AWG) Socket
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current 12A 12A(UL)/10A(CE) 12A 12A(UL)/10A(CE)
Outlet Type NEMA 5-15R IEC-320 C13 NEMA 5-15R IEC-320 C13
Outlet Number 10 12 10 12
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 1.75" x 9.3"/433mm x 44mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113oF/0oC to 45oC
Safety Approvals
Certifications UL 60950-1
FCC Class A
UL 60950-1
CE, FCC Class A
UL 60950-1
FCC Class A
UL 60950-1
CE, FCC Class A
* All specifications are subject to change without notice.
NEMA Type
IEC Type
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when installed
with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the ATS PDU.
C. Source Indicator
Indicates Source A or B is in use. When both sources are normal, selected
source shows constant green LED while another source shows blinking
green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to
previous menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. Ground Stud
Use to ground the ATS PDU.
J. AC Output Receptacles
Provides power distribution for connected equipment.
K. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected
equipment.
Front/Rear Panel Description (1U 15A Models)
Provides SNMP Card Co mmunication
Expansion Port
Select
Ente r
PDU20SWHVIEC10ATNET
A
B
Source Output
- Normal
- Warning
- Overloa d
QCN-0000003-00
Serial Port
A B C D E F G
H I K
J
H I K
J
SOURC E A SOURC E B
8 9 103 4 6
1 2 3 4 5 6 7 8 9 10 11 12
SOU RCE A
SOU RCE B
6
Provides SNMP Card Communication
Expansion Port
Serial Port
Selec t
Ente r
PDU30SWT17ATNET
A
B
Source Output
- Normal
- Warning
- Overloa d
QCN-0000005-00
B1
B2
B3
A B C D E F G
H
H
K
K
J
I
I
J
L
L
SOURCE A
SOURCE B
BANK 1
(20A)
BANK 2
(20A)
BANK 3
(24A)
L5-30R
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
BANK 1
SOURC E A
SOURC E B
(20A)
BANK 2 (2 0A)
BANK 3 (2 4A)
L6-30R
19
1 2 3 4
10 11 12 13
5 6 7 8
14 15 16 1 7
9
18
NEMA Type
IEC Type
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when installed
with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the ATS PDU.
C. Source Indicator
Indicates Source A or B is in use. When both sources are normal, selected source
shows constant green LED while another source shows blinking green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to previous
menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. AC Output Receptacles
Provides power distribution for connected equipment.
J. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected equipment.
K. Circuit Breaker
Provides output overload protection.
L. Ground Stud
Use to ground the ATS PDU.
Technical Specifications
Switched Series Metered Series
Model Name PDU30SWT17ATNET PDU30SWHVT19ATNET PDU30MT17AT PDU30MHVT19AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 24A
Plug Type (2) NEMA L5-30P (2) NEMA L6-30P (2) NEMA L6-30P(2) NEMA L5-30P
Power Cord Type SR (10 AWG)
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current 5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
Derated Output Current
(each bank) 20A
Bank Number 2
Outlet Type (16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
(16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
Outlet Number 17 19 17 19
Circuit Breaker Yes
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD
Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113 oF/0
oC to 45
oC
Safety Approvals
Certifications UL 60950-1, FCC Class A
* All specifications are subject to change without notice.
Product Features
Front/Rear Panel Description (2U 30A Models)


Product specificaties

Merk: CyberPower
Categorie: Niet gecategoriseerd
Model: PDU30SWHVT19ATNET
Kleur van het product: Zwart
Gewicht: 7600 g
Snoerlengte: 3 m
LED-indicatoren: Ja
Aantal Ethernet LAN (RJ-45)-poorten: 1
Certificering: UL60950_1 certified by ETL (USA), CSA C22.2 (Canada), FCC Class A
Duurzaamheidscertificaten: RoHS
Temperatuur bij opslag: -15 - 45 °C
Stroomspanning bescherming: Overbelasting
Luchtvochtigheid bij opslag: 0 - 95 procent
Hoogte bij opslag: 0 - 15000 m
Afmetingen (B x D x H): 433 x 236.22 x 88.9 mm
Seriële poort(en): 1
Beheerplatform: SNMP/HTTP
Rackcapaciteit: 2U
AC-ingangsfrequentie: 50 - 60 Hz
Bedrijfstemperatuur (T-T): 0 - 45 °C
Aantal AC uitgangen: 19 AC-uitgang(en)
Nominale input voltage: 200-240 V
Stopcontacttypes: C13 coupler, C19 coupler, NEMA L6-30R
Stroom (max.): 30 A
PDU types: Geschakeld
Netspanning, in bedrijf: 200-240 V

Heb je hulp nodig?

Als je hulp nodig hebt met CyberPower PDU30SWHVT19ATNET stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd CyberPower

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd